Plan Review Notes
Plan Review Notes For Permit 14120909
Permit Number 14120909
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-23 15:12:326/12/2015
 PROJECT: MORSE SENIOR CENTER PHASE
 PERMIT#: 14120909
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) CLARIFICATION IS REQUIRED. THE APPLICATION SUBMITTED
 WITH THESE PLANS STATE "FOUNDATION ONLY" HOWEVER THE
 PLANS ARE A FULL SET FOR CONSTRUCTION OF A HIGH RISE.
  
 2) G001
 UNDER APPLICABLE CODES LIST TOP LEFT OF THE PAGE ADD
 THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE
  
 3) E000
 UNDER CODES AND STANDARDS LIST TOP RIGHT OF THE PAGE.
 CHANGE THE 2011 EDITION OF THE NATIONAL ELECTRICAL CODE
 TO THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE.
  
 4) E001
 SUBMIT MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR
 AND CONTROLLER/ATS. INDICATE HP RATING LOAD AND VOLTAGE
 OF FIRE PUMP MOTOR.
 4A) PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE
 PUMP FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL
 WIRING AND PUMP WIRING ARE APPROPRIATELY FIRE
 PROTECTED. INDICATE THE FIRE RATING AND MATERIAL
 REQUIRED. NEC 695.6, 695.14
  
 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORIES.
 5A) VERIFY THE MAXIMUM VOLTAGE DROP IS NOT MORE THAN 15
 % BELOW NORMAL STARTING AND 5% BELOW WHEN THE MOTOR IS
 OPERATING AT 115% OF THE FULL LOAD CURRENT RATING. NEC
 695.6, 695.7
  
 6) CLARIFY THE NEED FOR EMERGENCY POWER AND THEREFORE
 THE NEED FOR LEGALLY REQUIRED EMERGENCY GENERATOR OR
 SIMPLY A STANDBY STAND BY GENERATOR.
  
 7) INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE
 IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY
 INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC
 700.9
  
 8) PROVIDE PROPER SIGNAGE INDICATING THE TYPE AND
 LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC
 700.8
 8A) PERMANENT PLAQUES OR DIRECTORIES SHALL BE INSTALLED
 AT EACH SERVICE DISCONNECT
 DENOTING ALL OTHER SERVICE LOCATION. NEC 230.2(E)
  
 9) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 10) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 12) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL
 POWER AND LIGHTING SYSTEMS. (MANDATORY) FBC SECTION 505
 12A) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 13) NEC 230.9(C) GROUND FAULT PERFORMANCE TESTING. THE
 GROUND-FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE
 TESTED WHEN FIRST INSTALLED ON SITE.
  
 14) PROVIDE A LAYOUT OF ALL ELECTRICAL ROOMS INDICATING
 COMPLIANCE WITH NEC 110.26 FOR ABOUT ALL ELECTRICAL
 EQUIPMENT.
  
 15) E605 INDICATE THE LOAD CALCULATION FOR PANEL
 NLGP1A. THE LOAD CALCULATION IS CUT OFF BY PANEL
 NLGP1B.
  
 16) CORRECT THE NAMING CONVENTION FOR THE ELECTRICAL
 SHEETS. THE ELECTRICAL SHEETS ARE NOT ALL TOGETHER.
  
 17) CORRECT THE NAME OF PANEL RDPB. ON PAGE E005 IT IS
 NAMED RDPB BUT ON PG E001 IT IS NAMED RMDPB
  
 18) E200A
 PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN
 UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE
 FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO
 REFERENCE FOR CLARIFICATION.
 18A) POWER PLAN NOTE 6. CALLS FOR A 20AMP CIRCUIT FOR
 DRYER BOOSTER FANS.
 BOOSTER FANS ARE NOT APPROVED FOR USE IN WPB PER THE
 WPB FIRE DEPT LOCAL CODES AND AMENDMENTS.
  
 19) E200B
 PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN
 UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE
 FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO
 REFERENCE FOR CLARIFICATION.
  
 20) E200C
 CORRECT PLAN NOTE 1 TO PROVIDE AFCI CIRCUIT BREAKER ON
 ALL CIRCUITS WITHIN SLEEPING AREA TO READ ?ALL
 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE BRANCH CIRCUIT.? PER NEC 210.12(B)
 20A) ANYWHERE RECEPTACLES ARE INSTALLED WITHIN 6 FT OF
 THE SINK SHALL BE GFI PROTECTED. NEC 210.8(B)(5)
  
 21) E202CPROVIDE A GFI WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. NEC 210.63 SEE ALSO 210.8(A)(3).
  
 22) E301A
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 23) E301B
 PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS.
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 24) E310B
 PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS.
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 25) E601
 REVISE PANEL SCHEDULE AND LOAD CALCULATION. PANEL C2
 INDICATES A 27KVA DEMAND LOAD AT ONLY 75AMPS. THIS
 SHOULD BE CLOSER TO 130AMPS.
 23A) APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS
 REQUIRED.
  
 26) E602
 APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS REQUIRED
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING,
 LIGHTNING PROTECTION, GENERATORS. HOOD EXHAUST, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,