Date |
Text |
2015-08-12 06:42:50 | 1) SHT.063-AS109 - DETAIL #1 - THE MAXIMUM HEIGHT OF |
| THE SINK CABINET SHALL BE 36 INCHES PER THE FAIR |
| HOUSING ACT CFR 100.205 (C) (1).ONE OF THE SINKS SHALL |
| HAVE A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE |
| CENTERED ON THE FIXTURE. SHOW THE REQUIRED CLEAR FLOOR |
| SPACE ON THE PLAN. THE RESPONSE NARRATIVE WHICH REFERS |
| TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT APPLICABLE. |
| (COMMENT # 6). |
| 2) SHT. 262-P.003 - THE PLAN STILL SHOWS A GENERATOR |
| BUT THE RESPONSE NARRATIVE STATES THE GENERATOR HAS |
| BEEN REMOVED FROM THE PERMIT SET. CLARIFY.(SEE PREVIOUS |
| REVIEW COMMENT #9). |
| 3) SHT.074-A101 - THE SINK IN THE ART STUDIO #124 AND |
| BREAK ROOM (#167) SHALL COMPLY WITH THE FAIR HOUSING |
| ACT CFR 100.205 (C) (1).THE SINKS SHALL HAVE A MAXIMUM |
| HEIGHT OF 36 INCHES AND SHALL HAVE A CLEAR FLOOR SPACE |
| OF 30" X 48" CENTERED ON THE FIXTURE. SHOW THE REQUIRED |
| CLEAR FLOOR SPACES ON THE PLAN. THE RESPONSE NARRATIVE |
| WHICH REFERS TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT |
| APPLICABLE. (COMMENT#10) . |
| 4) SHT. 146- A400 - SHOW THE MINIMUM AND MAXIMUM HEIGHT |
| DIMENSIONS FOR THE LOCATION OF THE REINFORCEMENT FOR |
| THE GRAB BARS. 2ND REQUEST. COMPLY WITH CFR 100.205 (6) |
| & ANSI A117.1. (SEE PREVIOUS REVIEW COMMENT #11). |
| 5) CLARIFY THE RESPONSE NARRATIVE TO MY PREVIOUS REVIEW |
| COMMENT #14. THIS PROJECT CLEARLY FALLS UNDER THE FAIR |
| HOUSING ACT YET THE RESPONSE FROM PERKINS EASTMAN |
| STATES THE A OR B DESIGN SPECIFICATION IS NOT REQUIRED |
| SINCE THE PROJECT MEETS FBC-A 233.3.1, EXCEPTION. |
| 6) SHT. 168-A451 - DETAIL # 10-MEN'S & WOMEN'S |
| RESTROOMS - BOTH OF THE AMBULATORY STALLS SHALL HAVE |
| GRAB BARS ON NOTH SIDES OF THE STALL PER 2010 |
| FBC-ACCESS. SEC.604.8.2.3. |
| 7) SHT. 169-A452 -DETAIL # 020 - THERE ARE NO DETAILS |
| FOR THE SEAT IN THE SHOWER IN THE ACCESSIBLE CHANGING |
| ROOM. THE SEAT SHALL COMPLY WITH ANSI A117.1 -1986 |
| SEC.4.24. |
| 8) SHT. 185-A510 - DETAIL # 2 - SHOW THE REQUIRE KNEE & |
| TOE CLEARANCES FOR THE SINK PER ANSI A117.1 - 1986. |
| 9) SHT. 153-403(A) -DETAIL #2 - SHOW THE REQUIRED 30 |
| INCHES BY 48 INCHES CLEAR FLOOR SPACE REQUIRED FOR THE |
| SHOWER PER THE FHA GUDELINES AND CFR 100.205. |
| 10) SHOW THE DEPTH OF THE TYPICAL LAVATORY IN THE |
| LIVING UNITS. THE LAVATORIES SHALL NOT EXCEED 24 INCHES |
| IN DEPTH PER THE FHA GUIDELINES. |
| 11) SHT. 148-A401B - DETAIL # 1A - SHOW THE DISTANCE |
| BETWEEN THE CABINETS . COMPLY WITH THE FHA GUIDELINES |
| REQUIREMENT #7 AND CFR 100.205.ALSO, SEE DETAIL #1. |
