Plan Review Notes
Plan Review Notes For Permit 15010073
Permit Number 15010073
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-28 17:47:551ST REVIEW: FBC 2010
  
 THE REPLACEMENT WINDOWS DO NOT MEET THE REQUIREMENTS OF
 :
  
 FBC R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
 THE WINDOWS MAY HOWEVER MEEET:
  
 FBC E 604.1 GENERAL.
 MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND
 THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE.
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 PROVIDE ADDITIONAL INFORMATION AS NEEDED.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS AS
 APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  