2015-05-06 08:21:22 | 5/6/2015 |
| PROJECT: TRADITION ONE DINING ROOM EXPANSION |
| PERMIT#: 14120908 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| SHEET E001 |
| 1) CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN |
| SCOPE OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING |
| THIS NOTE AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN |
| TO THIS SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE |
| SCOPE OF WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT |
| A NEW PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN |
| THE PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE |
| NEW, WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE |
| EXISTING TO REMAIN. |
| |
| SHEET E002 |
| CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN SCOPE |
| OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING THIS NOTE |
| AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN TO THIS |
| SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE SCOPE OF |
| WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT A NEW |
| PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN THE |
| PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE NEW, |
| WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE EXISTING |
| TO REMAIN. |
| |
| SHEET E102 |
| 1) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN |
| THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN. |
| 2) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE |
| THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT |
| NUMBER. |
| 3) CLARIFY CIRCUITRY AND EQUIPMENT ON FLOOR PLAN. THERE |
| IS A NOTE 2 THAT CALLS OUT AN RTU ON THE SECOND FLOOR |
| AND A CONFLICTING EQUIPMENT DESIGNATION AS AHU-1-1 WITH |
| A NOTE THE MAKES REFFERENCE TO THE CIRCUIT FEEDING IT |
| COMING FROM PANEL MDP. THERE IS NO EQUIPMENT NAMED |
| EITHER RTU OR AHU 1-1 IN PANEL MDP. CLARIFY IF THIS IS |
| AND AHU OR AND RTU. CLARIFY IT'S NUMBER DESIGNATION, |
| PANEL AND CIRCUIT FEEDING IT. |
| |
| SHEET E-103 |
| 1) FBC-ENERGY 505.2 LIGHTING CONTROLS (MANDATORY). |
| LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| 505.2.4. |
| 2) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN |
| THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN. |
| 3) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE |
| THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT |
| NUMBER. |
| |
| E601 |
| 1) INDICATE WHICH CIRCUIITS ARE NEW, WHICH ARE |
| RELOCATED, FROM WHERE, AND WHICH ARE EXISTING TO |
| REMAIN. |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |