Plan Review Notes For Permit 15010073 |
Permit Number |
15010073 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-28 17:47:55 | 1ST REVIEW: FBC 2010 | | | | THE REPLACEMENT WINDOWS DO NOT MEET THE REQUIREMENTS OF | | : | | | | FBC R310.1.3 MINIMUM OPENING WIDTH. | | THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES | | (508 MM). | | | | THE WINDOWS MAY HOWEVER MEEET: | | | | FBC E 604.1 GENERAL. | | MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION | | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 601.1 AND | | THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE. | | EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL | | DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT | | REDUCTION IN THE CLEAR OPENING DIMENSIONS OF | | REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED. | | | | PROVIDE ADDITIONAL INFORMATION AS NEEDED. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS AS | | APPLICABLE. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|