2015-08-10 07:21:46 | 2010 FLORIDA BUILDING CODE |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| REVISION REQUIRED PRIOR TO COMMENCEMENT |
| |
| ****PROVISOS**** |
| ISSUED AT CONTRACTOR'S RISK |
| THE FOLLOWING ITEMS ARE PROVISO ITEMS, REVISION |
| REQUIRED PRIOR TO FIRST INSPECTION |
| ITEMS ABOVE ARE TO BE DONE PRIOR TO PERMIT ISSUANCE |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 2010 FLORIDA BUILDING CODE |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| THE FOLLOWING COMMENTS ARE TO BE ADDRESSED IF PLANS ARE |
| RESUBMITTED FOR OTHER TRADES. IF PLANS ARE NOT |
| RESUBMITTED, THE FOLLOWING ITEMS WILL BE PROVISO ITEMS, |
| REVISION REQUIRED PRIOR TO COMMENCEMENT. |
| |
| PLEASE BE ADVISED THAT COMMENTS HAVE BEEN REARRANGED |
| AND RENUMBERED FOR CLARITY. COMMENTS WHICH ARE TO BE |
| ADDRESSED AT THIS TIME (AS OTHER TRADES FAILED AND A |
| RESUBMITTAL IS REQUIRED) ARE BELOW. THE ITEMS WHICH ARE |
| TO BE ADDRESSED AT A FUTURE DATE, OR ARE INFORMATIONAL |
| ONLY, ARE NOW ALL AT THE END OF THE COMMENT LIST. |
| |
| 1. ARCHITECT?S RESPONSE INCLUDED BUILDING REVIEWS 1 AND |
| 2. IF RESUBMITTING, ONLY CURRENT ITEMS ARE TO BE |
| ADDRESSED. |
| |
| 2. FBC 107, AN OVERALL INDEX WAS PROVIDED (SHEET G000C) |
| BUT THE INDEX IS NOT IN THE SAME ORDER AS THE |
| PROJECTDOX FILES AND MANY SHEETS ARE STILL OUT OF |
| ORDER. THIS HAS RESULTED IN ADDITIONAL PLAN REVIEW TIME |
| FOR ALL REVIEWERS TO ATTEMPT TO LOCATE PAGES AND SERIES |
| OF PLANS WITHIN THE FILE. A REVIEW OF PLAN ORDER WILL |
| BE DONE PRIOR TO THE NEXT PLAN REVIEW. |
| |
| SOME ITEMS MAY HAVE NOT BEEN REVIEWED DUE TO THIS |
| ISSUE. SOME OF THE PROJECTDOX ISSUES ARE: |
| |
| PHASE ONE/VOLUMEN ONE, EVERYTHING AFTER A625 (INCLUDING |
| A626-644, INTERIORS, FOOD SERVICE) IS MISSING (FILES DO |
| NOT FOLLOW SHEET A625 AS INDEX STATES, BUT ARE |
| SCATTERED THROUGHOUT THE PLAN). THERE ARE A TOTAL OF AT |
| LEAST 17 SHEETS WHICH ARE OUT OF ORDER. REPEAT COMMENT. |
| |
| IN101A BELONGS IN PHASE I, IS OUT OF ORDER AND IN PHASE |
| 2. THIS COMMENT APPLIES TO ALL OF THE IN SHEETS (OUT OF |
| ORDER, PAGES ARE SCATTERED THROUGHOUT THE PLAN). REPEAT |
| COMMENT. |
| |
| THE ORDER OF THE PHASE / VOLUMEN IS NOT CONSISTENT WITH |
| THE ORDERING OF THE PHASE / VOLUMEN IN THE PROJECTDOX |
| FILE |
| |
| PHASE 2 IRRIGATION SHEETS ARE NOT INCLUDED ON EITHER |
| INDEX (G000C OR PHASE TWO VOLUMEN TWO INDEX) |
| |
| 2110 - G000B DOESN'T INCLUDE FS (FOOD SERVICE) SHEETS, |
| BUT THERE ARE FS SHEETS WHICH FOLLOW THE T (TECHNOLOGY) |
| SHEETS. FS SHEETS ARE SHOWN ON G000C, BUT NOT IN THE |
| ORDER SHOWN. |
| |
| REGARDING NAMING OF SHEETS, PAGES HAVE BEEN DIFFICULT |
| TO LOCATE DUE TO INCONSISTENT INDEX AND NAMING |
| CONVENTION WHICH IS NOT TYPICAL. SP WAS USED FOR SITE |
| POOL, BUT IS USUALLY SITE PLAN. FS WAS USED FOR FOOD |
| SERVICE, BUT THIS NAME IS USUALLY ASSIGNED TO FIRE |
| SPRINKLER PAGES. K IS THE LETTER TYPICALLY USED FOR |
| KITCHEN EQUIPMENT PLANS. OTHER REVIEWERS ARE STILL |
| UNABLE TO LOCATE PAGES WHICH REQUIRE REVIEW. A DETAILED |
| EXPLANATION OF PLAN ORDER ISSUES IS AVAILABLE VIA EMAIL |
| UPON REQUEST. |
| |
| SEE PREVIOUS LIST REGARDING THE ORDER OF THE SERIES |
| WITHIN THE PROJECTDOX FILE. THIS WAS NOT FIXED FOR THIS |
| SUBMITTAL. |
| |
| ARCHITECT PROVIDED A RESPONSE NARRATIVE FOR AN |
| EXPLANATION OF THE FILE ORDER. THIS IS NOT CONSISTENT |
| WITH THE NAMING CONVENTION USED FOR THE FILES WHICH |
| WERE UPLOADED, SO THE NARRATIVE IS NOT CONSISTENT WITH |
| THE PROJECTDOX DOCUMENT. IN A 602 PAGE PLAN, IT IS VERY |
| TIME CONSUMING TO SPECTULATE AS TO LOCATION OF |
| INFORMATION. |
| |
| 3. APPENDIX C INCLUDES INFORMATION NOT INCLUDED IN THE |
| SUMMARY PAGE PREPARED BY ARCHITECT. PER ARCHITECT?S |
| COVER LETTER FOR THE APPENDIX DOCUMENT, APPENDIX C |
| SHOULD INCLUDE ONLY FIRESTOP SYSTEMS AND DOOR HARDWARE |
| INFORMATION. |
| |
| SOME PAGES INCLUDE INFORMATION REVIEWED BY OTHER TRADES |
| (ELECTRICAL WIRING SPECS, COMMERCIAL KITCHEN EQUIPMENT |
| SPECS, ETC.). |
| |
| THE SPEC BOOK SHEETS SUBMITTED HAVE NOT BEEN REVIEWED. |
| SPEC BOOKS SHOULD NOT BE A PART OF THE PERMIT FILE AS |
| THE PLANS ARE TO SHOW CODE COMPLIANCE. REMOVE THE SPEC |
| SHEETS AND ALL OTHER SHEETS NOT INCLUDED ON THE |
| APPENDIX SUMMARY FROM THE FILE. THEY SHOULD BE UPLOADED |
| AS A SEPARATE FILE. |
| |
| IT WOULD HELPFUL IF THE COVER PAGE SUMMARY (WHICH |
| SERVES AS AN INDEX) WOULD INCLUDE PAGE NUMBERS. THE |
| DOCUMENT IS 191 PAGES. ANY LARGE DOCUMENT SHOULD BE |
| PAGINATED, FBC 107. OR, SPLIT THE DOCUMENT INTO SEVERAL |
| DOCUMENT. |
| |
| 4. A101 DOES NOT MATCH THE LIFE SAFETY PLAN AND OTHER |
| SHEETS, PLEASE CORRELATE. IT IS DIFFICULT TO PERFORM A |
| LIFE SAFETY REVIEW WITH THE MULTIPLE GRAPHICS ON THE |
| LIFE SAFETY PAGE, OVERALL FLOOR PLAN WHICH IS CLEAN IS |
| AN OLD VERSION, AND THE ENLARGED FLOOR PLAN HAS |
| CONSTRUCTION DETAILS (WAS NOT INTENDED TO USE FOR LIFE |
| SAFETY). THE GRAPHICS ON THE LIFE SAFETY PLAN OBSCURES |
| WALLS AND DOORS. SHEET A101 IS REQUIRED FOR A COMPLETE |
| LIFE SAFETY REVIEW. |
| |
| 5. G101 HAS A NOTE, TRAVEL DISTANCE TO GATE 48FT 10IN, |
| APPEARS TO LEAD TO A DOOR, NOT A GATE, PLEASE REVISE. |
| THIS IS THE SAME EXIT ACCESS WHICH GRAPHICALLY DEPICTS |
| A WALL BLOCKING MEANS OF EGRESS, FBC 107. |
| |
| 6. DINING SHOW A DOUBLE DOOR OPENING INTO POOL AREA |
| WITH TRAVEL DISTANCE TO GATE 107FT 3IN, BUT NO EXIT |
| SIGN. EXIT STRATEGY NOT CLEAR. |
| |
| 7. FBC 1005.1, THE LOSS OF ONE MEANS OF EGRESS SHALL |
| NOT REDUCE THE CAPACITY TO LESS THAN 50 PERCENT, SEE |
| POOL AREA. ONE EXIT SIGN IS ADJACENT TO TWO GATES |
| (DOUBLE AND SINGLE), OCCUPANT LOADS LISTED FOR BOTH, AS |
| WELL AS OCCUPANT LOAD STATED FOR THE EXIT TO THE SOUTH, |
| NO EXIT SIGNS FROM BUILDING TO POOL AREA, NOT CLEAR |
| WHICH 452 OCCUPANTS ARE EXITING THROUGH THIS AREA (59, |
| 117, 276 LABELED FOR POOL GATES). |
| |
| 8. OK OR MOVED TO END OF COMMENT LIST (INFORMATIONAL OR |
| FUTURE PROVISO ITEMS, NOT REQUIRED TO BE ADDRESSED WITH |
| THE REVISION) |
| |
| 9. G101, CORRIDOR 187 IS NOT A RATED CORRIDOR BUT |
| SERVES THE RESIDENTIAL UNITS AS THERE IS AN EXIT SIGN |
| FROM CORRIDOR 188 TO CORRIDOR 187, FBC TABLE 1018.1. |
| THERE IS A NOTE WHICH STATES THAT TRAVEL DISTANCE IS |
| 134FT, BUT IT IS NOT CLEAR WHERE THIS IS APPLICABLE. |
| |
| SEE OTHER COMMENT REGARDING EXIT ENCLOSURE DEFINITION; |
| REVISE PLAN TO CLARIFY MEANS OF EGRESS COMPONENTS AND |
| EXIT STRATEGY. |
| |
| 10. A101A AND G101, 47 FIXED SEATS SHOWN INCLUDING ONE |
| COMPANION SEAT (TWO ARE REQUIRED BUT CAN BE MOVABLE IF |
| COMPARABLE TO FIXED SEATING), TWO WHEELCHAIR SPACES |
| APPEAR TO BE SHOWN (NOT MARKED, BUT RECTANGLES ARE |
| SHOWN) BUT AN OCCUPANT LOAD OF 46 STATED AND NO |
| OCCUPANT LOAD STATED FOR THE THEATER VESTIBULE. PLEASE |
| CLARIFY THE MATH AND OCCUPANT LOAD. ALSO INCORPORATE A |
| STATEMENT THAT ANY STAFF MEMBERS ENTERING THIS ROOM |
| WILL BE USING ONE OF THE SEATS OR ADD A REASONABLE |
| NUMBER OF STAFF MEMBERS TO THE OCCUPANT LOAD. |
| |
| REVISE PLAN TO LABEL THE TWO WHEELCHAIR SPACES AS SUCH. |
| |
| 11. PROVISO, G101 AND A213, THE DOORS FOR THE MULTI |
| PURPOSE ROOM INCLUDE SIDELIGHTS WHICH APPEAR TO BE |
| IDENTICAL TO THE DOORS BUT DO NOT OPERATE. SEE FBC |
| 1008.1, REVISE PLAN TO SHOW HOW THE DOORS WILL BE |
| EASILY DISTINGUISHABLE FROM THE INOPERABLE SIDELITES. |
| |
| SIGNAGE IS NOT ACCEPTABLE DUE TO THE LARGE NUMBER OF |
| OCCUPANTS ATTEMPTING TO EXIT. ALSO SIGNAGE WOULD BE |
| CONFUSING; SIGN STATES THIS IS NOT AN EXIT, BUT IT IS |
| AN EXIT; UNLESS THE SIGN IS POSTED ON THE SIDELITE, |
| SIGNAGE IS NOT CLEAR AS TO WHAT IS NOT AN EXIT. |
| |
| THIS ISSUE WILL BE A PROVISO ITEM. THE SIDELITES ARE |
| GRAPHICALLY SHOWN AS IDENTICAL TO THE DOORS. |
| |
| THIS APPLIES TO BOTH DOORS 126 AND 124 (AND ANY OTHER |
| DOORS AS APPLICABLE). |
| |
| 12. FROM PREVIOUS LISTS, G101, AEROBICS 146 AND FITNESS |
| 143 APPEAR TO HAVE AN OCCUPANT LOAD OVER 50, BUT SECOND |
| EXIT ACCESS NOT CLEAR. AEROBICS ROOM HAS TWO DOORS BUT |
| BOTH LEAD TO SAME CORRIDOR (COMMON PATH). FITNESS ROOM |
| HAS ONLY ONE EXIT ACCESS. TWO MEANS OF EGRESS REQUIRED |
| FROM SPACES WITH AN OCCUPANT LOAD OVER 50, TWO EXITS |
| REQUIRED FOR THE AREA. |
| |
| 2ND REVIEW, COMMENT NOT ADDRESSED. ARCHITECT RESPONSE |
| IS THAT THE ROOMS INDIVIDUALLY HAVE AN OCCUPANT LOAD |
| LESS THAN 50. |
| |
| AEROBICS AND FITNESS ROOMS EACH SEPARATELY HAVE AN |
| OCCUPANT LOAD LESS THAN 50 BUT TOGETHER HAVE AN |
| OCCUPANT LOAD OVER 50 WITH THE PARTITION OPEN. TO TREAT |
| EACH AREA SEPARATELY, REPLACE THE MOVABLE PARTITION |
| WITH A WALL. OCCUPANCY CLASSIFICATION IS STATED AS |
| BUSINESS. THIS SHOULD BE ASSEMBLY, SEE DEFINITION. |
| REGARDLESS OF OCCUPANCY CLASSIFICATION, THE DOORS ARE |
| TO SWING IN THE DIRECTION OF TRAVEL (146 AND 146A), |
| 1008.1.2 AS OCCUPANT LOAD EXCEEDS 50 WITH THE PARTITION |
| OPEN. |
| |
| TRAVEL DISTANCE IS MEASURED TO THE GALLERY WHICH IS |
| CALLED AN EXIT ENCLOSURE. SEE OTHER COMMENTS REGARDING |
| THE DEFINITION OF EXIT ENCLOSURE. NOTE THAT AS |
| DESIGNED, ALL OCCPANTS OF THIS AREA ARE FORCED TO GO |
| THROUGH THE GALLERY WHICH IS OPEN TO TWO ELEVATORS. |
| |
| CONSIDER THE SCENARIO THAT SHOULD THERE BE AN ISSUE |
| (FIRE OR SMOKE) IN THE ELEVATOR SHAFT, OCCUPANTS FOR |
| THIS AREA ARE FORCED TO GO THROUGH A SMOKE FILLED EXIT |
| ENCLOSURE. RATIONALE OF INCLUDING TWO ELEVATORS, TOILET |
| ROOMS, LOW VOLTAGE SERVER ROOM, HOUSEKEEPING ROOM, OPEN |
| LIVING ROOM LIBRARY, WORK ROOM IN AN ?EXIT ENCLOSURE? |
| IS NOT CLEAR. |
| |
| SEE ALSO IBC CODE AND COMMENTARY 2009 (THE BASE CODE |
| FOR FBC 2010), PAGE 7-62 (SECTION 708.14.1) WHERE |
| ELEVATOR LOBBIES AND EXCEPTIONS ARE DISCUSSED AT |
| LENGTH, WHICH SPECIFICALLY STATES: |
| |
| OF COURSE, THE ELEVATOR HOISTWAY DOORS CAN NEVER OPEN |
| INTO AN EXIT ENCLOSURE. |
| |
| REVISE PLAN SO THAT THE EXIT ENCLOSURE INCLUDES ONLY |
| ITEMS WHICH DO NOT POSE A HAZARD TO THE EXIT ENCLOSURE. |
| THE LIVING ROOM WILL CONTAIN FURNITURE AND OTHER |
| COMBUSTIBLES (HAZARD). THE ELEVATORS THEMSELVES POSE A |
| HAZARD (EVEN WITH PRESSURIZATION). THE OTHER ROOMS |
| CURRENTLY SHOWN WITHIN THE EXIT ENCLOSURE SHOULD ALSO |
| BE SEPARATED FROM THE EXIT ENCLOSURE. |
| |
| REVISE PLAN SO THAT EXIT STRATEGY ADDRESSES THESE |
| CONCERNS. |
| |
| 13. AN ADDITIONAL DOOR WAS PROVIDED TO ADDRESS THE DEAD |
| END BUT SEE OTHER COMMENTS REGARDING TWO EXITS REQUIRED |
| AND USE OF THE GALLERY AS AN EXIT ENCLOSURE. PRIOR TO |
| RESUBMITTAL, ENSURE THAT NO NEW DEAD ENDS ARE CREATED. |
| |
| 14. G101, REVISE PLAN TO INCLUDE OCCUPANT LOAD AND AREA |
| FOR THE FITNESS ROOM AND AEROBICS ROOM (SEPARATELY AS |
| THE LARGER AREA CAN BE COMBINED TO TWO SMALLER AREAS). |
| AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA |
| OCCUPANT LOAD WILL BE OVER 50, DOORS ARE TO SWING IN |
| THE DIRECTION OF TRAVEL, FBC 1008.1.2. |
| |
| NOT ADDRESSED. CHANGE DOOR SWING OR ADD A WALL AT THE |
| LOCATION OF THE FOLDING PARTITION. OCCUPANT FOR THE |
| ROOM WITH THE PARTITION IS OVER 50 (PER BUILDING |
| OFFICIAL). |
| |
| 15. THE AEROBICS AND FITNESS AREA OCCUPANT LOAD IS OVER |
| 50, FIRE EXIT HARDWARE OR PANIC HARDWARE REQUIRED FOR |
| THOSE DOORS AND ALL OTHER DOORS IN THE MEANS OF EGRESS, |
| FBC 1008.1.10, 1004.9. |
| |
| NOT ADDRESED. |
| |
| 16. EGRESS GATE IS REQUIRED TO HAVE EITHER FIRE EXIT |
| HARDWARE OR PANIC HARDWARE, FBC 1008.1.10, 1008.2. |
| REVISE PLAN TO INCLUDE THE REQUIREMENT OR DETAIL. |
| |
| RESPONSE LETTER STATES TO SEE AS102. INDEX SHOWS THE AS |
| SERIES BEFORE A SHEETS. UNABLE TO LOCATE SHEET (NOT IN |
| THIS LOCATION). COMMENT NOT ADDRESSED. |
| |
| 17. DOOR SCHEDULE HAS A COLUMN FOR ?ELECTRIC? BUT THAT |
| COLUMN IS BLANK. IT APPEARS THAT THIS SHOULD BE |
| APPLICABLE FOR SLIDING DOORS IN THE REQUIRED MEANS OF |
| EGRESS AND EXIT. EXIT DOOR 122 (DOOR TYPE G1) SHOULD |
| ALSO COMPLY WITH FBC 1008.1.4.2, 1008.1.4.3. |
| |
| 18. A601 AND G101, DOORS IN FIRE BARRIERS REQUIRE A 45 |
| MINUTE FIRE RATING, FBC TABLE 715.4. IT IS NOT CLEAR |
| WHICH DOORS ARE BEING CONSIDERED IN A CORRIDOR RATHER |
| THAN AN OCCUPANCY SEPARATION. SEE DOORS 173C, 182, 172, |
| 183. |
| |
| DOOR 173C IS A 20 MINUTE DOOR, BUT THE CORRIDOR 184 |
| RATING IS NOT CONTINUOUS AS IT APPEARS TO TRANSITION |
| INTO THE GALLERY. USE OF CORRIDORS, INCIDENTAL AND |
| ACCESSORY USES FBC 508 ARE NOT ENTIRELY CLEAR. IF ANY 1 |
| HOUR RATINGS ON THE PLAN ARE REMOVED WHEN RESUBMITTING, |
| PLEASE ALSO NOTE ALSO SMOKE AND PROTECTION REQUIREMENT |
| IN 508.2.5.2. |
| |
| 19. SEE G102 AND OTHER FLOORS, THERE IS AN UNIDENTIFIED |
| 1 HOUR RECTANGLE ADJACENT TO THE ELEVATOR 2-2. THIS |
| AREA IS NOT IDENTIFIED ON A102, A102A. FBC 107, USE OF |
| THIS SPACE AND REQUIRED FIRE RESISTANCE RATING NOT |
| CLEAR. |
| |
| 20. THE MCKEON DOOR SPECIFIED DOES NOT MEET THE MINIMUM |
| REQUIREMENTS OF FBC 715.4. THE DOOR SPEC SHEET STATES |
| THAT IT MEETS UL 10B FOR 20 MINUTES. SEE G101, 45 |
| MINUTE AND 60 MINUTE ARE REQUIRED. |
| |
| 21. PLANS IN MANY LOCATIONS USE THE LANGUAGE "UNDER |
| SEPARATE PERMIT" (FOR INSTANCE, SHEET 036 - S6.2). IF |
| ALL WORK TO BE INCLUDED IN THIS PERMIT, REVISE |
| LANGUAGE. |
| |
| PLANS STILL REFER TO SEPARATE PERMIT FOR PHASE I AND |
| PHASE II. PHASE ONE PLANS REFER TO PHASE TWO AS A |
| SEPARATE PERMIT. PHASE TWO REFERS TO PHASE ONE AS A |
| SEPARATE PERMIT. SEE OTHER COMMENT REGARDING |
| CONSIDERING PUTTING THE TWO PHASES INTO TWO SEPARATE |
| PERMITS. IF ALL WORK TO REMAIN UNDER ONE PERMIT, PLEASE |
| REVISE LANGUAGE AS IT IS CONFUSING. SEE FBC 107, PLANS |
| SHOULD BE CLEAR AS TO SCOPE AND NATURE OF WORK. |
| |
| 22. INCORPORATE FIRE RATING REQUIREMENTS AND DETAILS |
| FOR THE FLOOR, STRUCTURAL ELEMENTS FBC TABLE 601. |
| |
| NOT ADDRESSED. DETAILS SHOWING THE TESTED ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE REQUIRED, SEE FBC 703. A |
| STATEMENT IN A RESPONSE LETTER THAT EVERYTHING COMPLIES |
| IS NOT ADEQUATE TO DEMONSTRATE CODE COMPLIANCE FOR THIS |
| HIGH RISE BUILDING. |
| |
| NOTE THAT THE LIFE SAFETY PLAN, WHICH SHOWS OTHER FIRE |
| RESISTANCE RATINGS, IS LACKING INFORMATION REGARDING |
| EXTERIOR WALLS AND STRUCTURAL FRAME. PROPOSED FIRE |
| RATING FOR THE STRUCTURAL ELEMENTS IS NOT CLEAR. IT IS |
| NOT CLEAR WHETHER FBC TABLE 601 OR 602 WILL DETERMINE |
| THE EXTERIOR WALL RATINGS. |
| |
| NEW COMMENTS DUE TO NEW INFORMATION: |
| |
| 23. CLOUDS INDICATING CHANGES FROM REVISION 0 TO |
| REVISION 4 HAVE BEEN REMOVED. FOUR VERSIONS OF G101 |
| HAVE BEEN UPLOADED TO PROJECT DOX. ONE SET WAS NOT |
| REVIEWED (VERSION 2) AND IT APPEARS THAT VERSION 3 HAS |
| BEEN UPLOADED TWICE. |
| |
| PLEASE RETAIN ALL CLOUDS FOR CHANGES NOT REVIEWED |
| (FUTURE REVISIONS). |
| |
| 24. G101, AREA SCHEDULE (GROSS BUILDING) IS LACKING THE |
