Plan Review Notes
Plan Review Notes For Permit 15010067
Permit Number 15010067
Review Stop E
Sequence Number 4
Notes
Date Text
2015-12-30 11:06:10THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. AS PREVIOUSLY STATED, UNTIL THIS IS AUTHORIZED BY
 ZONING, THE ADDITIONAL METER WILL NOT BE APPROVED.
 2. CORRECT THE RISER DIAGRAM AS INDICATED ABOVE,
 ELIMINATING THE NEW METER.
 3. ADDED LOAD AS PRESENTED IS MINIMAL THEREFORE SERVICE
 CALCS ARE WAIVED.
 4. IT IS AMBIENT CONDITIONS NOT WIRE GAUGE THAT
 DETERMINE CONDUCTOR INSULATION. SEE NEC 300.5(B) FOR
 FURTHER DETAILS.
 5. NEC 210.8 REQUIRES THAT ALL RECEPTACLES IN GARAGES
 BE GFCI PROTECTED.
 6. NEC 406.8(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE
 WEATHER SHALL BE LISTED WEATHER-RESISTANT "WR".
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  