| 12) SHT.144-A352 - DETAIL # 9 - CLEARLY IDENTIFY THE |
| SCUPPER ON THE DETAIL AND SHOW THE SCUPPER OPENING. |
| SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS THAN |
| 4 INCHES PER 2010 FBC-SEC.1107.3. |
| 13) PLAN REVIEW COMMENT #24 - THE RESPONSE NARRATIVE |
| REFERS TO DRAWINGS # FS-2E & FS-3E. THERE ARE NO SUCH |
| DRAWINGS IN THIS PLAN SET. CLARIFY. |
| 14) WHY ARE PLANS FOR "EDWARD'S PAVILLION" INCLUDED |
| WITH THESE PLANS? |
| 15) SHT. 2075 -A407 IS NUMBERED AS A PHASE II DRAWING |
| IN THE NAMING CONVENTION BUT THE PLAN IS LISTED AS |
| BEING IN PHASE I ON THE PLAN ITSELF. CLARIFY.REFER TO |
| LOWER RIGHT HAND CORNING OF DRAWING. SHT. 2129-P4.02 |
| WHICH ARE THE RISERS FOR THIS AREA IS NOTED AS PHASE |
| II. WHICH IS IT? |
| 16) SHT.2128-P4.01 - ONE OF THE RISERS IS MISSING ITS |
| IDENTIFYING NUMBER. |
| 17) PLAN REVIEW COMMENT # 35 - SHT. 2126-P201B & 2130- |
| P403 - IDENTIFY THE OTHER TWO WATER MAINS AND PROVIDE |
| THE PAGE NUMBER FOR THE CONTINUATION POINT.WPB AMEND. |
| TO FBC SEC. 107.2.1. THE RESPONSE NARRATIVE REFERS TO |
| REVISED SHEETS P001 & P403. THESE SHEETS HAVE NOT BEEN |
| REVISED & P003 IS A PLUMBING SITE PLAN. CLARIFY. 2ND |
| REQUEST. |
| 18) PLAN REVIEW COMMENT # 37 - EXPLAIN HOW HALF OF UNIT |
| A1C CAN BE LOCATED IN PHASE I AND THE OTHER HALF IN |
| PHASE II. THE RESPONSE NARRATIVE NOTES THAT THE ROOM |
| NAME HAS BEEN CHANGED TO "STORAGE". THIS HAS NOT BEEN |
| DONE. IT IS STILL A LIVING UNIT. CLARIFY. |
| 19) PLAN REVIEW COMMENT # 39 - SHT.2135-P501 - SHOW THE |
| SIZE OF THE COPPER DWV LINE FROM THE WASHING MACHINE. |
| THE MINIMUM SIZE SHALL BE 2". THE RESPONSE NARRATIVE |
| NOTES THAT THE DETAIL HAS BEEN REMOVED FROM THE SHEET |
| BUT IN FACT IT HAS NOT. NOTHING HAS BEEN DONE TO THE |
| SHEET IN THE SET. CLARIFY. |
| 20) PLAN REVIEW COMMENT # 2131-P404 - THE SIZE OF THE |
| WATER RISERS DO NOT MATCH FROM THE 9TH TO THE 10TH |
| FLOOR. I ASSUME THE LINES ARE BEING REDUCED BECAUSE OF |
| THE NUMBER OF FIXTURES AT THE 10TH FLOOR. THE RESPONSE |
| NARRATIVE REFERS TO REVISED SHT.P404 BUT THERE IS NO |
| REVISED SHEET IN THE SET. REFER TO RISERS # |
| 24,26,27,29,30 & 31. ALSO , THERE ARE NO PIPE SIZES ON |
| THE RISERS ON WATER RISER #24 AT THE TENTH FLOOR |
| LEVEL.CLARIFY. |
| 21) PLAN REVIEW COMMENT # 41 - SHT. 2131-P404 - WATER |
| RISER #28 IS NOT SHOWN ON THE PLAN.THE RESPONSE |
| NARRATIVE NOTES " SEE REVISED SHEET P404. THERE IS NO |
| REVISED SHEET P404 IN THE SET. CLARIFY. |
| 22) PLAN REVIEW COMMENT # 53 - SHT.261-P002 - SUBMIT |
| MANUFACTURER'S SPECIFICATION SHEETS FOR THE ELEVATOR |
| SUMP PUMP. COMPLY WITH 2010 FBC-PLUMBING SEC.1003.4 - |
| EXCEPTION. THE RESPONSE NARRATIVE NOTES "SEE REVISED |
| SHEET P002. THERE IS NO REVISED SHEET P002. CLARIFY. |
| 23) PLAN REVIEW COMMENT # 55 - SHT.262-P003 - PLUMBING |
| KEYNOTE #3 STATES THAT THE COOLING TOWER WATER TO |
| DISCHARGE TO THE SANITARY. COOLING WATER CANNOT |
| DISCARGE TO THE SANITARY PER CWPB ORD. SECTION 90-126 |
| (5). COOLING TOWER WATER SHALL NOT DRAIN TO THE |
| STORMWATER SYSTEM PER CITY ORD. SEC.90-203. THE NOTE IS |
| STILL ON THE PLAN. CLARIFY. |
| 24) PLAN REVIEW COMMENT # 56 - SHT. 299- P501 SHOW THE |
| SIZE OF THE INTERCEPTORS AS 1500 GALS. THE MAXIMUM SIZE |
| OF AN INDIVIDUAL GREASE INTERCEPTOR CHAMBER SHALL BE |
| 1250 GALS. PER 2010 FBC-PLUMBING SEC.1003.5.1.WHEN THE |
| CAPACITY IS GREATER THAN 1250 GALLONS, MULTI-CHAMBERED |
| GREASE INTERCEPTORS OR GREASE INTERCEPTORS IS SERIES |
| SHALL BE REQUIRED. |
| 25) PLAN REVIEW COMMENT #69 - INDICATE ON THE STORM |
| RISER PLANS OR ON SHEETS 275-P105 & 276-P106 THAT THE |
| DESIGN OF THE STORM DRAINAGE SYSTEM INCLUDES 1/2 THE |
| AREA OF ANY VERTICAL WALLS THAT DIVERTS RAINWATER TO |
| THE ROOF. THE DESIGN SHALL ALSO INCLUDE THE SQUARE |
| FOOTAGE OF ANY SLOPED ROOF THAT DIVERTS RAINWATER TO |
| THE FLAT ROOFS.2010 FBC-PLUMBING SEC.1106.4. |
| 26) SHT. 268-P101C - THE NOTES AT THE GREASE TRAP ARE |
| DIFFICULT TO READ. THERE IS OTHER TEXT OVER TOP OF |
| IT.PLEASE CORRECT, WPB AMEND. TO FBC SEC. 107.2.1. |
| 27) SHT.299-P501 - SHOW THE PIPE SIZES OF ALL SECTIONS |
| OF PIPE FOR THE DOMESTIC BOOSTER WATER PUMP,WATER |
| SOFTENER AND PRESSURE REDUCING STATION. WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 28) SHT. 280-P301 - THE SANITARY AND WATER RISERS FOR |
| UNIT A1C ARE MISSING THE IDENTIFYING NUMBERS. |
| 29) SHT.297-P412 - SHOW THE DISTANCE IN DEVELOPED |
| LENGTH FROM EACH LINE PRESSURE REGULATOR TO THE MOST |
| REMOTE OUTLET AND THE LOAD OF THE SECTION.SHOW THE |
| LENGTHS OF EACH SECTION OF PIPE FOR THE 2 PSI SYSTEM |
| AND THE LESS THAN 2 PSI SYSTEM. 2010 FBC-FUEL GAS SEC. |
| 402.4.1, NFPA 54 SEC.6.1.3. |
| 30) SHT.297-P412 - THE GAS RISER IS SHOWING 4,996 CFH |
| ON A 1 1/4" LINE AT 2 PSI. THE SIZING TABLE REFERENCED |
| ON THE DRAWING ALLOWS A MAXIMUM OF 1,470 CFH AT 2 PSI |
| ON AN 1 1/4" LINE. IT APPEARS THE LINE IS SEVERELY |
| UNDERSIZED.THE MINIMUM SIZE SHALL BE 2 1/2 INCHES. |
| 31) SHT. 297-P412 - THE BTU LOAD AT POINT D ON THE |
| DRAWING DOES NOT EQUAL THE SUM OF THE BTU'S OF THE |
| LISTED FIXTURES. CLARIFY. |
| 32) SHOW THE BRANCH LINES TO THE POOL AND KITCHEN AREA |
| ON THE GAS RISER DIAGRAM AND SIZE THE LINE AND SUPPLY |
| THE BTU LOAD FOR THE BRANCH LINES.WPB AMEND. TO FBC |
