Plan Review Notes For Permit 14120908 |
Permit Number |
14120908 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-08-01 04:39:25 | 1) SUBMIT TOTAL BTU LOAD ON GAS SYSTEM, THE TOTAL | | DISTANCE FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET, TYPE OF PIPE, TYPE OF GAS, PSI OF THE SYSTEM, | | MANUF. SPECS FOR ALL NEW EQUIPMENT. WPB AMEND. TO FBC | | SEC. 103.3.5.1.5. | | 2)SUBMIT ROOF DRAINAGE CALCULATIONS.CALCULATIONS SHALL | | INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS | | RAINWATER TO THE ROOF AND SHALL ALSO INCLUDE ANY AREAS | | OF THE SLOPED ROOFS THAT DIVERT RAINWATER ONTO THE FLAT | | ROOFS.2010 FBC-PLUMBING SEC. 1106..1, 1106.4, 1106.7.. | | 3)TWO COPIES OF "KES" DRAWINGS SHALL BE SUBMITTED FOR | | REVIEW. WPB AMNED. TO FBC SEC. 107.2.1. | | 4) SIZING OF SANITARY AND INDIRECT WASTE PIPING SHALL | | COMPLY W/CHAPT.7 & CHAPT. 8 OF 2010 FBC-PLUMBING. | | 5) PER THE LIFE-SAFETY PLAN (G101) THE TOTAL ASSEMBLY | | OCCUPANT LOAD IS 160 PERSONS. IT IS DESIGNATED AS A-2. | | TABLE 403.1 REQUIRES 2 WATER CLOSETS FOR MALES (1 PER | | 75) AND TWO FOR FEMALES (1 PER 75). THE PLAN SHOWS ONE | | EACH. REVISE THE FIXTURE COUNT AND SHOW THE ADDITIONAL | | FIXTURES IN THE RESTROOMS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|