2015-06-23 15:12:32 | 6/12/2015 |
| PROJECT: MORSE SENIOR CENTER PHASE |
| PERMIT#: 14120909 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) CLARIFICATION IS REQUIRED. THE APPLICATION SUBMITTED |
| WITH THESE PLANS STATE "FOUNDATION ONLY" HOWEVER THE |
| PLANS ARE A FULL SET FOR CONSTRUCTION OF A HIGH RISE. |
| |
| 2) G001 |
| UNDER APPLICABLE CODES LIST TOP LEFT OF THE PAGE ADD |
| THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE |
| |
| 3) E000 |
| UNDER CODES AND STANDARDS LIST TOP RIGHT OF THE PAGE. |
| CHANGE THE 2011 EDITION OF THE NATIONAL ELECTRICAL CODE |
| TO THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE. |
| |
| 4) E001 |
| SUBMIT MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR |
| AND CONTROLLER/ATS. INDICATE HP RATING LOAD AND VOLTAGE |
| OF FIRE PUMP MOTOR. |
| 4A) PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE |
| PUMP FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL |
| WIRING AND PUMP WIRING ARE APPROPRIATELY FIRE |
| PROTECTED. INDICATE THE FIRE RATING AND MATERIAL |
| REQUIRED. NEC 695.6, 695.14 |
| |
| 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING |
| NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR, |
| PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE |
| ACCESSORIES. |
| 5A) VERIFY THE MAXIMUM VOLTAGE DROP IS NOT MORE THAN 15 |
| % BELOW NORMAL STARTING AND 5% BELOW WHEN THE MOTOR IS |
| OPERATING AT 115% OF THE FULL LOAD CURRENT RATING. NEC |
| 695.6, 695.7 |
| |
| 6) CLARIFY THE NEED FOR EMERGENCY POWER AND THEREFORE |
| THE NEED FOR LEGALLY REQUIRED EMERGENCY GENERATOR OR |
| SIMPLY A STANDBY STAND BY GENERATOR. |
| |
| 7) INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE |
| IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY |
| INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC |
| 700.9 |
| |
| 8) PROVIDE PROPER SIGNAGE INDICATING THE TYPE AND |
| LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC |
| 700.8 |
| 8A) PERMANENT PLAQUES OR DIRECTORIES SHALL BE INSTALLED |
| AT EACH SERVICE DISCONNECT |
| DENOTING ALL OTHER SERVICE LOCATION. NEC 230.2(E) |
| |
| 9) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16. |
| |
| 10) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| |
| 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 12) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL |
| POWER AND LIGHTING SYSTEMS. (MANDATORY) FBC SECTION 505 |
| 12A) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| |
| 13) NEC 230.9(C) GROUND FAULT PERFORMANCE TESTING. THE |
| GROUND-FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE |
| TESTED WHEN FIRST INSTALLED ON SITE. |
| |
| 14) PROVIDE A LAYOUT OF ALL ELECTRICAL ROOMS INDICATING |
| COMPLIANCE WITH NEC 110.26 FOR ABOUT ALL ELECTRICAL |
| EQUIPMENT. |
| |
| 15) E605 INDICATE THE LOAD CALCULATION FOR PANEL |
| NLGP1A. THE LOAD CALCULATION IS CUT OFF BY PANEL |
| NLGP1B. |
| |
| 16) CORRECT THE NAMING CONVENTION FOR THE ELECTRICAL |
| SHEETS. THE ELECTRICAL SHEETS ARE NOT ALL TOGETHER. |
| |
| 17) CORRECT THE NAME OF PANEL RDPB. ON PAGE E005 IT IS |
| NAMED RDPB BUT ON PG E001 IT IS NAMED RMDPB |
| |
| 18) E200A |
| PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN |
| UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE |
| FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO |
| REFERENCE FOR CLARIFICATION. |
| 18A) POWER PLAN NOTE 6. CALLS FOR A 20AMP CIRCUIT FOR |
| DRYER BOOSTER FANS. |
| BOOSTER FANS ARE NOT APPROVED FOR USE IN WPB PER THE |
| WPB FIRE DEPT LOCAL CODES AND AMENDMENTS. |
| |
| 19) E200B |
| PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN |
| UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE |
| FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO |
| REFERENCE FOR CLARIFICATION. |
| |
| 20) E200C |
| CORRECT PLAN NOTE 1 TO PROVIDE AFCI CIRCUIT BREAKER ON |
| ALL CIRCUITS WITHIN SLEEPING AREA TO READ ?ALL |
| 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH |
| CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT |
| FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE |
| PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, |
| COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF |
| THE BRANCH CIRCUIT.? PER NEC 210.12(B) |
| 20A) ANYWHERE RECEPTACLES ARE INSTALLED WITHIN 6 FT OF |
| THE SINK SHALL BE GFI PROTECTED. NEC 210.8(B)(5) |
| |
| 21) E202CPROVIDE A GFI WITHIN SIGHT OF MECHANICAL |
| EQUIPMENT. NEC 210.63 SEE ALSO 210.8(A)(3). |
| |
| 22) E301A |
| INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| FBC 505.2 |
| |
| 23) E301B |
| PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS. |
| INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| FBC 505.2 |
| |
| 24) E310B |
| PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS. |
| INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| FBC 505.2 |
| |
| 25) E601 |
| REVISE PANEL SCHEDULE AND LOAD CALCULATION. PANEL C2 |
| INDICATES A 27KVA DEMAND LOAD AT ONLY 75AMPS. THIS |
| SHOULD BE CLOSER TO 130AMPS. |
| 23A) APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS |
| REQUIRED. |
| |
| 26) E602 |
| APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS REQUIRED |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING, |
| LIGHTNING PROTECTION, GENERATORS. HOOD EXHAUST, FIRE |
| ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, |
| AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |