2015-08-20 08:43:34 | RESIDENTIAL (R3) GARAGE CONVERSION/ALTERATION THIRD |
| BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- KITCHEN IS NOT ALLOWED BY ZONING. SEE ZONING |
| COMMENTS. REVISE PLANS AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: ALSO, REVISE COVER SHEET . THE WORD APARTMENT |
| SHALL BE REMOVED SINCE APARTMENT IS NOT ALLOWED. |
| |
| 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 3- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) KITCHEN IS NOT ALLOWED BY ZONING. IT NEEDS TO BE |
| REMOVED AND CALCULATIONS REVISED. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| B) THIS IS NOT NEW CONSTRUCTION. IT'S EXISTING. 103.2.2 |
| OF 2010 FBC-ENERGY CONSERVATION. |
| |
| C) ADDRESS SHOWN ON THE ENERGY PERFORMANCE LEVEL |
| DISPLAY CARD IS INCORRECT. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| NOTE: COORDINATE ENERGY CALCULATIONS AND ARCHITECTURAL |
| PLANS TO AVOID CONFLICTS AND DELAYS. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS TO FBC. REVISE AS REQUIRED. PROVIDE |
| VALUATION FOR THE REAR STRUCTURE AND FOR THE MAIN HOUSE |
| SEPARATELY. PROVIDE COPY OF SIGNED CONTRACT FOR ALL |
| SCOPE OF WORK AND COPY OF CONTRACT FOR DESIGN |
| PROFESSIONAL FEES. (REPEAT COMMENT. NOT ADDRESSED). |
| |
| 5- SHEET A2.1: |
| A) REVISE EGRESS WINDOWS NOTES. THE CLEAR HEIGHT |
| DIMENSION IS INCORRECT. THE WRITTEN DIMENSION SAYS |
| "TWENTY- TWO" AND THE NUMBER SAYS "24" INCHES. REVISE |
| AS REQUIRED TO MATCH. SEC. R310 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| B) THE BEDROOM WINDOW SIZE (3'-0" (W) X 5'-0" (H) DON'T |
| CORRESPOND TO WINDOW TYPE (35 SH) SPECIFIED ON THE |
| WINDOW SCHEDULE. REVISE AS REQUIRED. R310 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| C) PROVIDE COMPLIANCE WITH THE REQUIRED HEATING. SEC. |
| R303.8 OF 2010 FBC-RESIDENTIAL. |
| NOTE: MINI SPLIT SYSTEM SHOWN ON PLANS BY THE ENTRY |
| DOOR DOESN'T COMPLY. NEED HEAT IN ALL HABITABLE ROOMS. |
| SEE SEC. R303.8. THERE IS NOT HEATING ON THE BEDROOM. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) WOOD ENTRY DOOR AS SPECIFIED ON PLANS. |
| NOTE: IF NOT USING WOOD DOOR, THEN REVISE DOOR SCHEDULE |
| TO MATCH PRODUCT APPROVAL SUBMITTED. |
| |
| B) HURRICANE SHUTTERS FOR ENTRY DOOR (PRODUCT APPROVAL |
| SUBMITTED IS FOR NON-IMPACT DOOR). AND PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| |
| 7- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |