Date Text
2015-08-12 06:42:501) SHT.063-AS109 - DETAIL #1 - THE MAXIMUM HEIGHT OF
 THE SINK CABINET SHALL BE 36 INCHES PER THE FAIR
 HOUSING ACT CFR 100.205 (C) (1).ONE OF THE SINKS SHALL
 HAVE A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE
 CENTERED ON THE FIXTURE. SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE PLAN. THE RESPONSE NARRATIVE WHICH REFERS
 TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT APPLICABLE.
 (COMMENT # 6).
 2) SHT. 262-P.003 - THE PLAN STILL SHOWS A GENERATOR
 BUT THE RESPONSE NARRATIVE STATES THE GENERATOR HAS
 BEEN REMOVED FROM THE PERMIT SET. CLARIFY.(SEE PREVIOUS
 REVIEW COMMENT #9).
 3) SHT.074-A101 - THE SINK IN THE ART STUDIO #124 AND
 BREAK ROOM (#167) SHALL COMPLY WITH THE FAIR HOUSING
 ACT CFR 100.205 (C) (1).THE SINKS SHALL HAVE A MAXIMUM
 HEIGHT OF 36 INCHES AND SHALL HAVE A CLEAR FLOOR SPACE
 OF 30" X 48" CENTERED ON THE FIXTURE. SHOW THE REQUIRED
 CLEAR FLOOR SPACES ON THE PLAN. THE RESPONSE NARRATIVE
 WHICH REFERS TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT
 APPLICABLE. (COMMENT#10) .
 4) SHT. 146- A400 - SHOW THE MINIMUM AND MAXIMUM HEIGHT
 DIMENSIONS FOR THE LOCATION OF THE REINFORCEMENT FOR
 THE GRAB BARS. 2ND REQUEST. COMPLY WITH CFR 100.205 (6)
 & ANSI A117.1. (SEE PREVIOUS REVIEW COMMENT #11).
 5) CLARIFY THE RESPONSE NARRATIVE TO MY PREVIOUS REVIEW
 COMMENT #14. THIS PROJECT CLEARLY FALLS UNDER THE FAIR
 HOUSING ACT YET THE RESPONSE FROM PERKINS EASTMAN
 STATES THE A OR B DESIGN SPECIFICATION IS NOT REQUIRED
 SINCE THE PROJECT MEETS FBC-A 233.3.1, EXCEPTION.
 6) SHT. 168-A451 - DETAIL # 10-MEN'S & WOMEN'S
 RESTROOMS - BOTH OF THE AMBULATORY STALLS SHALL HAVE
 GRAB BARS ON NOTH SIDES OF THE STALL PER 2010
 FBC-ACCESS. SEC.604.8.2.3.
 7) SHT. 169-A452 -DETAIL # 020 - THERE ARE NO DETAILS
 FOR THE SEAT IN THE SHOWER IN THE ACCESSIBLE CHANGING
 ROOM. THE SEAT SHALL COMPLY WITH ANSI A117.1 -1986
 SEC.4.24.
 8) SHT. 185-A510 - DETAIL # 2 - SHOW THE REQUIRE KNEE &
 TOE CLEARANCES FOR THE SINK PER ANSI A117.1 - 1986.
 9) SHT. 153-403(A) -DETAIL #2 - SHOW THE REQUIRED 30
 INCHES BY 48 INCHES CLEAR FLOOR SPACE REQUIRED FOR THE
 SHOWER PER THE FHA GUDELINES AND CFR 100.205.
 10) SHOW THE DEPTH OF THE TYPICAL LAVATORY IN THE
 LIVING UNITS. THE LAVATORIES SHALL NOT EXCEED 24 INCHES
 IN DEPTH PER THE FHA GUIDELINES.
 11) SHT. 148-A401B - DETAIL # 1A - SHOW THE DISTANCE
 BETWEEN THE CABINETS . COMPLY WITH THE FHA GUIDELINES
 REQUIREMENT #7 AND CFR 100.205.ALSO, SEE DETAIL #1.
 12) SHT.144-A352 - DETAIL # 9 - CLEARLY IDENTIFY THE
 SCUPPER ON THE DETAIL AND SHOW THE SCUPPER OPENING.
 SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS THAN
 4 INCHES PER 2010 FBC-SEC.1107.3.
 13) PLAN REVIEW COMMENT #24 - THE RESPONSE NARRATIVE
 REFERS TO DRAWINGS # FS-2E & FS-3E. THERE ARE NO SUCH
 DRAWINGS IN THIS PLAN SET. CLARIFY.
 14) WHY ARE PLANS FOR "EDWARD'S PAVILLION" INCLUDED
 WITH THESE PLANS?
 15) SHT. 2075 -A407 IS NUMBERED AS A PHASE II DRAWING
 IN THE NAMING CONVENTION BUT THE PLAN IS LISTED AS
 BEING IN PHASE I ON THE PLAN ITSELF. CLARIFY.REFER TO
 LOWER RIGHT HAND CORNING OF DRAWING. SHT. 2129-P4.02
 WHICH ARE THE RISERS FOR THIS AREA IS NOTED AS PHASE
 II. WHICH IS IT?
 16) SHT.2128-P4.01 - ONE OF THE RISERS IS MISSING ITS
 IDENTIFYING NUMBER.
 17) PLAN REVIEW COMMENT # 35 - SHT. 2126-P201B & 2130-
 P403 - IDENTIFY THE OTHER TWO WATER MAINS AND PROVIDE
 THE PAGE NUMBER FOR THE CONTINUATION POINT.WPB AMEND.
 TO FBC SEC. 107.2.1. THE RESPONSE NARRATIVE REFERS TO
 REVISED SHEETS P001 & P403. THESE SHEETS HAVE NOT BEEN
 REVISED & P003 IS A PLUMBING SITE PLAN. CLARIFY. 2ND
 REQUEST.
 18) PLAN REVIEW COMMENT # 37 - EXPLAIN HOW HALF OF UNIT
 A1C CAN BE LOCATED IN PHASE I AND THE OTHER HALF IN
 PHASE II. THE RESPONSE NARRATIVE NOTES THAT THE ROOM
 NAME HAS BEEN CHANGED TO "STORAGE". THIS HAS NOT BEEN
 DONE. IT IS STILL A LIVING UNIT. CLARIFY.
 19) PLAN REVIEW COMMENT # 39 - SHT.2135-P501 - SHOW THE
 SIZE OF THE COPPER DWV LINE FROM THE WASHING MACHINE.
 THE MINIMUM SIZE SHALL BE 2". THE RESPONSE NARRATIVE
 NOTES THAT THE DETAIL HAS BEEN REMOVED FROM THE SHEET
 BUT IN FACT IT HAS NOT. NOTHING HAS BEEN DONE TO THE
 SHEET IN THE SET. CLARIFY.
 20) PLAN REVIEW COMMENT # 2131-P404 - THE SIZE OF THE
 WATER RISERS DO NOT MATCH FROM THE 9TH TO THE 10TH
 FLOOR. I ASSUME THE LINES ARE BEING REDUCED BECAUSE OF
 THE NUMBER OF FIXTURES AT THE 10TH FLOOR. THE RESPONSE
 NARRATIVE REFERS TO REVISED SHT.P404 BUT THERE IS NO
 REVISED SHEET IN THE SET. REFER TO RISERS #
 24,26,27,29,30 & 31. ALSO , THERE ARE NO PIPE SIZES ON
 THE RISERS ON WATER RISER #24 AT THE TENTH FLOOR
 LEVEL.CLARIFY.
 21) PLAN REVIEW COMMENT # 41 - SHT. 2131-P404 - WATER
 RISER #28 IS NOT SHOWN ON THE PLAN.THE RESPONSE
 NARRATIVE NOTES " SEE REVISED SHEET P404. THERE IS NO
 REVISED SHEET P404 IN THE SET. CLARIFY.
 22) PLAN REVIEW COMMENT # 53 - SHT.261-P002 - SUBMIT
 MANUFACTURER'S SPECIFICATION SHEETS FOR THE ELEVATOR
 SUMP PUMP. COMPLY WITH 2010 FBC-PLUMBING SEC.1003.4 -
 EXCEPTION. THE RESPONSE NARRATIVE NOTES "SEE REVISED
 SHEET P002. THERE IS NO REVISED SHEET P002. CLARIFY.
