Date Text
2015-08-07 12:04:184920 LORING DRIVE
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 2ND REVIEW
 SHEET G101: NO EXIT SIGNAGE PROVIDED FOR CORRIDOR
 ADJACENT TO CONFERENCE #112.
  
 SHEET G101: PROVIDE ADDITIONAL EXIT SIGN AT EAST END OF
 CORRIDOR #146A. ALSO DOOR APPEARS TO SERVE 51 PERSONS
 SO THE SWING WOULD NEED TO BE WITH THE FLOW OF TRAFFIC
 AND BE EQUIPPED WITH PANIC HARDWARE.
  
 REPEAT COMMENT -SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 SHEET A101 DOES NOT APPEAR TO BE UPDATED TO MATCH THE
 LIFE SAFETY PLAN.
  
 NOTE: THE COOKING GRILL LOCATED ON THE POOL DECK SHALL
 COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST 10
 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES PER
 NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED
 UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH
 NFPA 96.
  
 REPEAT COMMENT - SHEET FP402: FIRE PUMP SCHEDULE DOES
 NOT INDICATE A RATED PRESSURE OR HORSEPOWER RATING. THE
 ENGINEERING DOCUMENTS WILL BE REQUIRED TO DETERMINE IF
 PRESSURE REDUCING VALVES ARE NEEDED ON THE STANDPIPES
 AND SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL
 ALSO REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH
 DRAIN RISER AS SHOWN ON THE PLANS.
  
 REPEAT COMMENT - SHEET FP402: PER FBC SECTION403.3.2
 WATER SUPPLY TO REQUIRED FIRE PUMPS - REQUIRED FIRE
 PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF
 TWO WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE
 SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION
 TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND
 THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS
 SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED
 FOR THE PUMPS TO OPERATE.
  
  
 PHASE 2 - FIRE DEPARTMENT REVIEW
  
 REPEAT COMMENT - SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. PER
 SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730