Date |
Text |
2015-05-18 14:50:23 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 2010 FLORIDA BUILDING CODE |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| |
| 1. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D) ALL PLANS |
| FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND |
| SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A |
| STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR |
| ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS |
| COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND |
| THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY |
| THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND |
| CHAPTER 633. |
| |
| PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS |
| TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF |
| DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH |
| SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY, |
| PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH |
| THE APPROPRIATE BOARD. |
| |
| 2. IT IS NOT CLEAR WHETHER THE NEW BUILDING WILL BE |
| CONSIDERED AN ADDITION TO THE EXISTING BUILDING, ON THE |
| SAME PARCEL, CONNECTED BY A WALKWAY, OR IF WILL BE |
| TREATED AS A NEW BUILDING, SEPARATE PARCEL, OR NEW |
| BUILDING, SAME PARCEL (WITH UNITY OF TITLE, SEE OTHER |
| COMMENTS). |
| |
| IF THE TWO TOWERS ARE DESIGNED AS ONE BUILDING, |
| DESIGNER TO REFERENCE FBC 2010 EXISTING BUILDING |
| CHAPTER 10 (ADDITIONS) AS WELL AS METHOD OF COMPLIANCE |
| FOR THE EXISTING BUILDING (SEE FBC 2010 EXISTING |
| BUILDING 101.5). THIS IS REQUIRED IN ORDER TO ADDRESS |
| ISSUES AS THEY ARISE EITHER IN THE FIELD OR IN PLAN. |
| |
| 3. CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES |
| FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE |
| I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF |
| THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS |
| ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE |
| PARTIES, PLEASE CONTACT ME TO DISCUSS. |
| |
| THRESHOLD DOCUMENTS REQUIRED: |
| |
| SPECIAL INSPECTOR AGREEMENT |
| RESUME AND COPIES OF LICENSES FOR SPECIAL INSPECTOR AND |
| ALL ON SITE INSPECTORS |
| RESUME AND COPIES OF LICENSES FOR CONTRACTOR, JOB |
| SUPERINTENDENT AND/OR PROJECT MANAGER |
| |
| 4. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN |
| ON THE PLAN (PERKINS EASTMAN, FS95000000559, |
| PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS |
| (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763, |
| NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE |
| NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT |
| POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING |
| RESPONSIBILITY FOR THE DESIGN. |
| |
| SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED |
| AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION |
| DOCUMENTS. |
| |
| HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES. |
| HTML |
| |
| 5. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT SHOWN |
| ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES REMAIN |
| SEPARATE PARCELS, HAVE THEY ALREADY BEEN COMBINED WITH |
| A UNITY OF TITLE, OR WILL THEY BE COMBINED WITH A UNITY |
| OF TITLE? IF THEY ARE TO REMAIN SEPARATE PARCELS, SEE |
| FBC TABLE 602, TABLE 705.8 AND REVISE PLAN TO SHOW |
| COMPLIANCE (DISTANCE TO PROPERTY LINE, RATED WALLS AS |
| APPLICABLE, PROTECTED OPENINGS IF PERMITTED). |
| |
| IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING |
| DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING |
| KNOWN AS TRADITIONS II PHASE ONE. |
| |
| THE DISTANCE OF PROPOSED BUILDING TO THE ACTUAL |
| PROPERTY LINE (AS PER PAPA, NOT SHOWN ON PLANS) IS |
| UNCLEAR. |
| |
| IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY |
| OF TITLE AND WISH TO DO SO, THE APPLICATION IS |
| AVAILABLE ONLINE: |
| |
| HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- |
| 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF |
| |
| 6. THE ADDRESS ASSIGNED TO THIS BUILDING IS 4850 LORING |
| DRIVE; PLEASE REVISE PLANS AS APPLICABLE. |
| |
| 7. FS553, AS PERMITS 14120908 AND 14120909 WERE |
| INITIALLY FOUNDATION PERMITS, PLEASE PROVIDE NEW |
| APPLICATIONS WITH THE NEW SCOPE OF WORK AND VALUE, |
| SIGNED BY THE QUALIFIER AND THE OWNER. ALSO PLEASE NOTE |
| THAT IT APPEARS THAT THE NEW BUILDING (TRADITIONS II |
| PHASE ONE) IS LOCATED PRIMARILY ON A PARCEL WITH AN |
| ADDRESS OF 4850 LORING DRIVE, LOCATED ON TRACT C, |
| PARCEL ID 74-42-43-12-26-003-0000. |
| |
| 8. SEPARATE PERMITS (PLANS, APPLICATION, REVIEWS, AND |
| FEES) REQUIRED FOR PARKING LOT, SIGNAGE, FENCING, POOL, |
| TRELLIS, FBC 107. |
| |
| 9. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT VIA |
| EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| 78-123, 78-126. |
| |
| THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| DOCUMENT THE PERMIT FILE. |
| |
| 10. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND |
| RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED |
| TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH |
| LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE |
| BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH |
| LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS |
| BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A |
| NOTE BE INCORPORATED INTO THE PLAN. |
| |
| 11. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| FBC 1609 (SUBMITTAL, NO FEE). |
| |
| 12. ADVISORY ONLY, POOL DETAILS NOT REVIEWED AT THIS |
| TIME. POOL WILL BE REVIEWED UNDER A SEPARATE PERMIT, |
| FBC 107. |
| |
| 13. FOR TRACKING PURPOSES, A SEPARATE PERMIT IS |
| REQUIRED FOR THE DETACHED GENERATOR BUILDING, FBC 107. |
| |
| 14. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP |
| HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND |
| ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF |
| ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE |
| PLAN REVIEW PROCESS FOR THE ADDITION. |
| |
| 15. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| AND OTHER INDEPENDENT STRUCTURAL ELEMENTS REQUIRE |
| SEPARATE PERMITS WHICH WOULD INCLUDE FEES, BUILDING |
| PERMIT APPLICATIONS, PLANS AND REVIEWS. |
| |
