Plan Review Notes
Plan Review Notes For Permit 14120908
Permit Number 14120908
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-27 15:10:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC
 SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS.
 MODEL D200E PROPOSED. PLEASE SEE FBC 715.4.2 ALLOWS UL
 10B AS A TESTED STANDARD. SEE SPEC SHEETS PROVIDED;
 THIS DOOR APPEARS TO BE LIMITED TO 20 MINUTES , 45
 MINUTES REQUIRED.
  
 THIS INFORMATION MAY BE SENT VIA EMAIL.
  
 ** IMPACT FEE PAYMENT REQUIRED (SEE IMPACT FEE REVIEW)
 **SEE THRESHOLD REVIEW - AGREEMENT AND PLAN REQUIRED TO
 BE REVISED PRIOR TO PERMIT ISSUANCE
  
 PROVISO ITEMS:
  
 1. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT
 COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE
 REQUIRED PRIOR TO CERTIFICATE OF COMPLETION.
  
 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF
 WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 3. SHEET A101 SHOWS A PROPOSED FUTURE 2 HOUR FIRE DOOR.
 SEE FBC TABLE 715.4, A 3 HOUR FIRE DOOR IS REQUIRED FOR
 A 3 HOUR FIRE WALL.
  
 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE
 PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT
 APPLICATIONS, PLANS AND REVIEWS.
  
 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT
 REVIEWED.
  
 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL
 ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD
 INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED
 TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE
 REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE
 APPROVED THROUGH PLAN REVIEW PRIOR TO INSTALLATION.
  
 8. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED
 FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS,
 STRUCTURAL FRAME, FBC TABLE 601. THE ROOF WAS SPECIFIED
 BUT NOT THE OTHER STRUCTURAL ELEMENTS.
  
 9. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A
 CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC
 ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF
 APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE
 EXIT HARDWARE, FBC 1008.1.10. SPEC SHEETS WERE
 SUBMITTED BUT CONTAINED INFORMATION NOT CODE RELATED
 (FINISHES, HINGES, KICK PLATES, ETC.). SPEC BOOKS
 CANNOT BE USED IN LIEU OF PLANS TO SHOW CODE COMPLIANCE
 DUE TO THE LARGE AMOUNT OF INFORMATION NOT RELEVANT TO
 CODE COMPLIANCE, FBC 107.
  
 10. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND
 FLOORS.
  
 11. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH
 THIS SECTION.
  
 12. TESTED ASSEMBLIES OR CALCULATED FIRE RESISTANCE
 DETAILS REQUIRED FOR ALL ELEMENTS REQUIRED TO BE RATED
 PER FBC TABLE 601. SUBMIT DETAILS PRIOR TO
 INSTALLATION.
  