2015-01-16 13:16:44RESIDENTIAL (R2) AWNING BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO PROVIDE ORIGINAL SEAL AND SIGNATURE ON
 PLANS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 2- ENGINEER TO SPECIFY ALL DESIGN CRITERIA INCLUDING
 AWNING LOCATION ON THE BUILDING (HEIGHT) AND THE
 EXPOSURE CATEGORY AS REQUIRED BY SEC. 3105.4 OF 2010
 FBC-BUILDING.
  
 3- AWNINGS TO BE APPROVED BY THE DESIGNER OF RECORD.
 SEC. 107.3.4.2 OF CITY AMENDMENTS TO FBC.
  
 4- ARCHITECTURAL DRAWINGS SUBMITTED NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
 (NOTE: DRAWING MAY NOT BE SIGNED AND SEALED IF THE
 ARCHITECT STAMPS THE DRAWING WITH THE REVIEW STAMP
 REQUIRED ON ITEM #3 ABOVE).
  
 5- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE FABRIC COVERED STRUCTURE IS DESIGNED
 FOR A QUICK REMOVAL OR BREAKAWAY ( A SERIES OF CLEAR
 PHOTOGRAPHS SHOWING THE DESIGN AND THE REMOVAL PROCESS
 IS ACCEPTABLE ALSO). SEC. 3105.4.2.1 OF 2010 FBC.
  
 B) PROVIDE LETTER SIGNED BY THE BUILDING OWNER STATING
 THAT THE FABRIC WILL BE REMOVED IN THE EVENT OF 75 MPH
 WINDS. SEC. 3105.4.2.1 FBC.
  