2015-03-31 11:25:344920 LORING DRIVE
 PERMIT #14120908
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 DEMO: PER NFPA 241, CONSTRUCTION/DEMOLITION AREAS SHALL
 BE SEPARATED WITH A 1-HOUR FIRE BARRIER FROM OTHER
 AREAS NOT UNDER CONSTRUCTION OR DEMOLITION.
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET G101: TWO DINING ROOM EXITS DISCHARGE OUTSIDE AT
 THE EAST SIDE OF THE BUILDING INTO THE CONSTRUCTION
 ZONE FOR THE NEW HIGH-RISE BUILDING.
  
 SHEET G101: FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES
 WITH AN OCCUPANT LOAD OF 100 OR MORE PERSONS (50
 PERSONS PER THE FLORIDA BUILDING CODE), PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 SHEET A101: SUBMIT A FURNITURE/SEATING PLAN.
  
 SHEET A101: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A101: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 SHEET E103: VERANDA #101/CORRIDOR HAS EXIT SIGNS SPACED
 MORE THAN 100 FEET APART.
  
 SHEET E103: NO ENGINEERED FIRE ALARM DRAWINGS
 SUBMITTED. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL." PER SECTION
 12.3.4.3.3, PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS.
  
 SHEET FP001: NO WATER SUPPLY INFORMATION PROVIDED
 (HYDRANT FLOW TEST OR FIRE PUMP TEST DATA).
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  