Plan Review Notes
Plan Review Notes For Permit 14120915
Permit Number 14120915
Review Stop P
Sequence Number 3
Notes
Date Text
2015-09-09 09:00:17THIS STRUCTURE WAS CITED FOR PLUMBING AND OTHER WORK
 (ELECTRICAL, BUILDING,MECHANICAL) DONE WITHOUT THE
 PROPER PERMITS OR INSPECTIONS.THE SUBMITTED PLANS ARE
 FOR AN "AS-BUILT" CONDITION. THIS IS NOT ACCEPTABLE FOR
 THIS APPLICATION. A SET OF PLANS SHALL BE SUBMITTED
 THAT SHOWS AN EXISTING FLOOR PLAN WITH ALL THE
 UNPERMITTED WORK THAT IS TO BE REMOVED AND THE PROPOSED
 FLOOR PLAN WITH THE UNPERMITTED WORK REMOVED. THERE IS
 NO WAY OF KNOWING IF ANY UNPERMITTED NON-COMPLIANT WORK
 IS REMAINING AND BEING CLASSIFIED AS "EXISTING" ON THE
 "AS-BUILT" PLANS. THE ENTIRE SCOPE OF WORK SHALL BE
 DONE WITH ONE SET OF PLANS. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.3.
  