Plan Review Notes
Plan Review Notes For Permit 14120908
Permit Number 14120908
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-12 14:37:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM FIRST BUILDING PLAN REVIEW BY JIM WITMER
 WHICH ARE STILL APPLICABLE:
  
 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND
 THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES
 BETWEEN.
 1.2) SURVEY WITH FLOOD ZONE DESIGNATION
 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR
 THIS BUILDING (DUNKELBERGER REPORT DATED 12/31/14
 REFERENCE ON SHEET S4.1; PROVIDE ALL GEOTECHNICAL
 REPORTS APPLICABLE TO THIS PROJECT).
 1.4) ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR
 BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS.
 1.5) OK
 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES (INCLUDE
 NUMBER OF STORIES FOR EXISTING BUILDING)
  
 2. THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE
 1/10/2015 01:05 PM BY JIM WITMER.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) OK; SHEET S 3.4, THRESHOLD INSPECTION NOTES ARE
 INCLUDED IN THIS SUBMITTAL.
 KEN CONRAD, CHIEF BUILDING INSPECTOR HAS BEEN ADVISED
 THAT THE PLAN IS AVAILABLE FOR HIS REVIEW.
  
 2B) THRESHOLD INSPECTOR REQUIRED; SEE PREVIOUS LIST FOR
 SPECIFICS.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND FIRE SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND 633 FLORIDA STATUTE.
  
 2ND REVIEW, I WAS UNABLE TO LOCATE THIS STATEMENT. SEE
 OTHER COMMENTS; THIS STATEMENT IS TYPICALLY
 INCORPORATED INTO EVERY PAGE.
  
 2D) SPECIAL INSPECTOR RESUME REQUIRED; SEE PREVIOUS
 LIST FOR SPECIFICS.
  
 2E) CONTRACTOR RESUME REQUIRED; SEE PREVIOUS LIST FOR
 SPECIFICS.
  
 2F) INFORMATIONAL ONLY; NOTE THIS IS A DIGITAL PLAN,
 AFTER PERMIT ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL
 YOU, THE APPROVED AND BATCH STAMPED PLANS SO YOU MAY
 PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS.
  
 2G) INFORMATIONAL ONLY; PLEASE CALL THE CITY OF WEST
 PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL
 COMPLY WITH :
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT GRANTED BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO
 THE PLAN.
  
 4. 2010 FBC B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW
 PROCESS, BUT MUST BE DONE PRIOR TO PERMIT ISSUANCE.
  
 NEW COMMENTS (NEW SHEETS SUBMITTED; SCOPE EXPANDED FROM
 FOUNDATION ONLY TO ADDITION TO EXISTING BUILDING):
 6. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D)?ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR
 ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND
 CHAPTER 633.
  
 PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS
 TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF
 DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH
 SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY,
 PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH
 THE APPROPRIATE BOARD.
  
 7. THIS DINING ROOM ADDITION TO AN EXISTING BUILDING IS
 TO BE CONNECTED TO A NEW BUILDING. SEE PREVIOUS LIST
 AND REFERENCE TO FBC 3104.5. IT IS NOT CLEAR WHETHER
 THE NEW BUILDING WILL BE CONSIDERED AN ADDITION TO THE
 EXISTING BUILDING, ON THE SAME PARCEL, CONNECTED BY A
 WALKWAY, OR IF WILL BE TREATED AS A NEW BUILDING,
 SEPARATE PARCEL, OR NEW BUILDING, SAME PARCEL (WITH
 UNITY OF TITLE, SEE OTHER COMMENTS).
  
 8. IT APPEARS THAT ALL PARTIES (ARCHITECT, ENGINEER,
 CONTRACTOR, OWNER) ARE IN AGREEMENT THAT THIS PROJECT
 WILL BE TREATED AS A THRESHOLD JOB. IF ANY OF THE
 PARTIES DISAGREE WITH THIS CLASSIFICATION, PLEASE
 CONTACT ME.
  
 CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES
 FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE
 I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF
 THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS
 ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE
 PARTIES, PLEASE CONTACT ME TO DISCUSS.
  
 9. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN
 ON THE PLAN (PERKINS EASTMAN, FS95000000559,
 PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS
 (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763,
 NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE
 NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT
 POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING
 RESPONSIBILITY FOR THE DESIGN.
 SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED
 AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION
 DOCUMENTS.
  
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES.
 HTML
  
 10. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT
 SHOWN ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES
 REMAIN SEPARATE PARCELS, HAVE THEY ALREADY BEEN
 COMBINED WITH A UNITY OF TITLE, OR WILL THEY BE
 COMBINED WITH A UNITY OF TITLE? IF THEY ARE TO REMAIN
 SEPARATE PARCELS, SEE FBC TABLE 602, TABLE 705.8 AND
 REVISE PLAN TO SHOW COMPLIANCE (DISTANCE TO PROPERTY
 LINE, RATED WALLS AS APPLICABLE, PROTECTED OPENINGS IF
 PERMITTED).
  
 IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING
 DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING
 KNOWN AS TRADITIONS II PHASE ONE.
  
 HTTP://WWW.PBCGOV.COM/PAPA/ASPS/PROPERTYDETAIL/PROPERTY
 DETAIL.ASPX?PARCEL=74424312260030000&SRCHTYPE=ADV&OWNER
 =&STREETNO=4850&PREFIX=&STREETNAME=LORING&SUFFIX=&POSTD
 IR=&UNITNO=&SRCHPARCEL=&RANGE=&TWP=&SECTION=&BOOK=&PAGE
 =&LEGAL=&SUBDIV=&MUNI=&ZIP=&USETYPE=&CONDO=
  
 DISTANCE OF PROPOSED DINING ROOM ADDITION TO THE
 PROPERTY LINE IS UNCLEAR.
  
 IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY
 OF TITLE AND WISH TO DO SO, THE APPLICATION IS
 AVAILABLE ONLINE:
  
 HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011-
 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF
  
 11. AS PERMITS 14120908 AND 14120909 WERE INITIALLY
 FOUNDATION PERMITS, PLEASE PROVIDE NEW APPLICATIONS
 WITH THE NEW SCOPE OF WORK AND VALUE, SIGNED BY THE
 QUALIFIER AND THE OWNER. ALSO PLEASE NOTE THAT IT
 APPEARS THAT THE NEW BUILDING (TRADITIONS II PHASE ONE)
 IS LOCATED PRIMARILY ON A PARCEL WITH AN ADDRESS OF
 4850 LORING DRIVE, LOCATED ON TRACT C, PARCEL ID
 74-42-43-12-26-003-0000.
  
 I WAS UNABLE TO LOCATE A RECORDED UNITY OF TITLE WHICH
 COMBINES THE TWO SEPARATE PARCELS. IF AVAILABLE, PLEASE
 PROVIDE. SEE OTHER COMMENT REGARDING DISTANCE TO
 PROPERTY LINE.
  
 12. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT
 VIA EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES
 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 13. ADVISORY ONLY, FS 553.79(7)(C)ALL SHORING AND
 RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED
 TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH
 LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE
 BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH
 LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS
 BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A
 NOTE BE INCORPORATED INTO THE PLAN.
  
 14. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 15. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP
 HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND
 ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF
 ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE
 PLAN REVIEW PROCESS FOR THE ADDITION.
  
 16. ADVISORY ONLY, NO ACTION REQUIRED AT THIS TIME.
 PLEASE BE ADVISED THAT LANDSCAPE SHEETS HAVE BEEN
 VOIDED BY ZONING AND HAVE NOT BEEN REVIEWED. A SEPARATE
 LANDSCAPE PERMIT AND REVIEW WILL BE REQUIRED.
  
 17. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE
 PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT
 APPLICATIONS, PLANS AND REVIEWS.
  
