Plan Review Notes
Plan Review Notes For Permit 14120909
Permit Number 14120909
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-03-13 13:52:384920 LORING DRIVE
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 GENERAL: INDICATE THE LOCATION AND SIZES OF ANY
 PROPOSED CONSTRUCTION TRAILERS/MODULAR BUILDINGS. PER
 NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE
 EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED OCCUPANCY.
  
 SHEET G101: FIRE COMMAND CENTER (#182B) SHALL BE AT
 LEAST 200 SQUARE FEET AND HAVE A MINIMUM DIMENSION OF
 10 FEET (FBC 911.1.3). PER NFPA 1 SECTION 11.9.2 THE
 EMERGENCY COMMAND CENTER SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY A FIRE BARRIER HAVING A
 FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 PER NFPA 1 SECTION 11.9.4 THE FOLLOWING SHALL BE
 PROVIDED IN THE EMERGENCY COMMAND CENTER:
 (1) THE FIRE DEPARTMENT COMMUNICATION UNIT
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT, AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE
 (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS
 FOR THE BUILDING
  
 PER NFPA 1 SECTION 11.9.5 WHERE OTHERWISE REQUIRED, THE
 FOLLOWING DEVICES OR FUNCTIONS SHALL BE PROVIDED WITHIN
 THE EMERGENCY COMMAND CENTER:
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT
 (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE
 ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 11.9.6 EMERGENCY COMMAND CENTER ACCEPTANCE TESTING.
 DEVICES, EQUIPMENT, COMPONENTS, AND SEQUENCES SHALL BE
 INDIVIDUALLY TESTED IN ACCORDANCE WITH APPROPRIATE
 STANDARDS AND MANUFACTURERS? DOCUMENTED INSTRUCTIONS.
  
 SHEET G101: PER TABLE 7.3.1.2, KITCHEN SPACES SHALL
 HAVE AN OCCUPANT LOAD FACTOR OF 100 SQUARE FEET PER
 PERSON IN LIEU OF THE 200 SQ.FT. INDICATED.
  
 SHEET G101: PROVIDE AN OCCUPANT LOAD FOR BREAKROOM
 #167.
  
 SHEET G101: LIBRARY #121, FITNESS #143, AEROBICS #145
 AND CONFERENCE #112 ARE TREATED AS ASSEMBLY USE SPACES
 IN THE FIRE CODE AND NEED AN OCCUPANT LOAD BASED UPON
 THE OCCUPANT LOAD FACTORS FOUND IN TABLE 7.3.1.2.
  
 ***SHEET G101: SEVERAL EXITS APPEAR TO ROUTE AND MERGE
 EXITING OCCUPANTS AT THE POOL DECK AREA. THERE DOES NOT
 APPEAR EXTERIOR EXIT SIGNAGE, EMERGENCY LIGHTING OR
 SUFFICIENT EXIT WIDTH (1 EGRESS GATE) TO HANDLE THE
 OCCUPANT LOAD. WHERE IS THE PUBLIC WAY? HOW WILL THE
 POOL DECK EGRESS ROUTES BE MAINTAINED UNOBSTRUCTED FOR
 THE LIFE OF THE BUILDING?
  
 SHEET G101: CORRIDOR #146A CREATES A DEAD-END THAT
 EXCEEDS 20 FEET. PER SECTION12.2.5.1.3 DEAD-END
 CORRIDORS SHALL NOT EXCEED 20 FEET.
  
 SHEET C103 &C106: SOUTH ACCESS ROAD INDICATES A 20 FOOT
 WIDE FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST
 AREA INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE
 20 FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION
 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS
 SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
 SHEET C107: FIRE HYDRANTS SHALL BE INSTALLED,
 INSPECTED, TESTED AND APPROVED BY THE FIRE DEPARTMENT
 PRIOR TO VERTICAL CONSTRUCTION.PER SECTION 18.3.4.1
 (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH
 CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO
 THE BACKSIDE OF THE STEAMER CAP.
  
 SHEET C107: NORTHWEST PIV - PER NFPA 24 SECTION 6.2.1,
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET C107: PER FBC SECTION403.3.2 WATER SUPPLY TO
 REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING
 SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER
 MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY
 PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE
 SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE
 PUMPS TO OPERATE.
  