| 16. FBC 107, AN INDEX LOCATED AT THE BEGINNING OF THE |
| DIGITAL ROLL OF PLANS WOULD BE HELPFUL. THE PLANS ARE |
| ORDERED IN THIS MANNER: |
| |
| INDEX FOR PHASE I FOR ARCH/STRUCTURAL ONLY |
| PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE, |
| STRUCTURAL, DEMO, SITE, ARCH |
| INDEX FOR PHASE II FOR ARCH/STRUCTURAL ONLY |
| PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE, |
| STRUCTURAL, DEMO, SITE, ARCH |
| FMEP INDEX FOR PHASE II |
| FMEP SHEETS |
| FMEP INDEX FOR PHASE I |
| FMEP INDEX |
| |
| SINCE THERE ARE 577 PLAN PAGES FOR THIS PROJECT, PLEASE |
| PROVIDE AN INDEX AT THE BEGINNING OF THE DIGITAL ROLL. |
| ALTHOUGH A COMPLETE SHEET INDEX IS NOT REQUIRED, AN |
| INDEX WHICH SHOWS THE SERIES ORDER WOULD BE HELPFUL, |
| ESPECIALLY AS PHASE II FMEP PAGES ARE LOCATED BEFORE |
| PHASE I FMEP. |
| |
| 17. FBC 107, SHEET WHICH IS LABELED 201 - A626.PDF IS |
| IN THE MIDDLE OF THE CIVIL SHEETS FOR PHASE II. PLEASE |
| COORDINATE TO HAVE THIS PAGE RELOCATED SO IT IS IN |
| NUMERICAL ORDER, ARCHITECTURAL SHEETS. |
| |
| THIS ALSO APPLIES TO SHEETS: |
| 202 ? A630 (BETWEEN L AND S SHEETS, PHASE II) |
| 204 - A642 |
| 206 - A644 |
| 209 - IN101C |
| 210 - IN101D |
| 2-110 ? G000B |
| |
| THIS MAY NOT BE A COMPLETE LIST. CHECK ALL PRIOR TO |
| RESUBMITTAL. DUE TO NAMING CONVENTION, THE SERIES OF |
| SHEETS DO NOT APPEAR IN THE ORDER ON THE DRAWING |
| SCHEDULE, AND FMEP ARE NOT INCLUDED (HAVE THEIR OWN |
| INDEXES). DUE TO THE SIZE OF THIS PLAN, WHILE NOT |
| REQUIRED TO BE IN ORDER OF THE INDEX (ALTHOUGH THAT |
| WOULD BE HELPFUL), THE SERIES SHOULD BE TOGETHER AND IN |
| THE ORDER ON THE INDEX FOR THAT SERIES. |
| |
| 18. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS |
| REQUIRED. |
| |
| 19. G001, IT APPEARS THAT THE PROPOSED BUILDING WILL BE |
| USED AS EITHER ASSISTED LIVING OR INDEPENDENT LIVING |
| WHICH ARE REGULATED BY FAIR HOUSING ACT, FBC 2010 |
| ACCESSIBILITY. SHEET G001 HAS A LINE WHICH STATES THAT |
| PER 11 9.1.4, NINE UNITS ARE REQUIRED TO BE ACCESSIBLE. |
| PLEASE REVISE THIS INFORMATION TO CLARIFY. IF THIS IS |
| EITHER ASSISTED LIVING OR INDEPENDENT LIVING, |
| ACCESSIBILITY DOES NOT APPLY TO THE RESIDENTIAL PORTION |
| OF THE BUILDING, BUT APPLIES TO PORTIONS OF THE AMENITY |
| AND BUSINESS AREAS. ALSO, THIS REFERENCE APPEARS TO BE |
| FROM FBC 2007; THIS SPECIFIC SECTION IS FOR TRANSIENT |
| LODGING. PER FAIR HOUSING, ALL UNITS ARE TO CONSIDERED |
| COVERED UNITS AND ARE TO COMPLY WITH THE REQUIREMENTS |
| IN SECTION 3, 100.205 C. |
| |
| IF THE UNITS ARE NOT EITHER INDEPENDENT OR ASSISTED |
| LIVING UNITS, PLEASE REVISE PLAN TO CLARIFY. |
| |
| 20. UNIT PLANS HAVE NOT BEEN REVIEWED AS ALL |
| INFORMATION PROVIDED INDICATES THAT THEY ARE SUBJECT TO |
| FAIR HOUSING, BUT NO INFORMATION REGARDING WAS PROVIDED |
| ON THE UNIT PLANS, AND ACCESSIBLE UNITS ARE SHOWN. A |
| REVIEW CANNOT BE DONE WITHOUT MORE INFORMATION, FBC |
| 107. |
| |
| 21. PHASE II SHEET A101, CLARIFY USE OF GUEST ROOM 105 |
| (REVISE PLAN TO INCLUDE INTENDED USE). IF THIS IS A |
| ROOM AVAILABLE FOR RENT, IT APPEARS THAT THIS UNIT |
