Plan Review Notes
Plan Review Notes For Permit 14120908
Permit Number 14120908
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-06 08:21:225/6/2015
 PROJECT: TRADITION ONE DINING ROOM EXPANSION
 PERMIT#: 14120908
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SHEET E001
 1) CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN
 SCOPE OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING
 THIS NOTE AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN
 TO THIS SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE
 SCOPE OF WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT
 A NEW PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN
 THE PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE
 NEW, WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE
 EXISTING TO REMAIN.
  
 SHEET E002
 CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN SCOPE
 OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING THIS NOTE
 AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN TO THIS
 SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE SCOPE OF
 WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT A NEW
 PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN THE
 PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE NEW,
 WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE EXISTING
 TO REMAIN.
  
 SHEET E102
 1) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN
 THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN.
 2) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE
 THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT
 NUMBER.
 3) CLARIFY CIRCUITRY AND EQUIPMENT ON FLOOR PLAN. THERE
 IS A NOTE 2 THAT CALLS OUT AN RTU ON THE SECOND FLOOR
 AND A CONFLICTING EQUIPMENT DESIGNATION AS AHU-1-1 WITH
 A NOTE THE MAKES REFFERENCE TO THE CIRCUIT FEEDING IT
 COMING FROM PANEL MDP. THERE IS NO EQUIPMENT NAMED
 EITHER RTU OR AHU 1-1 IN PANEL MDP. CLARIFY IF THIS IS
 AND AHU OR AND RTU. CLARIFY IT'S NUMBER DESIGNATION,
 PANEL AND CIRCUIT FEEDING IT.
  
 SHEET E-103
 1) FBC-ENERGY 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 2) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN
 THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN.
 3) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE
 THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT
 NUMBER.
  
 E601
 1) INDICATE WHICH CIRCUIITS ARE NEW, WHICH ARE
 RELOCATED, FROM WHERE, AND WHICH ARE EXISTING TO
 REMAIN.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  