 18. FBC EXISTING BUILDING 101.5, ADDITION AND
 ALTERATION TO COMPLY WITH ONE OF THE COMPLIANCE METHODS
 LISTED IN SECTIONS 101.5.1 THROUGH 101.5.3 AS SELECTED
 BY APPLICANT. REVISE PLAN TO INDICATE METHOD OF
 COMPLIANCE SELECTED. AS THIS IS BOTH AN ADDITION AND AN
 ALTERATION, WITH FUTURE ADDITIONS PLANNED, INFORMATION
 REGARDING THE EXISTING BUILDING (SUCH AS THE CODE IT
 WAS PERMITTED UNDER) WOULD HELP EXPEDITE PLAN REVIEW.
 FOR INSTANCE, THE COMMENT REGARDING THE FIRE RESISTANCE
 RATING FOR THE FIRE PUMP ROOM; 2 HOURS REQUIRED BY
 TABLE 508.2.5. IN ORDER TO DETERMINE WHETHER THIS WAS
 IN COMPLIANCE WHEN THE BUILDING WAS CONSTRUCTED AND CAN
 REMAIN AS IS, CODE IN EFFECT FOR CONSTRUCTION OF
 EXISTING BUILDING AND METHOD OF ALTERATION IS REQUIRED.
 THIS IS ONE EXAMPLE OF ISSUES WHICH MAY ARISE, BOTH IN
 PLAN REVIEW AND IN THE FIELD, WHICH WOULD BE ADDRESSED
 UNDER THE APPLICABLE PORTIONS OF THE EXISTING BUILDING
 CODE.
  
 19. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS
 REQUIRED.
  
 20. G001 PROVIDES A SUMMARY OF BUILDING CODE
 REQUIREMENTS BUT I WAS UNABLE TO LOCATE INFORMATION
 REGARDING THE EXISTING BUILDING. PLEASE PROVIDE
 BUILDING HEIGHT, AREA, TOTAL OCCUPANT LOAD (SEE COMMENT
 REGARDING RISK CATEGORY).
  
 IT APPEARS THAT THIS ADDITION IS AN ADDITION TO A HIGH
 RISE AND IS BEING TREATED AS SUCH IN PLAN REVIEW.
  
 21. G101, PATH OF TRAVEL IS SHOWN ACROSS THE DIAGONAL
 OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN ALONG
 THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS FURNITURE
 WILL BE PLACED IN THE CENTER OF THE ROOM, THE PATH
 SHOULD BE MEASURED ALONG THE ROOM PERIMETER.
  
 22. SHEET G101, 2 HOUR SEPARATION REQUIRED FOR THE FIRE
 PUMP ROOM, FBC 2010 508.2.5. SEE OTHER COMMENT
 REGARDING EXISTING BUILDING CODE; IT IS NOT CLEAR IF
 THIS SHOULD BE ADDRESSED OR WAS COMPLIANT AT TIME OF
 PERMITTING.
  
 23. G101, 200 SF PER OCCUPANT IN THE EXTERIOR COURTYARD
 (AREA 110) DOES NOT APPEAR TO BE A REASONABLE OCCUPANT
 LOAD, ESPECIALLY AS ADJACENT TO THIS AREA ON ALL SIDES
 IS ASSEMBLY. IT APPEARS THAT THIS AREA SHOULD ALSO BE
 CLASSIFIED AS ASSEMBLY, 15 SF PER PERSON. PLEASE REVISE
 OCCUPANCY CLASSIFICATION AND OCCUPANT LOAD. IT APPEARS
 HIGHLY LIKELY THAT THIS AREA MAY BE USED AS OUTDOOR
 DINING AT SOME POINT.
  
 24. G101, FOR ASSEMBLY AREAS, OCCUPANT LOAD CAN BE
 BASED ON NET SF AREA, SEE TABLE 1004; GROSS SF WAS
 STATED IN SOME PLACES AND NET WAS STATED IN OTHER
 PLACES. IT IS ACCEPTABLE TO EXCEED THE MINIMUM
 REQUIREMENTS OF THE CODE (USE GROSS RATHER THAN NET),
 BUT THIS METHOD SHOULD REMAIN CONSISTENT.
  
 25. EXIT STRATEGY NOT CLEAR. EX VERANDA IS LABELED AS
 R2, BUT APPEARS TO NOW PRIMARILY SERVE THE ASSEMBLY
 AREA. IT APPEARS THAT THE R2 CORRIDOR EXITS THROUGH
 DOORS 101 AND 101B. IT APPEARS THAT THE EXISTING A2 WAS
 SEPARATED FROM THE EXITING AREA (LOUNGE AND VERANDA)
 ALTHOUGH THE SEPARATION IS NOT SHOWN AS CONTINUOUS ON
 THIS PLAN.
  
