Plan Review Notes
Plan Review Notes For Permit 15010189
Permit Number 15010189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-01-14 09:39:01PERMIT # 15010189
 MASTER # 14100842
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SCALE SIZE IS TOO SMALL FOR A PROPER AND DETAILED
 REVIEW. PLEASE PROVIDE PLANS WITH A 1/8" = 1' SCALE.
  
 2) REVISED AREA WITH A "HONEYCOMB" STYLE CEILING
 APPEARS TO SHOW BOTH PENDANT AND SIDEWALL SPRINKLER
 HEADS AT THE SAME ELEVATION. PLEASE EXPLAIN HOW THIS
 WILL WORK.
  
 3) REVISED AREA WITH A "HONEYCOMB" STYLE CEILING
 APPEARS TO SHOW BOTH A PENDANT AND SIDEWALL SPRINKLER
 HEAD RUNNING OFF OF THE SAME BRANCH LINE. PLEASE
 PROVIDE HYDRAULIC CALCULATIONS TO SUPPORT.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  