Plan Review Notes For Permit 14120909 |
Permit Number |
14120909 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-10 07:22:53 | ****PROVISO**** | | ISSUED AT CONTRACTOR?S RISK | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 2010 FLORIDA BUILDING CODE WITH 2012 FBC SUPPLEMENTS | | ADOPTED APRIL 25/2013. | | | | NO ROOF COVERING INFORMATION HAS BEEN SUBMITTED AT THIS | | TIME | | | | ROOF PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD, | | ARE TO BE SUBMITTED WITH ROOF PERMIT APPLICATION PRIOR | | TO INSTALLATION | | | | THE ROOF COVERING ASSEMBLY AT THE CONNECTING CORRIDOR | | IS TO HAVE A CLASS B RATING (PER SHEET G101, PER FBC | | 706.6 EXCEPTION 3) | | | | ALL ROOFS TO MEET THE FOLLOWING DESIGN PRESSURES PER | | SHEET S8.5: | | | | ZONE 1 +52.0 / -76.4 | | ZONE 2 +76.4 / -119.9 | | ZONE 3 +52.0 / -119.9 | | | | | | | | | | |
|