2015-03-31 11:25:34 | 4920 LORING DRIVE |
| PERMIT #14120908 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION |
| AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| DEMO: PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION |
| SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| |
| DEMO: PER NFPA 241, CONSTRUCTION/DEMOLITION AREAS SHALL |
| BE SEPARATED WITH A 1-HOUR FIRE BARRIER FROM OTHER |
| AREAS NOT UNDER CONSTRUCTION OR DEMOLITION. |
| |
| SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH |
| EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| WITH FLORIDA AMENDMENTS. |
| |
| SHEET G101: TWO DINING ROOM EXITS DISCHARGE OUTSIDE AT |
| THE EAST SIDE OF THE BUILDING INTO THE CONSTRUCTION |
| ZONE FOR THE NEW HIGH-RISE BUILDING. |
| |
| SHEET G101: FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES |
| WITH AN OCCUPANT LOAD OF 100 OR MORE PERSONS (50 |
| PERSONS PER THE FLORIDA BUILDING CODE), PANIC HARDWARE |
| SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| BE RELEASED BY THE PANIC HARDWARE. |
| |
| SHEET A101: SUBMIT A FURNITURE/SEATING PLAN. |
| |
| SHEET A101: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING |
| FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM |
| POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM |
| THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| SHEET A101: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| EXIT DOORS WITH EXIT SIGNS. |
| |
| SHEET E103: VERANDA #101/CORRIDOR HAS EXIT SIGNS SPACED |
| MORE THAN 100 FEET APART. |
| |
| SHEET E103: NO ENGINEERED FIRE ALARM DRAWINGS |
| SUBMITTED. PER FBC SECTION 907.1.1 CONSTRUCTION |
| DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM |
| SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL." PER SECTION |
| 12.3.4.3.3, PROVIDE SPEAKER/STROBE NOTIFICATION |
| APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM |
| NOTIFICATION BY VISIBLE SIGNALS AND VOICE |
| ANNOUNCEMENTS. |
| |
| SHEET FP001: NO WATER SUPPLY INFORMATION PROVIDED |
| (HYDRANT FLOW TEST OR FIRE PUMP TEST DATA). |
| |
| DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| VIOLATIONS OF THIS CODE. |
| |