Plan Review Notes
Plan Review Notes For Permit 14120915
Permit Number 14120915
Review Stop E
Sequence Number 2
Notes
Date Text
2015-01-21 15:27:021/21/2015
 PROJECT: 827 BRIGGS
 PERMIT#: 14120915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PLAN VIEW INDICATES ELECTRICAL OUTLETS. THE
 ELEVATION VIEW DOES NOT. PLEASE MAKE THE PLANS
 CONSISTANT.
  
 2) THERE ARE ADDITIONAL SHEETS INDICATING AN ELECTRICAL
 SERVICE AND A WATER HEATER. PROVIDE A SITE PLAN AND A
 FLOOR PLAN INDICATING THE LOCATION OF THE ELECTRICAL
 SERVICE, THE ELECTRICAL PANEL, AND THE WATER HEATER.
  
 3) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE
 REQUIRED FOR SUBMITTAL. WPB AMENDMENTS TO THE FBC
 107.3.1 THERE IS ONLY ONE DRAWING SUBMITTED FOR THE
 WATER HEATER CONNECTION.
  
 4) THE WATER HEATER CONNECTION PLAN SUBMITTED INDICATED
 THE WATER HEATER AND THE WIRING FEEDING IT ARE ALL
 OUTDOORS. PROVIDE METHODS AND MATERIALS APPROVED FOR
 THE ENVIRONMENT USED FOR THIS WORK.
  
 5) THE RISER DIAGRAM SUBMITTED DOES NOT INCLUDE A MAIN
 DISCONNECT. A DISCONNECT IS REQUIRED TO BE INSTALLED AS
 CLOSE AS PRACTICAL TO THE SERVICE ENTRANCE. INDICATE
 THE LOCATION, TYPE AND SIZE OF MAIN DISCONNECT. NEC
 230.70(A)(1)
  
 6) THE RISER DIAGRAM IS UNCLEAR WITH REGARDS TO THE
 SERVICE ENTRANCE SIZE TYPE AND LOCATION. IF THIS IS
 TRUELY A DUPLEX ELECTRICAL SERVICE WITH TWO 100AMP
 ELECTRICAL SERVICES PROVIDE THE SERVICE ENTRANCE SIZE
 TYPE AND LOCATION.
  
 7) PROVIDE A LOAD CALCULATION INDICATED THE TOTAL
 CONNECTED LOAD FOR THE SERVICE INCLUDING BOTH UNITS.
  
 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. PROVIDE A FLOOR PLAN OF THE UNIT(S)
 INDICATING THE LOCATION FOR THE REQUIRED SMOKE
 DETECTORS.
  
 9) INDICATE ANY ELECTRICAL WORK, OUTLETS LIGHTS AND
 CIRCUITS THAT ARE NEW, ALTERRED, RELOCATED, OR EXISTING
 TO REMAIN ON THE NEW FLOOR PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
 .