| WOULD BE SUBJECT TO ALL REQUIREMENTS OF FBC 2010 |
| ACCESSIBILITY. ALSO, ONE PUBLIC ACCOMODATION ROOM MAY |
| CAUSE OTHER AREAS (SUCH AS THE POOL) TO BE SUBJECT TO |
| ACCESSIBILITY (IN PARTICULAR, SEE FBC 2010 |
| ACCESSIBILITY 1004, 1009). |
| |
| 22. G001, REQUIREMENTS ARE STATED BUT SOME THINGS ARE |
| NOT CLEAR AS TO JOB SPECIFIC APPLICABLILITY. WILL THIS |
| BUILDING BE CONSIDERED AN ADDITION TO THE EXISTING |
| RESIDENTIAL TOWER (TRADITION 1), OR IS IT DESIGNED AS A |
| SEPARATE BUILDING? SHOW COMPLIANCE WITH FBC 2010 TABLE |
| 503. NO INFORMATION PROVIDED REGARDING THE EXISTING |
| BUILDING. |
| |
| EITHER THIS IS ONE LARGE BUILDING (PROVIDE INFORMATION |
| REGARDING THE EXISTING BUILDING) OR TWO SEPARATE |
| BUILDINGS WITH AN ASSUMED PROPERTY LINE (SHOW |
| COMPLIANCE FBC 705.3. REVISE PLAN TO CLARIFY. |
| |
| 23. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE |
| BUILDINGS, A 2 HOUR FIRE WALL IS SHOWN, 3 HOURS |
| REQUIRED PER FBC TABLE 706.4. |
| |
| 24. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE |
| BUILDINGS, THE FIRE WALL IS TO COMPLY WITH THE |
| REQUIREMENT OF 706.2, STRUCTURAL INTEGRITY. |
| |
| 25. G101, CLARIFY THE EXIT STRATEGY FOR THE CONNECTING |
| DOOR BETWEEN TRADITION I AND II. IF THIS IS AN EXIT FOR |
| BOTH SIDES, HOW WILL THE DOOR SWING IN BOTH DIRECTIONS, |
| AND HOW WOULD YOU CONTROL CONFLICTS SUCH AS OCCUPANTS |
| TRAVELING IN OPPOSITE DIRECTIONS? IT IS NOT CLEAR HOW |
| THE FIRE WALL WILL ALLOW OCCUPANTS TO PASS THROUGH. IF |
| THIS IS TO BE A MCKEON DOOR, IT IS NOT CLEAR HOW THIS |
| WILL MEET THE STRUCTURAL INTEGRITY REQUIREMENT. |
| |
| REVISE PLAN TO INCLUDE A DETAIL FOR THE PROPOSED FIRE |
| WALL AND CLARIFY THE ABOVE CONCERNS, FBC 107. |
| |
| 26. G101, CORRIDOR 187 IS NOT A RATED CORRIDOR BUT |
| SERVES THE RESIDENTIAL UNITS AS THERE IS AN EXIT SIGN |
| FROM CORRIDOR 188 TO CORRIDOR 187, FBC TABLE 1018.1. |
| THERE IS A NOTE WHICH STATES THAT TRAVEL DISTANCE IS |
| 134FT, BUT IT IS NOT CLEAR WHERE THIS IS APPLICABLE. |
| |
| 27. A101, FBC 1022.4, STAIR 1, OPENINGS INTO THE STAIR |
| ARE LIMITED TO THOSE REQUIRED FOR EXITING. THE |
| RATIONALE FOR HAVING AN EXIT FOR THE CHILLERS GO |
| THROUGH THE EXIT FOR THE RESIDENTIAL IS NOT CLEAR; IF |
| TWO EXITS ARE REQUIRED FROM THIS SPACE, IT APPEARS THAT |
| THERE IS ENOUGH ROOM TO ADD A DOOR IN ANOTHER LOCATION. |
| |
| 28. SOME MECHANICAL SHEETS DO NOT SHOW THE REQUIRED |
| FIRE RATING (FBC708) FOR THE ADJACENT SHAFT FOR THE |
| PRESSURIZED STAIRS (FOR INSTANCE, 305 M202A), PLEASE |
| CORRELATE. |
| |
| 29. G001 MAKES REFERENCE TO THE EXCEPTION FOR A 1 HOUR |
| SHAFT RATING PER FBC 403.2.1.2. INCORPORATE THIS |
| REQUIREMENT INTO THE FIRE PROTECTION SHEETS. A BUILDING |
| REVIEW WILL BE DONE IN ADDITION TO FIRE AND MECHANICAL |
| REVIEWS WHEN THE FIRE SPRINKLER PERMIT APPLICATION AND |
| PLANS ARE SUBMITTED. NOTE THAT FLOOR PLANS SHOW A 2 |
| HOUR SHAFT RATING. CLARIFY WHERE THIS EXCEPTION WILL |
| APPLY. IF THIS EXCEPTION DOES NOT APPLY, REMOVE FROM |
| PLAN AND ADVISE. |
| |
| 30. G101 AND OTHER PAGES, REVISE LIFE SAFETY PLAN TO |
| SHOW EXIT DISCHARGE TO THE PUBLIC WAY FOR ALL EXITS. |
| |
| EXIT DISCHARGE NOT CLEAR FOR THE EXITS WHICH OPEN TO |
| THE POOL AREA AND FOR THE EXITING FROM CORRIDOR THROUGH |
| THE DINING ROOM EXTENSION, FBC 1027. EXIT STRATEGY IS |
| NOT CLEAR. SEE FIRE COMMENTS. SEE ALSO 1004.8 (OUTDOOR |
| AREAS), 1006.1.1 (ILLUMINATION). TWO REQUIRED EXITS |
| FROM DINING ROOM OPEN INTO THE POOL AREA. THE POOL AREA |
| ITSELF HAS A HIGH OCCUPANT LOAD. IT IS NOT CLEAR HOW |
| HUNDREDS OF OCCUPANTS WILL TRAVEL FROM THE POOL AREA TO |
| THE PUBLIC WAY; ONLY A SMALL GATE IS SHOWN AND THE |
| OCCUPANTS WILL HAVE TO CROSS AN AREA MARKED FOR THE |
| FIRE TRUCK. |
| |
| OTHER EXITS SHOW SIDEWALKS BUT ACCESS TO THE PUBLIC WAY |
| (OR OTHER APPROVED AREA) IS NOT CLEAR. FOR INSTANCE, |
| FP001 SHOWS A SIDEWALK FOR EXIT STAIRS 3 AND 4 WHICH |
| LEADS BACK INTO THE BUILDING. |
| |
| 31. G101, STAIR 4, FBC 1022.6, IN ORDER TO FACILITATE |
| PHASE II, THE EXTERIOR WALL IS TO BE FIRE RESISTANCE |
| RATED (LESS THAN 180DEGREES WHEN PHASE II IS BUILT). |
| |
| 32. G101, THEATER VESTIBULE AND MULTIPURPOSE ROOM (ALSO |
| REFERRED TO AS THEATER ON SHEET G001, USE GROUP |
| CLASSIFICATION) IS SHOWN AS GROUP A1. SHEET G001 ALSO |
| REFERS TO MULTIPURPOSE AS A3. |
| |
| 33. A101, SHOW 18IN MANEUVERING CLEARANCE PULL SIDE, |
| FOR THE FOLLOWING DOORS PER FBC 2010 ACCESSIBILITY |
| 404.2.4: |
| |
| AEROBICS ROOM 146 |
| ACCESSIBLE CHANGING ROOM 149 |
| |
| 34. A101A, WHEN RESUBMITTING, INCLUDE SEATING PLAN FOR |
| THE MULTIPURPOSE ROOM. |
| |
| NOTE: SEATING REVIEWED IN PLANGRID, A101A. FORTY SEVEN |
| FIXED SEATS SHOWN, OCCUPANT LOAD IS 51. |
| |
| REVISE PLAN TO INCLUDE INFORMATION REGARDING THE USE OF |
| THIS SPACE. WILL THIS BE ONLY FOR RESIDENTS AND THEIR |
| GUESTS (FAIR HOUSING), OR WILL TICKETS EVER BE SOLD TO |
| THE GENERAL PUBLIC (ACCESSIBILITY)? |
| |
| NO ACCESSIBLE SEATING IS SHOWN. SEE FBC 2010 |
| ACCESSIBILITY 802 REGARDING WHEELCHAIR SPACES, SIGHT |
| LINES, AND COMPANION SPACES REQUIRED. REVISE PLAN TO |
| CLARIFY COMPLIANCE FOR ACCESSIBILITY OR FAIR HOUSING |
| (REQUIREMENT THAT ALL PUBLIC AND COMMON USE AREAS ARE |
| READILY ACCESSIBLE TO AND USABLE BY DISABLED PERSONS) |
| AS APPLICABLE. |
| |
| 35. EXERCISE AREAS, MULTIPURPOSE ROOM (SEE OTHER |
| COMMENT), SALON, SPA, POOL, DINING, GUEST ROOM, ALL |
| COMMON AREAS, REVISE PLAN TO INDICATE WHETHER THESE |
| AREAS ARE FOR RESIDENTS AND THEIR GUESTS ONLY (SUBJECT |
| TO FAIR HOUSING ONLY) OR IF THE PORTION OF THE FACILITY |
| IS OPEN TO NON RESIDENTS FOR A FEE, OR AVAILABLE FOR |
| EMPLOYEE USE (SUBJECT TO ACCESSIBILITY AS WELL AS FAIR |
| HOUSING). |
| |
| 36. G101 AND A213, THE DOORS FOR THE MULTI PURPOSE ROOM |
| INCLUDE SIDELIGHTS WHICH APPEAR TO BE IDENTICAL TO THE |
| DOORS BUT DO NOT OPERATE. SEE FBC 1008.1, REVISE PLAN |
| TO SHOW HOW THE DOORS WILL BE EASILY DISTINGUISHABLE |
| FROM THE INOPERABLE SIDELITES. |
| |
| 37. G101 OR RELATED A SHEET, REVISE PLAN TO INCLUDE |
| INFORMATION REGARDING WHAT WILL BE STORED IN THE |
| CHEMICAL ROOM 137A (ASSOCIATED WITH SALON), FBC 107, |
| FBC 307. PLAN SHOULD INCLUDE A BRIEF DESCRIPTION OF |
