Date |
Text |
2015-04-12 14:37:40 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| COMMENTS FROM FIRST BUILDING PLAN REVIEW BY JIM WITMER |
| WHICH ARE STILL APPLICABLE: |
| |
| 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT: |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND |
| THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES |
| BETWEEN. |
| 1.2) SURVEY WITH FLOOD ZONE DESIGNATION |
| 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR |
| THIS BUILDING (DUNKELBERGER REPORT DATED 12/31/14 |
| REFERENCE ON SHEET S4.1; PROVIDE ALL GEOTECHNICAL |
| REPORTS APPLICABLE TO THIS PROJECT). |
| 1.4) ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR |
| BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS. |
| 1.5) OK |
| 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES (INCLUDE |
| NUMBER OF STORIES FOR EXISTING BUILDING) |
| |
| 2. THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE |
| 1/10/2015 01:05 PM BY JIM WITMER. |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 2A) OK; SHEET S 3.4, THRESHOLD INSPECTION NOTES ARE |
| INCLUDED IN THIS SUBMITTAL. |
| KEN CONRAD, CHIEF BUILDING INSPECTOR HAS BEEN ADVISED |
| THAT THE PLAN IS AVAILABLE FOR HIS REVIEW. |
| |
| 2B) THRESHOLD INSPECTOR REQUIRED; SEE PREVIOUS LIST FOR |
| SPECIFICS. |
| |
| 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| MINIMUM BUILDING CODES AND FIRE SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 2ND REVIEW, I WAS UNABLE TO LOCATE THIS STATEMENT. SEE |
| OTHER COMMENTS; THIS STATEMENT IS TYPICALLY |
| INCORPORATED INTO EVERY PAGE. |
| |
| 2D) SPECIAL INSPECTOR RESUME REQUIRED; SEE PREVIOUS |
| LIST FOR SPECIFICS. |
| |
| 2E) CONTRACTOR RESUME REQUIRED; SEE PREVIOUS LIST FOR |
| SPECIFICS. |
| |
| 2F) INFORMATIONAL ONLY; NOTE THIS IS A DIGITAL PLAN, |
| AFTER PERMIT ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL |
| YOU, THE APPROVED AND BATCH STAMPED PLANS SO YOU MAY |
| PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| OTHER FOR THE MEP INSPECTORS. |
| |
| 2G) INFORMATIONAL ONLY; PLEASE CALL THE CITY OF WEST |
| PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| JOBSITE INSPECTIONS. |
| |
| 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL |
| COMPLY WITH : |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF |
| CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO |
| THE PLAN. |
| |
| 4. 2010 FBC B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW |
| PROCESS, BUT MUST BE DONE PRIOR TO PERMIT ISSUANCE. |
| |
| NEW COMMENTS (NEW SHEETS SUBMITTED; SCOPE EXPANDED FROM |
| FOUNDATION ONLY TO ADDITION TO EXISTING BUILDING): |
| 6. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D)?ALL PLANS |
| FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND |
| SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A |
| STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR |
| ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS |
| COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND |
| THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY |
| THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND |
| CHAPTER 633. |
| |
| PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS |
| TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF |
| DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH |
| SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY, |
| PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH |
| THE APPROPRIATE BOARD. |
| |
| 7. THIS DINING ROOM ADDITION TO AN EXISTING BUILDING IS |
| TO BE CONNECTED TO A NEW BUILDING. SEE PREVIOUS LIST |
| AND REFERENCE TO FBC 3104.5. IT IS NOT CLEAR WHETHER |
| THE NEW BUILDING WILL BE CONSIDERED AN ADDITION TO THE |
| EXISTING BUILDING, ON THE SAME PARCEL, CONNECTED BY A |
| WALKWAY, OR IF WILL BE TREATED AS A NEW BUILDING, |
| SEPARATE PARCEL, OR NEW BUILDING, SAME PARCEL (WITH |
| UNITY OF TITLE, SEE OTHER COMMENTS). |
| |
| 8. IT APPEARS THAT ALL PARTIES (ARCHITECT, ENGINEER, |
| CONTRACTOR, OWNER) ARE IN AGREEMENT THAT THIS PROJECT |
| WILL BE TREATED AS A THRESHOLD JOB. IF ANY OF THE |
| PARTIES DISAGREE WITH THIS CLASSIFICATION, PLEASE |
| CONTACT ME. |
| |
| CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES |
| FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE |
| I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF |
| THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS |
| ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE |
| PARTIES, PLEASE CONTACT ME TO DISCUSS. |
| |
| 9. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN |
| ON THE PLAN (PERKINS EASTMAN, FS95000000559, |
| PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS |
| (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763, |
| NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE |
| NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT |
| POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING |
| RESPONSIBILITY FOR THE DESIGN. |
| SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED |
| AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION |
| DOCUMENTS. |
| |
| HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES. |
| HTML |
| |
| 10. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT |
| SHOWN ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES |
| REMAIN SEPARATE PARCELS, HAVE THEY ALREADY BEEN |
| COMBINED WITH A UNITY OF TITLE, OR WILL THEY BE |
| COMBINED WITH A UNITY OF TITLE? IF THEY ARE TO REMAIN |
| SEPARATE PARCELS, SEE FBC TABLE 602, TABLE 705.8 AND |
| REVISE PLAN TO SHOW COMPLIANCE (DISTANCE TO PROPERTY |
| LINE, RATED WALLS AS APPLICABLE, PROTECTED OPENINGS IF |
| PERMITTED). |
| |
| IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING |
| DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING |
| KNOWN AS TRADITIONS II PHASE ONE. |
| |
| HTTP://WWW.PBCGOV.COM/PAPA/ASPS/PROPERTYDETAIL/PROPERTY |
| DETAIL.ASPX?PARCEL=74424312260030000&SRCHTYPE=ADV&OWNER |
| =&STREETNO=4850&PREFIX=&STREETNAME=LORING&SUFFIX=&POSTD |
| IR=&UNITNO=&SRCHPARCEL=&RANGE=&TWP=&SECTION=&BOOK=&PAGE |
| =&LEGAL=&SUBDIV=&MUNI=&ZIP=&USETYPE=&CONDO= |
| |
| DISTANCE OF PROPOSED DINING ROOM ADDITION TO THE |
| PROPERTY LINE IS UNCLEAR. |
| |
| IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY |
| OF TITLE AND WISH TO DO SO, THE APPLICATION IS |
| AVAILABLE ONLINE: |
| |
| HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- |
| 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF |
| |
| 11. AS PERMITS 14120908 AND 14120909 WERE INITIALLY |
| FOUNDATION PERMITS, PLEASE PROVIDE NEW APPLICATIONS |
| WITH THE NEW SCOPE OF WORK AND VALUE, SIGNED BY THE |
| QUALIFIER AND THE OWNER. ALSO PLEASE NOTE THAT IT |
| APPEARS THAT THE NEW BUILDING (TRADITIONS II PHASE ONE) |
| IS LOCATED PRIMARILY ON A PARCEL WITH AN ADDRESS OF |
| 4850 LORING DRIVE, LOCATED ON TRACT C, PARCEL ID |
| 74-42-43-12-26-003-0000. |
| |
| I WAS UNABLE TO LOCATE A RECORDED UNITY OF TITLE WHICH |
| COMBINES THE TWO SEPARATE PARCELS. IF AVAILABLE, PLEASE |
| PROVIDE. SEE OTHER COMMENT REGARDING DISTANCE TO |
| PROPERTY LINE. |
| |
| 12. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT |
| VIA EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| 78-123, 78-126. |
| |
| THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| DOCUMENT THE PERMIT FILE. |
| |
| 13. ADVISORY ONLY, FS 553.79(7)(C)ALL SHORING AND |
| RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED |
| TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH |
| LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE |
| BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH |
| LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS |
| BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A |
| NOTE BE INCORPORATED INTO THE PLAN. |
| |
| 14. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| FBC 1609 (SUBMITTAL, NO FEE). |
| |
| 15. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP |
| HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND |
| ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF |
| ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE |
| PLAN REVIEW PROCESS FOR THE ADDITION. |
| |
| 16. ADVISORY ONLY, NO ACTION REQUIRED AT THIS TIME. |
| PLEASE BE ADVISED THAT LANDSCAPE SHEETS HAVE BEEN |
| VOIDED BY ZONING AND HAVE NOT BEEN REVIEWED. A SEPARATE |
| LANDSCAPE PERMIT AND REVIEW WILL BE REQUIRED. |
| |
| 17. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE |
| PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT |
| APPLICATIONS, PLANS AND REVIEWS. |
| |
| 18. FBC EXISTING BUILDING 101.5, ADDITION AND |
| ALTERATION TO COMPLY WITH ONE OF THE COMPLIANCE METHODS |
| LISTED IN SECTIONS 101.5.1 THROUGH 101.5.3 AS SELECTED |
| BY APPLICANT. REVISE PLAN TO INDICATE METHOD OF |
| COMPLIANCE SELECTED. AS THIS IS BOTH AN ADDITION AND AN |
| ALTERATION, WITH FUTURE ADDITIONS PLANNED, INFORMATION |
| REGARDING THE EXISTING BUILDING (SUCH AS THE CODE IT |
| WAS PERMITTED UNDER) WOULD HELP EXPEDITE PLAN REVIEW. |
| FOR INSTANCE, THE COMMENT REGARDING THE FIRE RESISTANCE |
| RATING FOR THE FIRE PUMP ROOM; 2 HOURS REQUIRED BY |
| TABLE 508.2.5. IN ORDER TO DETERMINE WHETHER THIS WAS |
| IN COMPLIANCE WHEN THE BUILDING WAS CONSTRUCTED AND CAN |
| REMAIN AS IS, CODE IN EFFECT FOR CONSTRUCTION OF |
| EXISTING BUILDING AND METHOD OF ALTERATION IS REQUIRED. |
| THIS IS ONE EXAMPLE OF ISSUES WHICH MAY ARISE, BOTH IN |
| PLAN REVIEW AND IN THE FIELD, WHICH WOULD BE ADDRESSED |
| UNDER THE APPLICABLE PORTIONS OF THE EXISTING BUILDING |
| CODE. |
| |
| 19. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS |
| REQUIRED. |
| |
| 20. G001 PROVIDES A SUMMARY OF BUILDING CODE |
| REQUIREMENTS BUT I WAS UNABLE TO LOCATE INFORMATION |
| REGARDING THE EXISTING BUILDING. PLEASE PROVIDE |
| BUILDING HEIGHT, AREA, TOTAL OCCUPANT LOAD (SEE COMMENT |
| REGARDING RISK CATEGORY). |
| |
| IT APPEARS THAT THIS ADDITION IS AN ADDITION TO A HIGH |
| RISE AND IS BEING TREATED AS SUCH IN PLAN REVIEW. |
| |
| 21. G101, PATH OF TRAVEL IS SHOWN ACROSS THE DIAGONAL |
| OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN ALONG |
| THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS FURNITURE |
| WILL BE PLACED IN THE CENTER OF THE ROOM, THE PATH |
| SHOULD BE MEASURED ALONG THE ROOM PERIMETER. |
| |
| 22. SHEET G101, 2 HOUR SEPARATION REQUIRED FOR THE FIRE |
| PUMP ROOM, FBC 2010 508.2.5. SEE OTHER COMMENT |
| REGARDING EXISTING BUILDING CODE; IT IS NOT CLEAR IF |
| THIS SHOULD BE ADDRESSED OR WAS COMPLIANT AT TIME OF |
| PERMITTING. |
| |
| 23. G101, 200 SF PER OCCUPANT IN THE EXTERIOR COURTYARD |
| (AREA 110) DOES NOT APPEAR TO BE A REASONABLE OCCUPANT |
| LOAD, ESPECIALLY AS ADJACENT TO THIS AREA ON ALL SIDES |
| IS ASSEMBLY. IT APPEARS THAT THIS AREA SHOULD ALSO BE |
| CLASSIFIED AS ASSEMBLY, 15 SF PER PERSON. PLEASE REVISE |
| OCCUPANCY CLASSIFICATION AND OCCUPANT LOAD. IT APPEARS |
| HIGHLY LIKELY THAT THIS AREA MAY BE USED AS OUTDOOR |
| DINING AT SOME POINT. |
| |
| 24. G101, FOR ASSEMBLY AREAS, OCCUPANT LOAD CAN BE |
| BASED ON NET SF AREA, SEE TABLE 1004; GROSS SF WAS |
| STATED IN SOME PLACES AND NET WAS STATED IN OTHER |
| PLACES. IT IS ACCEPTABLE TO EXCEED THE MINIMUM |
| REQUIREMENTS OF THE CODE (USE GROSS RATHER THAN NET), |
| BUT THIS METHOD SHOULD REMAIN CONSISTENT. |
| |
| 25. EXIT STRATEGY NOT CLEAR. EX VERANDA IS LABELED AS |
| R2, BUT APPEARS TO NOW PRIMARILY SERVE THE ASSEMBLY |
| AREA. IT APPEARS THAT THE R2 CORRIDOR EXITS THROUGH |
| DOORS 101 AND 101B. IT APPEARS THAT THE EXISTING A2 WAS |
| SEPARATED FROM THE EXITING AREA (LOUNGE AND VERANDA) |
| ALTHOUGH THE SEPARATION IS NOT SHOWN AS CONTINUOUS ON |
| THIS PLAN. |
| |
| THE NEW ADDITION IS NOW OPEN TO THE EX VERANDA AND USES |
| THE SAME EXIT AS THE R2 OCCUPANCY. ONCE A GIVEN LEVEL |
| OF EXIT PROTECTION IS ACHIEVED, SUCH LEVEL OF PROECTION |
| SHALL NOT BE REDUCED UNTIL ARRIVAL AT THE EXIT |
| DISCHARGE. IN THE MEETING, CLASSIFICATION OF THIS AREA |
| WAS DISCUSSED. FEEL FREE TO CONTACT ME FOR FURTHER |
| DISCUSSION. PERHAPS CONSIDER A VESTIBULE, 1027.1 TO |
| RESOLVE THE ISSUE OF A2 EXITING THROUGH R2 OR R2 |
| EXITING THROUGH A2. |
| |
| 26. G101, REVISE PLAN TO SHOW THE EXIT DISCHARGE. THE |
| PATH FROM THE EXIT TO THE PUBLIC WAY OR OTHER COMPLIANT |
| AREA SHOULD BE SHOWN ON EITHER THIS PLAN OR ANOTHER |
| SHEET, FBC 1027. |
| |
| 27. G101, DOOR 102 IS SHOWN AS AN EXIT, BUT A101 SHOWS |
| THIS DOOR ENTERING ANOTHER (FUTURE) BUILDING, PLEASE |
| CLARIFY, FBC 3302.1. ALTHOUGH THIS MAY BE ADDRESSED ON |
| ANOTHER PLAN CURRENTLY IN THE PLAN REVIEW PROCESS, EACH |
| PERMIT IS TO DEMONSTRATE CODE COMPLIANCE WITHOUT |
| RELYING ON ANOTHER PLAN (PARTICULARLY ONE WHICH IS NOT |
| YET ISSUED OR REVIEWED). |
| |
| 28. UL ASSEMBLIES ARE SPECIFIED ON THE PLANS IN VARIOUS |
| PLACES (EXAMPLE A301). FBC 107, EITHER INCORPORATE THE |
| UL DETAILS INTO THE PLAN OR, PRIOR TO INSTALLATION, A |
| SUBMITTAL WILL BE REQUIRED. THE SUBMITTAL SHOULD |
| INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED |
| TO BE MARKED. THE SUBMITTAL IS REQUIRED TO BE REVIEWED |
| BY DOR. IF THE UL ASSEMBLIES ARE NOT INCORPORATED INTO |
| THE PLAN WITH OPTIONS INDICATED, THE SUBMITTAL IS |
| REQUIRED TO BE APPROVED THROUGH PLAN REVIEW PRIOR TO |
| INSTALLATION. |
| |
| IF THE ASSEMBLIES WITH APPLICABLE OPTIONS ARE NOT |
| INCORPORATED INTO THE PLAN, FUTURE SUBMISSION AS A |
| SUBMITTAL WILL BE A PROVISO ITEM. |
| |
| 29. SHEET A301 AND OTHER PAGES AS APPLICABLE, SPECIFY |
| FIRE RESISTANCE RATING ON THE PLAN SO DESIGN INTENT IS |
| CLEAR, FBC TABLE 601. IF A REDUCTION IS TAKEN DUE TO AN |
| EXCEPTION, CITE THE APPLICABLE EXCEPTION (SUCH AS FBC |
| 2010 BUILDING 402.1.1(2)) AND PROVIDE ENOUGH |
| INFORMATION REGARDING THE EXISTING BUILDING TO |
| DEMONSTRATE COMPLIANT APPLICABILITY. |
| |
| 30. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED |
| FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS, |
| STRUCTURAL FRAME, FBC TABLE 601. |
| |
| 31. SHEET S3.1, WIND LOADS, 170 MPH, RISK CATEGORY II, |
| EXPOSURE C, ENCLOSED IS STATED AS WIND DESIGN CRITIERA |
| FBC 1609. SEE SHEET G000, THE MAP FOR RISK CATEGORY III |
| AND IV BUILDINGS IS SHOWN (FBC FIGURE 1609B). PLEASE |
| CORRELATE. |
| |
| IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL |
| BUILDING OCCUPANT LOAD. |
| |
| 32. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE |
| (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY |
| AS APPLICABLE. |
| |
| 33. S3.1, STANDARDS CANNOT BE REFERENCED AS "LATEST |
| EDITION," SEE FBC 2010 CHAPTER 35. DESIGN IS TO COMPLY |
| WITH THE STANDARD VERSION REFERENCED IN CHAPTER 35, |
| REVISE ALL AS APPLICABLE. |
| |
| IF ENGINEER HAS SPECIFIC CONDITIONS WHERE THE EDITION |
| USED FOR DESIGN CONFLICTS WITH THE EDITION SPECIFIED IN |
| FBC CHAPTER 35, THIS CAN BE PROPOSED UNDER FBC 104.11, |
| ALTERNATIVE MATERIALS, DESIGN AND METHODS OF |
| CONSTRUCTION. IF APPLICABLE, THIS SHOULD BE DONE PRIOR |
| TO RESUBMITTAL FOR CONSIDERATION BY THE BUILDING |
| OFFICIAL. |
| |
| 34. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES, |
| PLYWOOD SHEATHING SHOWN. THIS BUILDING IS REQUIRED TO |
| BE NON COMBUSTIBLE, FBC 602.1. REVISE TO INCLUDE |
| REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND |
| OTHER SHEETS), FBC 603.1.1.1.3. |
| |
| 35. S3.2, SPECIFY FLOOR LOADS FOR 2ND FLOOR MECHANICAL |
| ROOM, FBC 1606, 1607. |
| |
| 36. A101, DETAILS 7 AND 11, REVISE TO SHOW CENTER LINE |
| AND DISTANCE REQUIRED FOR GRAB BAR, SEE FBC 2010 |
| ACCESSIBILITY FIGURE 604.5.2. |
| |
| 37. A101, DETAIL 3, DOOR APPEARS TO ENCROACH CLEAR |
| FLOOR SPACE REQUIRED FOR LAVATORY IN ROOM 111, FBC 2010 |
| ACCESSIBILITY 603.2.3. |
| |
| 38. A101, DETAIL 3, SHOW 18IN CLEARANCE FOR DOOR 112, |
| PULL SIDE, FBC ACCESSIBILITY FIGURE 404.2.4.1(A). |
| |
| 39. A101, DETAIL 3, PROVIDE A DETAIL FOR THE DRINKING |
| FOUNTAIN (INCLUDING CLEAR FLOOR SPACE), FBC 2010 |
| ACCESSIBILITY 211. |
| |
| 40. DETAIL A502 AND 1 A503, OTHER LOCATIONS, ROOF |
| DETAIL IS LACKING THE 90LB OR OTHER CAP SHEET FOR TILE |
| WHICH IS A REQUIREMENT IN THE CONCRETE ROOF TILE |
| PRODUCT APPROVAL, FBC 1609. |
| |
| 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC |
| SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS. |
| ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR |
| ACCESS FOR MAINTENANCE, FBC 107. |
| |
| 42. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A |
| CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC |
| ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF |
| APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE |
| EXIT HARDWARE, FBC 1008.1.10. |
| |
| 43. FBC 1503.4, PROVIDE ROOF DRAINAGE CALUCLATIONS. |
| |
| 44. DETAIL 4 SHEET A503, OVERFLOW SCUPPER APPEARS TO BE |
| AT ROOF LEVEL. SEE FBC 1503.4.2.1, OVERFLOW SCUPPERS TO |
| BE NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE |
| THE ROOF COVERING. |
| |
| 45. SHEET G101, FIRST FLOOR LIFE SAFETY PLAN, DOES NOT |
| INCLUDE EXITING FOR THE OCCUPANTS OF THE COURTYARD, FBC |
| 1004.8. REVISE PLAN TO INCLUDE TRAVEL DISTANCE. IF |
| OCCUPANT LOAD IS OVER 50, DOOR 109A TO SWING IN THE |
| DIRECTION OF TRAVEL, BUT ALSO CANNOT BLOCK THE |
| CORRIDOR, FBC 1008.1.2, 1005.2. |
| |
| 46. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND |
| FLOORS. |
| |
| 47. SEE FIRE COMMENTS REGARDING EXIT SIGNS, FBC 1011.1. |
| |
| 48. REVISE PLAN TO SHOW LOCATION AND TYPE OF FIRE ALARM |
| DEVICES, FBC 403.4.2, FBC ACCESSIBILITY 702. |
| |
| 49. NO INFORMATION PROVIDED REGARDING SOME OF THE OTHER |
| HIGH RISE REQUIREMENTS (FBC 403). SOME MAY BE EXISTING |
| IN ANOTHER PORTION OF THE BUILDING NOT SHOWN, SOME MAY |
| NOT BE REQUIRED DUE TO CODE IN EFFECT WHEN BUILDING WAS |
| PERMITTED, BUT IN ORDER TO PROVIDE A COMPLETE REVIEW, |
| DESIGNER TO ELECT METHOD OF ALTERATION AND STATE THE |
| CODE UNDER WHICH THE EXISTING BUILDING WAS CONSTRUCTED. |
| |
| 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH |
| THIS SECTION. |
| |
| |
| |