 SHEET A101: CHILLER #182 HAS A DOOR LEADING INTO THE
 FIRE RATED STAIR ENCLOSURE. PER SECTION 7.1.3.2.1 DOORS
 INTO EXIT ENCLOSURES ARE ONLY PERMITTED FOR NORMALLY
 OCCUPIED ROOMS.
  
 SHEET A101C: THE COOKING GRILL LOCATED ON THE POOL DECK
 SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST
 10 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES
 PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED
 UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH
 NFPA 96.
  
 SHEET A101D: PLANS SHOW OCCUPANTS USING CORRIDOR #185
 AS A MEANS OF EXIT ACCESS; HOWEVER, BOTH SIDES OF THE
 DOOR APPEAR TO BE ACCOMODATING MORE THAN 50 PERSONS AND
 WOULD NEED TO SWING IN BOTH DIRECTIONS OF EGRESS.
  
 SHEET A102B: TRASH ROOM #205C WALL ADJACENT TO
 RESIDENTIAL ROOM DOES NOT APPEAR TO BE FIRE RATED.
 TYPICAL ALL LEVELS.
  
 SHEET A490: PER SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET FP001: ALL NFPA STANDARDS REFERENCES SHALL BE
 UPDATED TO REFLECT THOSE ADOPTED IN THE 5TH EDITION OF
 FLORIDA FIRE PREVENTION CODE EFFECTIVE DECEMBER 31,
 2014. FOR EXAMPLE. THE SPRINKLER AND STANDPIPE DESIGNS
 SHALL CONFORM TO THE 2010 EDITION OF NFPA 13 AND NFPA
 14 RESPECTIVELY.
  
 STANDPIPE DESIGN: PROVIDE 2-1/2" OUTLETS ONLY. REMOVE
 THE 1-1/2" REDUCING COUPLINGS ON ALL FIRE DEPARTMENT
 VALVES.
  
 SHEET FP201B: TRASH ROOM #105C IS MISSING THE
 DESIGNATION FOR ORDINARY HAZARD SPRINKLER PROTECTION.
 TYPICAL ALL FLOORS.
  
 SHEET FP402: ENGINEERING DOCUMENTS ARE REQUIRED TO
 INDICATE THE WATER SUPPLY RESULTS FROM A CURRENT
 HYDRANT FLOW TEST. FIRE PUMP SCHEDULE DOES NOT INDICATE
 A RATED PRESSURE OR HORSEPOWER RATING. THE ENGINEERING
 DOCUMENTS WILL BE REQUIRED TO DETERMINE IF PRESSURE
 REDUCING VALVES ARE NEEDED ON THE STANDPIPES AND
 SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL ALSO
 REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH DRAIN
 RISER AS SHOWN ON THE PLANS.
  
 SHEET FP402: PER FBC SECTION403.3.2 WATER SUPPLY TO
 REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING
 SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER
 MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY
 PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE
 SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE
 PUMPS TO OPERATE.
  
  
 SHEET M201B: ALL HVAC KEY NOTES APPEAR TO BE MISLABLED.
  
  
  
  
  
  
 PHASE 2 - FIRE DEPARTMENT REVIEW
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE
 EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED OCCUPANCY.
  
 SHEET G101: THE FIRE RATING FOR STAIR #4 DOES NOT
 CONTINUE TO THE EXTERIOR WALLS OR DOORS. PER SECTION
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES, THE
 BUILDING ENCLOSURE WALLS WITHIN 10 FEET HORIZONTALLY OF
 THE NONRATED WALL OR UNPROTECTED OPENING SHALL BE
 CONSTRUCTED AS REQUIRED FOR STAIRWAY ENCLOSURES,
 INCLUDING OPENING PROTECTIVES. PER SECTION 7.2.2.5.2.2
 CONSTRUCTION SHALL EXTEND VERTICALLY FROM THE FINISHED
 GROUND LEVEL TO A POINT 10 FEET ABOVE THE TOPMOST
 LANDING OF THE STAIRS OR TO THE ROOFLINE, WHICHEVER IS
 LOWER.
  
 SHEET L101: SOUTH ACCESS ROAD INDICATES A 20 FOOT WIDE
 FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST AREA
 INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE 20
 FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION
 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS
 SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
  
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  