| CHEMICALS TO BE STORED AND, IF ANY CHEMICALS ARE THOSE |
| LISTED IN FBC307, INCLUDE CHEMICAL AND AMOUNT TO SHOW |
| THAT IT IS BELOW THE ALLOWABLE LIMIT. |
| |
| 38. G101, AEROBICS 146 AND FITNESS 143 APPEAR TO HAVE |
| AN OCCUPANT LOAD OVER 50, BUT SECOND EXIT ACCESS NOT |
| CLEAR. AEROBICS ROOM HAS TWO DOORS BUT BOTH LEAD TO |
| SAME CORRIDOR (COMMON PATH). FITNESS ROOM HAS ONLY ONE |
| EXIT ACCESS. TWO MEANS OF EGRESS REQUIRED FROM SPACES |
| WITH AN OCCUPANT LOAD OVER 50, TWO EXITS REQUIRED FOR |
| THE AREA. |
| |
| 39. G101, CORRIDOR 146A APPEARS TO EXCEED DEAD END |
| CORRIDOR LIMIT, FBC 1018.4. REVISE PLAN TO ADDRESS. |
| |
| 40. G101, FBC 303, FITNESS LOUNGE, FITNESS, AEROBICS, |
| BREAK ROOM, CONFERENCE ROOM, LIBRARY ARE ASSEMBLY |
| OCCUPANCY, FBC 303. PROVIDE OCCUPANT LOAD (TABLE |
| 1004.1.1, EXERCISE ROOMS) AND SEPARATION BETWEEN |
| ASSEMBLY AND BUSINESS UNLESS EXCEPTION APPLIES. IF |
| COVERED UNDER AN EXCEPTION, INCORPORATE INTO PLAN (FBC |
| 508.1, 508.2 AND COMMENTARY). |
| |
| 41. LIVING ROOM LIBRARY IS SHOWN AS A CIRCULATION AREA |
| WITH OCCUPANT LOAD BASED ON 200 SF PER PERSON. FBC |
| TABLE 1004, READING ROOMS ARE TO HAVE AN OCCUPANT LOAD |
| OF 50 SF PER PERSON. REVISE PLAN TO CLARIFY THE USE AND |
| OCCUPANT LOAD FOR THIS AREA. |
| |
| 42. G101, REVISE PLAN TO INCLUDE OCCUPANT LOAD AND AREA |
| FOR THE FITNESS ROOM AND AEROBICS ROOM (SEPARATELY AS |
| THE LARGER AREA CAN BE COMBINED TO TWO SMALLER AREAS). |
| AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA |
| OCCUPANT LOAD WILL BE OVER 50, DOORS ARE TO SWING IN |
| THE DIRECTION OF TRAVEL, FBC 1008.1.2. |
| |
| 43. AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA |
| OCCUPANT LOAD WILL BE OVER 50, FIRE EXIT HARDWARE OR |
| PANIC HARDWARE REQUIRED FOR THOSE DOORS AND ALL OTHER |
| DOORS IN THE MEANS OF EGRESS, FBC 1008.1.10, 1004.9. |
| |
| 44. EGRESS GATE IS REQUIRED TO HAVE EITHER FIRE EXIT |
| HARDWARE OR PANIC HARDWARE, FBC 1008.1.10, 1008.2. |
| REVISE PLAN TO INCLUDE THE REQUIREMENT OR DETAIL. |
| |
| 45. G101, FBC 911.1.1, FIRE COMMAND CENTER ROOM SHALL |
| BE A MINIMUM OF 200 SF AND A MINIMUM DIMENSION OF 10FT; |
| REVISE PLAN TO SHOW COMPLIANCE WITH SIZE REQUIREMENT. |
| |
| 46. G101, FBC 911.1.2, FIRE COMMAND CENTER ROOM |
| REQUIRES A 1 HOUR FIRE BARRIER; THIS IS SHOWN AT THE |
| CORRIDOR BUT NOT BETWEEN FIRE COMMAND CENTER AND |
| CHILLERS RM 182. |
| |
| 47. G101, PROVIDE OCCUPANT LOAD FOR DINING F. IF THE |
| OCCUPANT LOAD IS OVER 50, TWO EXITS REQUIRED. REQUIRED |
| MEANS OF EGRESS DOORS ARE TO BE SIDE SWINGING; A |
| SLIDING DOOR IS SHOWN AS SECOND MEANS OF EGRESS, FBC |
| 1008.1.2. |
| |
| 48. FBC 911.1.4, LAYOUT OF FIRE COMMAND CENTER AND ALL |
| FEATURES REQUIRED BY 911.1.5 TO BE SUBMITTED AND |
| APPROVED PRIOR TO INSTALLATION. |
| |
| 49. TK G102, RATING BETWEEN STAIR 2, STAIR 4 IS SHOWN |
| BETWEEN ADJACENT SHAFTS FOR PRESSURIZATION ON SHEET |
| M202A, G102 SHOWS THE RATING OUTSIDE THE SHAFT (BETWEEN |
| SHAFT AND CORRIDOR). |
| |
| 50. G102 AND OTHER FLOORS, PROVIDE OCCUPANT LOAD AND |
| OCCUPANCY CLASSIFICATION FOR THE COMMUNITY ROOM AND |