| SEC. 107.3.5.1. |
| 33) THE SIZE OF THE GAS LINE TO THE FIREPLACE MAY |
| BEREQUIRED TO BE A MINIMUM OF 3/4" PER TABLE 6.2 (A) OF |
| NFPA 54. |
| 34) THE CFH AT THE METER SHOW 5020.3 CFH BUT THE CFH ON |
| THE 1 1/4" LINE DOWNSTREAM OF THE METER SHOWS 4,996 |
| CFH, WHERE DID THE ADDITIONAL LOAD AT THE METER COME |
| FROM? CLARIFY. |
| 35) PLEASE EXPLAIN THE NOTATION OF "8 OZ." ON THE GAS |
| DRAWING. |
| 36) THE PRV 'S SHALL COMPLY WITH THE FBC- FUEL GAS |
| SEC.410.2 (4),(5), (6),& 410.3. |
| 37)THE LINE FROM THE METER TO POINT "B" SHALL BE A |
| MINIMUM OF 2 1/2 INCHES PER NFPA 54 TABLE 6.2 (C). |
| 38) LIST THE CORRECT APPLICABLE GAS SIZING TABLES FOR |
| EACH TYPE OF MATERIAL BEING USED . WPB AMEND. TO FBC |
| SEC. 107.3.5.1.3. |
| 39) THE BTU LOAD DOWNSTREAM OF OF POINT "D" APPEARS |
| INCORRECT. ADDING THE 1,996 CFH FROM THE POOL AND |
| KITCHEN AREA TO THE BTU LOAD COMES TO 3,310.3. RE-CHECK |
| YOUR CALCULATIONS.(SEE AREA AT 2020.3 CFH). CHECK THE |
| ENTIRE SYSTEM FOR CORRECT SIZING. |
| 40 ) THE BTU LOAD UPSTREAM OF POINT "D" SHOULD BE |
| 6310.3.I CALCULATE THE ENTIRE BTU LOAD ON THE SYSTEM AS |
| 7610.3 CFH. CLARIFY. |
| 41) PVC IS NOT PERRMITED TO BE USED TO VENT REGULATORS |
| INDOORS PER FBC-FUEL GAS SEC.403.6.3. |
| 42.) SHT. 297-P412 - SHOWS THE GAS PIPING BEING |
| INSTALLED UNDER THE SLAB. THIS METHOD IS PERMITTTED IF |
| THERE IS NO OTHER METHOD TO INSTALL THE PIPING. IF THE |
| PIPING CAN BE RUN OVERHEAD THAT IT HOW IT SHALL BE |
| INSTALLED. IF THERE IS NO OTHER METHOD, THE |
| INSTALLATION SHALL COMPLY WITH 2010 FBC-FUEL GAS |
| SEC.404.12.1 OR 404.12.2. THE VENT TO THE ROOF IS NOT |
| AN ACCEPTED METHOD. |
| 43) THE PLAN SHOWS PE PIPE IN THE CONDUIT. PLASTIC PIPE |
| SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY PER |
| FBC-FUEL GAS SEC.404.15.1. |
| 44) PLAN REVIEW COMMENT # 77 - SHT. 297-412 - SUBMIT |
| CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE WITH 2010 |
| FBC-FUEL GAS SEC. 304. SUBMIT DETAILS ON THE |
| LOCATION/TERMINATION AND TYPES OF GAS VENTS, HEIGHT |
| ABOVE THE ROOF, ETC.THE RESPNSE NARRATIVE REFERS TO |
| DRAWINGS M206, M503 & M505. THERE ARE NO SUCH DETAILS |
| ON M206 AND I COULD NOT FIND A SHEET LABELED M505. |
| CLARIFY. |
| 45) IT APPEARS THAT CALCULATIONS FOR COMBUSTION AIR FOR |
| THE GAS SYSTEM HAVE NOT BEEN SUBMITTED. I COULD NOT |
| FIND THE CALCULATIONS ON ANY PLANS. CLARIFY. |
| 46) SHT.332-M504 - DETAIL #3 REFERS TO DETAIL #6 ON |
| SHT. 327-M404. THERE IS NO SUCH DETAIL. CLARIFY. |
| 47) SUBMIT VENT DETAILS FOR THE POOL HEATERS . WPB |
| AMEND. TO FBC SEC. 107.3.5.1.3. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |