2015-08-07 12:04:18 | 4920 LORING DRIVE |
| PERMIT #14120909 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| |
| |
| 2ND REVIEW |
| SHEET G101: NO EXIT SIGNAGE PROVIDED FOR CORRIDOR |
| ADJACENT TO CONFERENCE #112. |
| |
| SHEET G101: PROVIDE ADDITIONAL EXIT SIGN AT EAST END OF |
| CORRIDOR #146A. ALSO DOOR APPEARS TO SERVE 51 PERSONS |
| SO THE SWING WOULD NEED TO BE WITH THE FLOW OF TRAFFIC |
| AND BE EQUIPPED WITH PANIC HARDWARE. |
| |
| REPEAT COMMENT -SHEET G001: UPDATE THE CODE LIST TO |
| REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE |
| PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH |
| NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| |
| SHEET A101 DOES NOT APPEAR TO BE UPDATED TO MATCH THE |
| LIFE SAFETY PLAN. |
| |
| NOTE: THE COOKING GRILL LOCATED ON THE POOL DECK SHALL |
| COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST 10 |
| FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES PER |
| NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED |
| UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH |
| NFPA 96. |
| |
| REPEAT COMMENT - SHEET FP402: FIRE PUMP SCHEDULE DOES |
| NOT INDICATE A RATED PRESSURE OR HORSEPOWER RATING. THE |
| ENGINEERING DOCUMENTS WILL BE REQUIRED TO DETERMINE IF |
| PRESSURE REDUCING VALVES ARE NEEDED ON THE STANDPIPES |
| AND SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL |
| ALSO REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH |
| DRAIN RISER AS SHOWN ON THE PLANS. |
| |
| REPEAT COMMENT - SHEET FP402: PER FBC SECTION403.3.2 |
| WATER SUPPLY TO REQUIRED FIRE PUMPS - REQUIRED FIRE |
| PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF |
| TWO WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE |
| SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION |
| TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND |
| THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS |
| SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED |
| FOR THE PUMPS TO OPERATE. |
| |
| |
| PHASE 2 - FIRE DEPARTMENT REVIEW |
| |
| REPEAT COMMENT - SHEET G001: UPDATE THE CODE LIST TO |
| REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE |
| PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH |
| NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. PER |
| SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN OCCUPANCY |
| TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY |
| SHALL BE TREATED AS A MIXED OCCUPANCY. |
| |
| |
| DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| VIOLATIONS OF THIS CODE. |
| |