| CONCIERGE 936, FBC 107, SEE ALSO FBC 508.2. |
| |
| NOTE THAT IF OCCUPANT LOAD IS 50 OR MORE, TWO EXITS ARE |
| REQUIRED. |
| |
| 51. A610, REVISE DOOR NOTE (GENERAL GLAZING |
| REQUIREMENTS) TO UPDATE CODE REFERENCE (FBC 2007). |
| |
| 52. DOOR SCHEDULE HAS A COLUMN FOR ?ELECTRIC? BUT THAT |
| COLUMN IS BLANK. IT APPEARS THAT THIS SHOULD BE |
| APPLICABLE FOR SLIDING DOORS IN THE REQUIRED MEANS OF |
| EGRESS AND EXIT. EXIT DOOR 122 (DOOR TYPE G1) SHOULD |
| ALSO COMPLY WITH FBC 1008.1.4.2, 1008.1.4.3. |
| |
| 53. A601 AND G101, DOORS IN FIRE BARRIERS REQUIRE A 45 |
| MINUTE FIRE RATING, FBC TABLE 715.4. IT IS NOT CLEAR |
| WHICH DOORS ARE BEING CONSIDERED IN A CORRIDOR RATHER |
| THAN AN OCCUPANCY SEPARATION. SEE DOORS 173C, 182, 172, |
| 183. |
| |
| DOOR 173C IS A 20 MINUTE DOOR, BUT THE CORRIDOR 184 |
| RATING IS NOT CONTINUOUS AS IT APPEARS TO TRANSITION |
| INTO THE GALLERY. USE OF CORRIDORS, INCIDENTAL AND |
| ACCESSORY USES FBC 508 ARE NOT ENTIRELY CLEAR. IF ANY 1 |
| HOUR RATINGS ON THE PLAN ARE REMOVED WHEN RESUBMITTING, |
| PLEASE ALSO NOTE ALSO SMOKE AND PROTECTION REQUIREMENT |
| IN 508.2.5.2. |
| |
| 54. S8.1 AND G000 PHASE I AND II, MAP FOR IMPORTANCE |
| FACTOR III & IV IS INCLUDED, BUT SHEET S8.1 STATES |
| DESIGN CRITERIA AS RISK CATEGORY II; PLEASE CORRELATE. |
| |
| IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL |
| BUILDING OCCUPANT LOAD. AT THIS POINT IT IS NOT CLEAR |
| WHETHER THE TOTAL OCCUPANT LOAD SHOULD INCLUDE |
| TRADITION I AND TRADITION II, OR IF THE TWO WILL BE |
| DESIGNED AS SEPARATE BUILDINGS. |
| |
| 55. S8.1, SOME STANDARD REFERENCES REFER TO "LATEST |
| EDITION." PLEASE REVISE TO BE THE VERSION SPECIFIED IN |
| FBC CHAPTER 35. |
| |
| 56. S9.1, SECTION 9 AND OTHER PLACES, PLYWOOD |
| SPECIFIED. FBC 603.1, PLEASE REVISE TO FRT. |
| |
| 57. AN ENCLOSED ELEVATOR LOBBY IS NOT SHOWN. FBC |
| 708.14.1, PLEASE ADVISE AS TO WHICH EXCEPTION IS BEING |
| USED IN THIS DESIGN AND WHERE THIS INFORMATION CAN BE |
| LOCATED ON THE PLAN. |
| |
| 58. A002 AND OTHER SHEETS REFER TO UL ASSEMBLIES. |
| INCORPORATE DETAILS WITH SPECIFIC OPTIONS INTO THE PLAN |
| OR THIS PERMIT WILL BE ISSUED WITH PROVISO THAT THE |
| DETAILS BE SUBMITTED PRIOR TO INSTALLATION, AFTER |
| REVIEW BY DESIGNER OF RECORD. |
| |
| 59. A101, A "W" SHAPE APPEARS IN FRONT OF DOORS AT 186 |
| ELEVATOR LOBBY AND 118 WOMEN WHICH DOES NOT APPEAR ON |
| OTHER SHEETS, CLARIFY, FBC 107. |
| |
| 60. FBC 1207, PROVIDE THE FOLLOWING TEST REPORTS FOR |
| THE FLOORING UNDERLAYMENT WILL BE REQUIRED AS |
| APPLICABLE (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR |
| SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR |
| LESS ARE ACCEPTABLE): |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| NOT BE ALTERED. |
| |
| PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| BELOW WILL NOT BE ALTERED. |
| |
| PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| E 84 OR UL 723. |
| |
| IF THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT |
| ISSUANCE, PERMIT WILL BE ISSUED WITH PROVISO THAT THIS |
| BE SUBMITTED PRIOR TO INSTALLATION. REVIEW BY DESIGNER |