 23) PLAN REVIEW COMMENT # 55 - SHT.262-P003 - PLUMBING
 KEYNOTE #3 STATES THAT THE COOLING TOWER WATER TO
 DISCHARGE TO THE SANITARY. COOLING WATER CANNOT
 DISCARGE TO THE SANITARY PER CWPB ORD. SECTION 90-126
 (5). COOLING TOWER WATER SHALL NOT DRAIN TO THE
 STORMWATER SYSTEM PER CITY ORD. SEC.90-203. THE NOTE IS
 STILL ON THE PLAN. CLARIFY.
 24) PLAN REVIEW COMMENT # 56 - SHT. 299- P501 SHOW THE
 SIZE OF THE INTERCEPTORS AS 1500 GALS. THE MAXIMUM SIZE
 OF AN INDIVIDUAL GREASE INTERCEPTOR CHAMBER SHALL BE
 1250 GALS. PER 2010 FBC-PLUMBING SEC.1003.5.1.WHEN THE
 CAPACITY IS GREATER THAN 1250 GALLONS, MULTI-CHAMBERED
 GREASE INTERCEPTORS OR GREASE INTERCEPTORS IS SERIES
 SHALL BE REQUIRED.
 25) PLAN REVIEW COMMENT #69 - INDICATE ON THE STORM
 RISER PLANS OR ON SHEETS 275-P105 & 276-P106 THAT THE
 DESIGN OF THE STORM DRAINAGE SYSTEM INCLUDES 1/2 THE
 AREA OF ANY VERTICAL WALLS THAT DIVERTS RAINWATER TO
 THE ROOF. THE DESIGN SHALL ALSO INCLUDE THE SQUARE
 FOOTAGE OF ANY SLOPED ROOF THAT DIVERTS RAINWATER TO
 THE FLAT ROOFS.2010 FBC-PLUMBING SEC.1106.4.
 26) SHT. 268-P101C - THE NOTES AT THE GREASE TRAP ARE
 DIFFICULT TO READ. THERE IS OTHER TEXT OVER TOP OF
 IT.PLEASE CORRECT, WPB AMEND. TO FBC SEC. 107.2.1.
 27) SHT.299-P501 - SHOW THE PIPE SIZES OF ALL SECTIONS
 OF PIPE FOR THE DOMESTIC BOOSTER WATER PUMP,WATER
 SOFTENER AND PRESSURE REDUCING STATION. WPB AMEND. TO
 FBC SEC. 107.2.1.
 28) SHT. 280-P301 - THE SANITARY AND WATER RISERS FOR
 UNIT A1C ARE MISSING THE IDENTIFYING NUMBERS.
 29) SHT.297-P412 - SHOW THE DISTANCE IN DEVELOPED
 LENGTH FROM EACH LINE PRESSURE REGULATOR TO THE MOST
 REMOTE OUTLET AND THE LOAD OF THE SECTION.SHOW THE
 LENGTHS OF EACH SECTION OF PIPE FOR THE 2 PSI SYSTEM
 AND THE LESS THAN 2 PSI SYSTEM. 2010 FBC-FUEL GAS SEC.
 402.4.1, NFPA 54 SEC.6.1.3.
 30) SHT.297-P412 - THE GAS RISER IS SHOWING 4,996 CFH
 ON A 1 1/4" LINE AT 2 PSI. THE SIZING TABLE REFERENCED
 ON THE DRAWING ALLOWS A MAXIMUM OF 1,470 CFH AT 2 PSI
 ON AN 1 1/4" LINE. IT APPEARS THE LINE IS SEVERELY
 UNDERSIZED.THE MINIMUM SIZE SHALL BE 2 1/2 INCHES.
 31) SHT. 297-P412 - THE BTU LOAD AT POINT D ON THE
 DRAWING DOES NOT EQUAL THE SUM OF THE BTU'S OF THE
 LISTED FIXTURES. CLARIFY.
 32) SHOW THE BRANCH LINES TO THE POOL AND KITCHEN AREA
 ON THE GAS RISER DIAGRAM AND SIZE THE LINE AND SUPPLY
 THE BTU LOAD FOR THE BRANCH LINES.WPB AMEND. TO FBC
 SEC. 107.3.5.1.
 33) THE SIZE OF THE GAS LINE TO THE FIREPLACE MAY
 BEREQUIRED TO BE A MINIMUM OF 3/4" PER TABLE 6.2 (A) OF
 NFPA 54.
 34) THE CFH AT THE METER SHOW 5020.3 CFH BUT THE CFH ON
 THE 1 1/4" LINE DOWNSTREAM OF THE METER SHOWS 4,996
 CFH, WHERE DID THE ADDITIONAL LOAD AT THE METER COME
 FROM? CLARIFY.
 35) PLEASE EXPLAIN THE NOTATION OF "8 OZ." ON THE GAS
 DRAWING.
 36) THE PRV 'S SHALL COMPLY WITH THE FBC- FUEL GAS
 SEC.410.2 (4),(5), (6),& 410.3.
 37)THE LINE FROM THE METER TO POINT "B" SHALL BE A
 MINIMUM OF 2 1/2 INCHES PER NFPA 54 TABLE 6.2 (C).
 38) LIST THE CORRECT APPLICABLE GAS SIZING TABLES FOR
 EACH TYPE OF MATERIAL BEING USED . WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
 39) THE BTU LOAD DOWNSTREAM OF OF POINT "D" APPEARS
 INCORRECT. ADDING THE 1,996 CFH FROM THE POOL AND
 KITCHEN AREA TO THE BTU LOAD COMES TO 3,310.3. RE-CHECK
 YOUR CALCULATIONS.(SEE AREA AT 2020.3 CFH). CHECK THE
 ENTIRE SYSTEM FOR CORRECT SIZING.
 40 ) THE BTU LOAD UPSTREAM OF POINT "D" SHOULD BE
 6310.3.I CALCULATE THE ENTIRE BTU LOAD ON THE SYSTEM AS
 7610.3 CFH. CLARIFY.
 41) PVC IS NOT PERRMITED TO BE USED TO VENT REGULATORS
 INDOORS PER FBC-FUEL GAS SEC.403.6.3.
 42.) SHT. 297-P412 - SHOWS THE GAS PIPING BEING
 INSTALLED UNDER THE SLAB. THIS METHOD IS PERMITTTED IF
 THERE IS NO OTHER METHOD TO INSTALL THE PIPING. IF THE
 PIPING CAN BE RUN OVERHEAD THAT IT HOW IT SHALL BE
 INSTALLED. IF THERE IS NO OTHER METHOD, THE
 INSTALLATION SHALL COMPLY WITH 2010 FBC-FUEL GAS
 SEC.404.12.1 OR 404.12.2. THE VENT TO THE ROOF IS NOT
 AN ACCEPTED METHOD.
 43) THE PLAN SHOWS PE PIPE IN THE CONDUIT. PLASTIC PIPE
 SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY PER
 FBC-FUEL GAS SEC.404.15.1.
 44) PLAN REVIEW COMMENT # 77 - SHT. 297-412 - SUBMIT
 CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE WITH 2010
 FBC-FUEL GAS SEC. 304. SUBMIT DETAILS ON THE
 LOCATION/TERMINATION AND TYPES OF GAS VENTS, HEIGHT
 ABOVE THE ROOF, ETC.THE RESPNSE NARRATIVE REFERS TO
 DRAWINGS M206, M503 & M505. THERE ARE NO SUCH DETAILS
 ON M206 AND I COULD NOT FIND A SHEET LABELED M505.
 CLARIFY.
 45) IT APPEARS THAT CALCULATIONS FOR COMBUSTION AIR FOR
 THE GAS SYSTEM HAVE NOT BEEN SUBMITTED. I COULD NOT
 FIND THE CALCULATIONS ON ANY PLANS. CLARIFY.
 46) SHT.332-M504 - DETAIL #3 REFERS TO DETAIL #6 ON
 SHT. 327-M404. THERE IS NO SUCH DETAIL. CLARIFY.
 47) SUBMIT VENT DETAILS FOR THE POOL HEATERS . WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
  
  
 PLUMBING PLAN REVIEW