1 |
|
Notes |
Date |
Text |
2015-06-01 09:51:37 | PLAN DENIED | | 1) PROVIDE ENERGY CALCULATIONS WITH THE | | PLANS. PER SECTION 503.2.1 CALCULATIONS | | OF HEATING AND COOLING LOADS. 2010 | | FLORIDA ENERGY CODE. | | 2) PROVIDE FRESH AIR CALCULATIONS ON PLAN | | PER TABLE 403.3 FBC (M) 2010 | | 3) DRYER BOOSTER FANS ARE NOT PERMITTED | | IN THE CITY OF WEST PALM BEACH PER WPB. | | FIRE DEPARTMENT. | | 4) MISSING FIRE DAMPERS ON 1ST FLOOR | | REFER TO SECTION 607 FBC (M) 2010 | | 5) PROVIDE NOA ON ALL OUTSIDE GRILLS | | PER SECTION 107.3.4.1 GENERAL 2010 FBC. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|