Plan Review Notes
Plan Review Notes For Permit 15010077
Permit Number 15010077
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-07 10:35:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE THE NUMBER OF UNITS IN THIS
 STRUCTURE, FBC 107. REVIEW CANNOT BE DONE UNTIL THE
 CODE BOOK TO USE IS DETERMINED (FBC 2010 OR FBC 2010
 RESIDENTIAL).
  
 2. THIS HAS BEEN CLASSIFIED AS A "REPAIR" BY EOR. BASED
 ON SCOPE, IT APPEARS THAT ALL OF THE STAIRS WILL BE
 REBUILT. SEE FBC 2010 EXISTING BUILDING 402 FOR THE
 DEFINITION OF "REPAIR". THIS APPEARS TO BE A LEVEL 1
 ALTERATION. EITHER REVISE PLAN OR CLARIFY THE
 CLASSIFICATION OF REPAIR.
  
  