Plan Review Notes
Plan Review Notes For Permit 14120909
Permit Number 14120909
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-01 09:51:37PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH THE
 PLANS. PER SECTION 503.2.1 CALCULATIONS
 OF HEATING AND COOLING LOADS. 2010
 FLORIDA ENERGY CODE.
 2) PROVIDE FRESH AIR CALCULATIONS ON PLAN
 PER TABLE 403.3 FBC (M) 2010
 3) DRYER BOOSTER FANS ARE NOT PERMITTED
 IN THE CITY OF WEST PALM BEACH PER WPB.
 FIRE DEPARTMENT.
 4) MISSING FIRE DAMPERS ON 1ST FLOOR
 REFER TO SECTION 607 FBC (M) 2010
 5) PROVIDE NOA ON ALL OUTSIDE GRILLS
 PER SECTION 107.3.4.1 GENERAL 2010 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  