Plan Review Notes
Plan Review Notes For Permit 14120915
Permit Number 14120915
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-21 13:13:02REVIEW FROM 14100826:
  
 11/25/2014
 PROJECT: LJUBO
 PERMIT#: 14100826
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ACCORDING TO CODE ENFORCEMENT REPORT CASE # CE
 14070585, THE VIOLATION INCLUDES INTERIOR ALTERATIONS
 /EXTERIOR WORK THAT WAS DONE WITHOUT THE BENEFIT OF
 PERMITS AND INSPECTIONS. THE ELECTRICAL PERMIT CANNOT
 BE ISSUED UNTIL A FULL SET OF PROFESSIONALLY DRAWN
 PLANS DONE BY A DESIGN PROFESSIONAL LICENSED IN THE
 STATE OF FLORIDA IN ACCORDANCE WITH FL. STATUTES 471 &
 481 ARE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW
 AND APPROVAL. THE PLANS SHALL INCLUDE ALL THE
 INFORMATION, DETAILS AND APPROVALS REQUIRED BY SEC.
 107.3.5.3 OF THE WPB AMEND. TO 2010 FL. BLDG. CODE FOR
 PLAN REVIEW FOR THIS STRUCTURE. ELECTRICAL PLAN REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]