Plan Review Notes For Permit 14120909 |
Permit Number |
14120909 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-02-16 11:03:44 | REVIEWED THE UNI-SPAN PARTIAL SHORING PLANS FOR THE 2ND | | LEVEL DECK (POUR #1) SHEETS S-1, S-2,S-3, AND LEVELS | | 3-8 (GRIDLINES #3 THRU #16) FROM LINES H.2 TO R-LINE, | | SHEETS S-4 AND S-5. | | | | | | 1) REQUIRE THE SUBMITTAL OF THE SHORING DESIGN | | CALCULATIONS PURSUANT TO THE FBC, SECTION 107.1/1603.1. | | | | 2) PROVIDE DETAILS/CALCULATIONS FOR GUARD RAIL SYSTEM | | PER THE FBC, SECTION 1607.8. | | | | 3) PLEASE SUBMIT RE-SHORING PLANS FOR REVIEW AND ENSURE | | THAT THE SAME IS REVIEWED BY THE ENGINEER OF RECORD. |
|