| TOTAL AND ALSO LACKS THIRD THROUGH SEVENTH FLOOR, FBC |
| 107, FBC 107. |
| |
| 25. G101, AT 3 HOUR FIRE WALL, PLAN STATES THAT 1 HOUR |
| FIRE PROTECTION IS REQUIRED (EXTENDED 4 FT FROM FIRE |
| WALL). SEE FBC TABLE 601 AND 602; BASED ON OTHER MORE |
| STRINGENT REQUIREMENTS, 1 HOUR DOES NOT APPEAR TO BE |
| SUFFICIENT. BEARING WALLS ARE TO BE 3 HOURS. SEE OTHER |
| COMMENT REGARDING FIRE RATING DETAILS. |
| |
| 26. A352, PT WOOD AND EXT PLYWOOD IS SHOWN. SEE FBC |
| 603, 717.5, 718.3, IT APPEARS THAT THERE IS AN |
| EXCESSIVE AMOUNT OF COMBUSTIBLE, NON FRT LUMBER |
| INSTALLED AT 130 FT. EITHER REVISE TO NON COMBUSTIBLE |
| MATERIALS OR PROVIDE RATIONALE OR EXCEPTION. |
| |
| 27. G101, ROOM TO THE NORTH OF AIR HANDLER ROOM 180 IS |
| NOT LABELED. |
| |
| 28. G101, THE DINING ROOM EGRESS (SOUTH EAST CORNER OF |
| DISPLAY KITCHEN DINING B) PATH TO WOUTH EXIT GOES |
| THROUGH A WALL, SEE THE L SHAPE AREA BETWEEN NORTH |
| WALLS OF OFFICE 163C AND DRY STORAGE 166. REVISE OR |
| CLARIFY. |
| |
| 29. SP AND WF SHEETS, NEW POOL AND WALL FOUNTAIN PLANS |
| WERE SUBMITTED. THEY HAVE NOT BEEN REVIEWED AT THIS |
| TIME AND REQUIRE SEPARATE PERMITS. HOWEVER, IN TAKING A |
| CURSORY GLANCE AT THE PLANS, IT APPEARS THAT THE POOL |
| WAS DESIGNED TO FBC 2010 RESIDENTIAL DUE TO THE FBC |
| 2010 RESIDENTIAL REFERENCES ON THE PLANS. |
| |
| 30. ENERGY CALCS WERE SUBMITTED. INCLUDED ON THE ENERGY |
| CALCS IS A GAS HOT WATER BOILER, BETWEEN 300,000 AND |
| 2.5 MILLION BTUS. SEE FBC 1015.3 REGARDING EXITING |
| REQUIREMENTS FOR BOILER ROOMS. WHERE IS THIS BOILER |
| LOCATED? IT IS NOT SHOWN ON THE LIFE SAFETY PLAN, FBC |
| 107. REVISE OR CLARIFY. |
| |
| 31. REVISED SHEET G101 SHOWS TRAVEL DISTANCE AS 130FT |
| FROM THE FITNESS LOUNGE TO THE EXIT ENCLOSURE. SEE THE |
| DEFINITION OF CORRIDOR, FBC 1002, AN ENCLOSED EXIT |
| ACCESS COMPONENT THAT DEFINES AND PROVIDES A PATH OF |
| EGRESS TRAVEL TO AN EXIT. |
| |
| SEE ALSO DEFINITION OF EXIT ENCLOSURE, AN EXIT |
| COMPONENT THAT IS SEPARATED FROM OTHER INTERIOR SPACES |
| OF A BUILDING OR STRUCTURE BY FIRE RESISTANCE RATED |
| CONSTRUCTION AND OPENING PROTECTIVES. MANY ROOMS ARE |
| INCLUDED IN THE GALLERY (HOUSEKEEPING, LIVING ROOM, |
| ELEVATOR LOBBIES, TOILET ROOMS, ETC.). DEFINITION |
| STATES THAT AN EXIT ENCLOSURE IS TO BE SEPARATED FROM |
| OTHER INTERIOR SPACES. |
| |
| THIS COMMENT ALSO APPLIES TO THE RESIDENTIAL AREA |
| EXITING. RESIDENTIAL CORRIDOR TAKES THE OCCUPANT |
| THROUGH THE 1 HOUR RATED CORRIDOR THROUGH THIS GALLERY |
| AREA, NOW CALLED AN EXIT ENCLOSURE, BUT THE GALLERY AS |
| SHOWN ON G101 DOES NOT MEET THE DEFINITION OF AN EXIT |
| ENCLOSURE. AN EXIT ENCLOSURE IS TO BE SEPARATED FROM |
| OTHER INTERIOR SPACES. ONCE AN OCCUPANT ENTERS THE |
| EXIT, THE EXIT IS TO BE CONTINUOUS UNTIL THE EXIT |
| DISCHARGE. |
| |
| 32. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT |
| COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF |
| EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING |
| REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE |
| REQUIRED PRIOR TO CERTIFICATE OF COMPLETION. |
| |
| 33. REVISE SHEET G001, REQUIRED FIRE RESISTIVE RATINGS. |
| DISTANCE TO PROPERTY LINE IS FOR GREATER THAN 30FT |
| SEPARATION. AS THERE IS A PROPERTY LINE BETWEEN THE TWO |
| BUILDINGS, THIS IS NOT ACCURATE. DUE TO THE EXCEPTION |
| FOR ONE STORY (1 HOUR REDUCTION FBC TABLE 601 FOOTNOTE |
| A), DISTANCE TO PROPERTY LINE (FBC TABLE 602) APPEARS |
| TO BE MORE RESTRICTIVE (2 HOUR REEQUIRED FROM 5 FEET TO |
| UNDER 20 FEET). |
| |
| 34. THRESHOLD PLAN STATEMENT REQUIRED BY FS 553.79 TO |
| BE CORRECTED ON STRUCTURAL DRAWINGS. EVIDENCE THAT THIS |
| HAS BEEN CORRECTED IS TO BE SENT TO ME VIA EMAIL PRIOR |
| TO PERMIT ISSUANCE. PLANS ARE TO BE SUBMITTED AS A |
| REVISION PRIOR TO COMMENCEMENT IF PERMIT IS ISSUED THIS |
| REVIEW CYCLE. IF PERMIT IS NOT ISSUED IN THIS REVIEW |
| CYCLE, REVISED DRAWINGS TO BE RESUBMITTED. (EMAIL |
| RECEIVED FROM STRUCTURAL ENGINEER ON 8/18/15) |
| |
| 35. AS ALL STRUCTURAL SHEETS ARE REQUIRED TO BE |
| REVISED, SEE PREVIOUS LIST REGARDING THE ADDRESS ON THE |
| PLAN AND REVISE. STRUCTURAL SHEETS STILL HAVE INCORRECT |
| ADDRESS OF 4920 LORING DRIVE. |
| |
| 36. UNIT 1A, SHOW CLEAR FLOOR SPACE CENTERED ON SINK, |
| SHEET A 401A. |
| |
| 37. AS 109, POOL BAR AREA, CLARIFY PURPOSE THIS AREA; |
| IS THIS FOR STAFF ONLY (WORK AREA), OR FOR USE BY |
| RESIDENTS AND THEIR GUESTS? THERE IS A STATEMENT ON THE |
| PLAN WHICH STATES THAT AMENITY SPACES AND COMMON AREAS |
| ARE ONLY USED BY RESIDENTS AND THEIR GUEST. THERE ARE |
| OFFICES, SPA, LARGE RESTAURANT STYLE DINING AREA, BUT |
| THE PLAN DOES NOT INDICATE WHICH AREAS ARE FOR USE BY |
| EMPLOYEES. |
| |
| IT IS NOT CLEAR WHETHER ACCESSIBILITY OR FAIR HOUSING |
| APPLIES. MORE INFORMATION REQUIRED; NO CLEAR FLOOR |
| SPACE SHOWN FOR FIXTURES, SINK AND COUNTER ARE AT 40 |
| INCHES. WILL FOOD OR DRINKS BE SOLD AT THIS LOCATION? |
| SEE FBC 2010 ACCESSIBILITY 804, 902, 904, 606, CFR |
| 100.205(C)(1). |
| |
| 38. BREAK ROOM APPEARS TO BE FOR EMPLOYEE USE. SINK TO |
| COMPLY WITH FBC 2010 ACCESSIBILITY 606. |
| |
| 39. SEE PLUMBING COMMENTS REGARDING OTHER ACCESSIBILITY |
| AND FAIR HOUSING AND REVISE PLAN TO SHOW APPLICABLE |
| DIMENSIONS. |
| |
| 40. SEE FIRE REPEAT COMMENT REGARDING FBC 403.3.2, |
| SHEET 402, FIRE PUMP SHALL BE SUPPLIED BY A MINIMUM OF |
| TWO WATER MAINS LOCATED IN DIFFERENT STREETS. AS WITH |
| THE STRUCTURAL SHEETS, REVISE AND PROVIDE EVIDENCE VIA |
| EMAIL THAT THIS ITEM HAS BEEN ADDRESSED. |
| ***************************** |
| PROVISOS |
| ISSUED AT CONTRACTOR'S RISK |
| |
| 1. AS PER OWNER?S AGREEMENT, A REPLAT WILL BE FILED |
| WITHIN 45 DAYS OF PERMIT ISSUANCE. FINAL PLAT REQUIRED |
| PRIOR TO C.O. A NEW SITE PLAN SHOWING DISTANCE TO THE |
| NEW PROPERTY LINE TO BE SUBMITTED FOR REVIEW AS A |
| REVISION. |
| |
| 2. ADVISORY ONLY, SEPARATE PERMITS (PLANS, APPLICATION, |
| REVIEWS, AND FEES) REQUIRED FOR PARKING LOT, SIGNAGE, |
| AWNINGS, FENCING, POOL, TRELLIS, SITE WALL, SEPARATE |
| BUILDINGS (INCLUDING GENERATOR BUILDING), FBC 107. |
| |
| 3. THE FOLLOWING SHEETS HAVE BEEN VOIDED AND WERE NOT |
| REVIEWED: SP101, SP102, SP103, SP104, SP105, SP106, |
| WF101, WF102, AND WF103. SUBMIT THESE PAGES UNDER |
| SEPARATE PERMIT APPLICATION. |
| |
| 4. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT VIA |
| EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| 78-123, 78-126. |
| |
| THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| DOCUMENT THE PERMIT FILE. |
| |
| 5. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND |
| RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED |
| TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH |
| LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE |
| BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH |
| LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS |
| BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A |
| NOTE BE INCORPORATED INTO THE PLAN. |
| |
| 6. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| TO INSTALLATION, FBC 107, FBC 1609 (SUBMITTAL, NO FEE). |
| COMPONENTS AND CLADDING TO COMPLY WITH WALL PRESSURES |
| SHOWN ON SHEET S8.5: |
| |
| ZONE 4 + 52.0 / - 52.2 |
| ZONE 5 + 52.0 / -95.7 |
| |
| FOR ROOF COVERING, SEE ROOF PLAN REVIEW STOP OR SHEET |
| S8.5 FOR PRESSURES. |
| |
| 8. PROVISO, FBC 911.1.4, LAYOUT OF FIRE COMMAND CENTER |
| AND ALL FEATURES REQUIRED BY 911.1.5 TO BE SUBMITTED |
| AND APPROVED PRIOR TO INSTALLATION. |
| |
| 9. PROVISO, G101 AND A213, THE DOORS FOR THE MULTI |
| PURPOSE ROOM INCLUDE SIDELIGHTS WHICH APPEAR TO BE |
| IDENTICAL TO THE DOORS BUT DO NOT OPERATE. SEE FBC |
| 1008.1, DOORS TO BE EASILY DISTINGUISHABLE FROM THE |
| INOPERABLE SIDELITES. |
| |
| 10. PROVISO, THE FOLLOWING TEST REPORTS FOR THE |
| FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO |
| INSTALLATION (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR |
| SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR |
| LESS ARE ACCEPTABLE): STC (FBC 1207.2), IIC (FBC |
| 1207.3), ASTM E 84 (FBC 603.1). |
| |
| 11. PROVISO, FBC 2010 ACCESSIBILITY 703, SIGNS TO |
| COMPLY WITH THIS SECTION. |
| |
| 12. PROVISO, DETAILS FOR UL ASSEMBLIES REFERENCED ON |
| THE PLANS ARE TO BE SUBMITTED WITH OPTIONS NOTED PRIOR |
| TO INSTALLATION. IF NOT PREPARED BY DESIGNER OF RECORD, |
| SHOP DRAWING REVIEW REQUIRED PRIOR TO SUBMITTAL. |
| |
| AS THE EXTERIOR WALLS ARE FIRE RATED, DETAILS FOR |
| STRUCTURE AND EXTERIOR WALLS REQUIRED PRIOR TO |
| COMMENCEMENT. |
| |
| 13. PROVISO, REVISED PLANS TO INCLUDE TOTAL SQUARE FOOT |
| AREA, PER FLOOR, PER OCCUPANCY CLASSIFICATION, TO |
| INCLUDE BOTH PHASE I AND PHASE II, FBC 107, FBC 109. |
| VALUE (ADJUSTED PER ICC TABLE AND COTLEUR & HEARING |
| SITE PLAN) WILL BE CONFIRMED AND MAY BE INCREASED. |
| ISSUED AT CONTRACTOR'S RISK. |
| |
| |