| OF RECORD REQUIRED PRIOR TO SUBMITTAL, FBC 107.3.4.1. |
| |
| 61. PROVIDE THE GEOTECHNICAL REPORT FOR THIS PROJECT, |
| FBC 1803. THE SOILS REPORT IS TO BE REVIEWED BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| |
| 62. FBC 107, PROVIDE THE SURVEY FOR THIS PROPERTY. |
| |
| 63. THE PLANS INDICATE THERE WILL BE A POOL BUILT VERY |
| CLOSE TO THIS BUILDING PLEASE PROVIDE HOW THE |
| FOUNDATION /FOOTING WILL BE PRESERVED WHILE THE POOL IS |
| BEING EXCAVATED? 1808.7. |
| |
| 64. 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE |
| PROTECTION SHALL BE PROVIDED BY REGISTERED |
| TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES, |
| BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR |
| OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE |
| TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| AND CONSUMER SERVICES." |
| |
| 65. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 66. PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL |
| COMPLY WITH : |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF |
| CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO |
| THE PLAN. |
| |
| 67. G101, REVISE LIFE SAFETY PLAN TO INCLUDE WORST CASE |
| WITH TRAVEL DISTANCE FOR EACH AREA (NOT NECESSARY FOR |
| EACH ROOM). PATH OF TRAVEL IS TO BE SHOWN ACROSS THE |
| DIAGONAL OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN |
| ALONG THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS |
| FURNITURE WILL BE PLACED IN THE CENTER OF THE ROOM, THE |
| PATH SHOULD BE MEASURED ALONG THE ROOM PERIMETER. |
| |
| 68. SEE OTHER COMMENTS, SHAFT RATING PROPOSED NOT |
| CLEAR. PLEASE CLARIFY SHAFT RATING FOR ELEVATOR 2 PHASE |
| I, A 1 HOUR SHAFT IS SHOWN, BUT A 2 HOUR SHAFT IS SHOWN |
| FOR ELEVATOR 1 |
| |
| 69. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE |
| (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY |
| AS APPLICABLE. PLEASE ALSO REVISE OTHER AFFECTED |
| SHEETS. |
| |
| 70. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES, |
| PLYWOOD SHEATHING SHOWN. FBC 602.1, REVISE TO INCLUDE |
| REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND |
| OTHER SHEETS), FBC 603.1.1.1.3. |
| |
| 71. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC |
| SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS. |
| ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR |
| ACCESS FOR MAINTENANCE, FBC 107. |
| |
| 72. 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY |
| WITH THIS SECTION. |
| |
| 73. PLANS IN MANY LOCATIONS USE THE LANGUAGE "UNDER |
| SEPARATE PERMIT" (FOR INSTANCE, SHEET 036 - S6.2). IF |
| ALL WORK TO BE INCLUDED IN THIS PERMIT, REVISE |
| LANGUAGE. IF THIS IS PROVIDED FOR INFORMATION ONLY, |
| PLEASE ADVISE. |
| |
| 74. INCORPORATE FIRE RATING REQUIREMENTS AND DETAILS |
| FOR THE FLOOR, STRUCTURAL ELEMENTS FBC TABLE 601. |
| |
| 75. PLEASE IDENTIFY THE RECTANGLE ADJACENT TO THE SINK |
| IN THE GUEST ROOM, S1.2 AND OTHER PAGES. |
| |
| 76. PROVIDE A DETAIL FOR THE OVERFLOW SCUPPER, FBC 107 |
| (OR ADVISE AS TO WHERE THIS CAN BE LOCATED). |
| |
| |
| |
| |
| |
| |
| |