 THE NEW ADDITION IS NOW OPEN TO THE EX VERANDA AND USES
 THE SAME EXIT AS THE R2 OCCUPANCY. ONCE A GIVEN LEVEL
 OF EXIT PROTECTION IS ACHIEVED, SUCH LEVEL OF PROECTION
 SHALL NOT BE REDUCED UNTIL ARRIVAL AT THE EXIT
 DISCHARGE. IN THE MEETING, CLASSIFICATION OF THIS AREA
 WAS DISCUSSED. FEEL FREE TO CONTACT ME FOR FURTHER
 DISCUSSION. PERHAPS CONSIDER A VESTIBULE, 1027.1 TO
 RESOLVE THE ISSUE OF A2 EXITING THROUGH R2 OR R2
 EXITING THROUGH A2.
  
 26. G101, REVISE PLAN TO SHOW THE EXIT DISCHARGE. THE
 PATH FROM THE EXIT TO THE PUBLIC WAY OR OTHER COMPLIANT
 AREA SHOULD BE SHOWN ON EITHER THIS PLAN OR ANOTHER
 SHEET, FBC 1027.
  
 27. G101, DOOR 102 IS SHOWN AS AN EXIT, BUT A101 SHOWS
 THIS DOOR ENTERING ANOTHER (FUTURE) BUILDING, PLEASE
 CLARIFY, FBC 3302.1. ALTHOUGH THIS MAY BE ADDRESSED ON
 ANOTHER PLAN CURRENTLY IN THE PLAN REVIEW PROCESS, EACH
 PERMIT IS TO DEMONSTRATE CODE COMPLIANCE WITHOUT
 RELYING ON ANOTHER PLAN (PARTICULARLY ONE WHICH IS NOT
 YET ISSUED OR REVIEWED).
  
 28. UL ASSEMBLIES ARE SPECIFIED ON THE PLANS IN VARIOUS
 PLACES (EXAMPLE A301). FBC 107, EITHER INCORPORATE THE
 UL DETAILS INTO THE PLAN OR, PRIOR TO INSTALLATION, A
 SUBMITTAL WILL BE REQUIRED. THE SUBMITTAL SHOULD
 INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED
 TO BE MARKED. THE SUBMITTAL IS REQUIRED TO BE REVIEWED
 BY DOR. IF THE UL ASSEMBLIES ARE NOT INCORPORATED INTO
 THE PLAN WITH OPTIONS INDICATED, THE SUBMITTAL IS
 REQUIRED TO BE APPROVED THROUGH PLAN REVIEW PRIOR TO
 INSTALLATION.
  
 IF THE ASSEMBLIES WITH APPLICABLE OPTIONS ARE NOT
 INCORPORATED INTO THE PLAN, FUTURE SUBMISSION AS A
 SUBMITTAL WILL BE A PROVISO ITEM.
  
 29. SHEET A301 AND OTHER PAGES AS APPLICABLE, SPECIFY
 FIRE RESISTANCE RATING ON THE PLAN SO DESIGN INTENT IS
 CLEAR, FBC TABLE 601. IF A REDUCTION IS TAKEN DUE TO AN
 EXCEPTION, CITE THE APPLICABLE EXCEPTION (SUCH AS FBC
 2010 BUILDING 402.1.1(2)) AND PROVIDE ENOUGH
 INFORMATION REGARDING THE EXISTING BUILDING TO
 DEMONSTRATE COMPLIANT APPLICABILITY.
  
 30. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED
 FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS,
 STRUCTURAL FRAME, FBC TABLE 601.
  
 31. SHEET S3.1, WIND LOADS, 170 MPH, RISK CATEGORY II,
 EXPOSURE C, ENCLOSED IS STATED AS WIND DESIGN CRITIERA
 FBC 1609. SEE SHEET G000, THE MAP FOR RISK CATEGORY III
 AND IV BUILDINGS IS SHOWN (FBC FIGURE 1609B). PLEASE
 CORRELATE.
  
 IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL
 BUILDING OCCUPANT LOAD.
  
 32. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE
 (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY
 AS APPLICABLE.
  
 33. S3.1, STANDARDS CANNOT BE REFERENCED AS "LATEST
 EDITION," SEE FBC 2010 CHAPTER 35. DESIGN IS TO COMPLY
 WITH THE STANDARD VERSION REFERENCED IN CHAPTER 35,
 REVISE ALL AS APPLICABLE.
  
 IF ENGINEER HAS SPECIFIC CONDITIONS WHERE THE EDITION
 USED FOR DESIGN CONFLICTS WITH THE EDITION SPECIFIED IN
 FBC CHAPTER 35, THIS CAN BE PROPOSED UNDER FBC 104.11,
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION. IF APPLICABLE, THIS SHOULD BE DONE PRIOR
 TO RESUBMITTAL FOR CONSIDERATION BY THE BUILDING
 OFFICIAL.
  
 34. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES,
 PLYWOOD SHEATHING SHOWN. THIS BUILDING IS REQUIRED TO
 BE NON COMBUSTIBLE, FBC 602.1. REVISE TO INCLUDE
 REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND
 OTHER SHEETS), FBC 603.1.1.1.3.
  
 35. S3.2, SPECIFY FLOOR LOADS FOR 2ND FLOOR MECHANICAL
 ROOM, FBC 1606, 1607.
  
 36. A101, DETAILS 7 AND 11, REVISE TO SHOW CENTER LINE
 AND DISTANCE REQUIRED FOR GRAB BAR, SEE FBC 2010
 ACCESSIBILITY FIGURE 604.5.2.
  
 37. A101, DETAIL 3, DOOR APPEARS TO ENCROACH CLEAR
 FLOOR SPACE REQUIRED FOR LAVATORY IN ROOM 111, FBC 2010
 ACCESSIBILITY 603.2.3.
  
 38. A101, DETAIL 3, SHOW 18IN CLEARANCE FOR DOOR 112,
 PULL SIDE, FBC ACCESSIBILITY FIGURE 404.2.4.1(A).
  
 39. A101, DETAIL 3, PROVIDE A DETAIL FOR THE DRINKING
 FOUNTAIN (INCLUDING CLEAR FLOOR SPACE), FBC 2010
 ACCESSIBILITY 211.
  
 40. DETAIL A502 AND 1 A503, OTHER LOCATIONS, ROOF
 DETAIL IS LACKING THE 90LB OR OTHER CAP SHEET FOR TILE
 WHICH IS A REQUIREMENT IN THE CONCRETE ROOF TILE
 PRODUCT APPROVAL, FBC 1609.
  
 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC
 SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS.
 ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR
 ACCESS FOR MAINTENANCE, FBC 107.
  
 42. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A
 CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC
 ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF
 APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE
 EXIT HARDWARE, FBC 1008.1.10.
  
 43. FBC 1503.4, PROVIDE ROOF DRAINAGE CALUCLATIONS.
  
 44. DETAIL 4 SHEET A503, OVERFLOW SCUPPER APPEARS TO BE
 AT ROOF LEVEL. SEE FBC 1503.4.2.1, OVERFLOW SCUPPERS TO
 BE NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE
 THE ROOF COVERING.
  
 45. SHEET G101, FIRST FLOOR LIFE SAFETY PLAN, DOES NOT
 INCLUDE EXITING FOR THE OCCUPANTS OF THE COURTYARD, FBC
 1004.8. REVISE PLAN TO INCLUDE TRAVEL DISTANCE. IF
 OCCUPANT LOAD IS OVER 50, DOOR 109A TO SWING IN THE
 DIRECTION OF TRAVEL, BUT ALSO CANNOT BLOCK THE
 CORRIDOR, FBC 1008.1.2, 1005.2.
  
 46. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND
 FLOORS.
  
 47. SEE FIRE COMMENTS REGARDING EXIT SIGNS, FBC 1011.1.
  
 48. REVISE PLAN TO SHOW LOCATION AND TYPE OF FIRE ALARM
 DEVICES, FBC 403.4.2, FBC ACCESSIBILITY 702.
  
 49. NO INFORMATION PROVIDED REGARDING SOME OF THE OTHER
 HIGH RISE REQUIREMENTS (FBC 403). SOME MAY BE EXISTING
 IN ANOTHER PORTION OF THE BUILDING NOT SHOWN, SOME MAY
 NOT BE REQUIRED DUE TO CODE IN EFFECT WHEN BUILDING WAS
 PERMITTED, BUT IN ORDER TO PROVIDE A COMPLETE REVIEW,
 DESIGNER TO ELECT METHOD OF ALTERATION AND STATE THE
 CODE UNDER WHICH THE EXISTING BUILDING WAS CONSTRUCTED.
  
 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH
 THIS SECTION.
  
  
  