2015-01-10 13:09:46 | BUILDING PLAN REVIEW |
| PERMIT: 14120908 |
| ADD: 4920 LORING DR. |
| CONT: THE WHITING TURNER CO. |
| CONTACT: RYAN TEMPONE |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW- FOUNDATION PERMIT/ TRADITION I DINING ROOM |
| EXTENTION |
| DATE: SAT. JAN. 10/ 2015 |
| ACTION: DENIED |
| |
| NOTE: FOUNDATION PERMIT/ PHASED PERMITING. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION |
| 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE |
| APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION |
| AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| |
| 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT: |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION |
| |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND |
| THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES |
| BETWEEN. |
| 1.2) SURVEY WITH FLOOD ZONE DESIGNATION |
| 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR |
| THIS BUILDING |
| 1.4) A ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR |
| BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS. |
| 1.5) OCCUPANCY TYPE |
| 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES |
| |
| 2) SINCE THE TRADITION TOWER WILL BE ASSUMED THE 10 |
| STORY THERE HAS BEEN DISCUSSION ABOUT, THIS BUILDING |
| WOULD BE CLASSIFIED AS A THRESHOLD BUILDING BY |
| DEFINITION AND NEED TO MEET THE STATE REQUIREMENTS FOR |
| SUCH A BUILDING. NOTE SHEET S-1.1 DRAWING INDEX |
| INDICATES 10 FLOOR FRAMING PLAN. |
| |
| THE DINING ROOM APPEARS TO BE AN ADDITION TO ANOTHER |
| BUILDING BUT CONNECTED BY A ENCLOSED PEDESTRIAN WALKWAY |
| BETWEEN BUILDINGS. THE BUILDING TYPE IS NOT KNOWN FOR |
| THE OTHER BUILDING, OCCUPANCY, SPRINKLERED OR NOT. THE |
| PLANS ALSO DO NOT SHOW FIRE BARRIERS BETWEEN THE |
| PEDESTRIAN WALKWAY AND THE BUILDING. PLEASE SHOW |
| COMPLIANCE WITH 2010 FBC-B 3104.5. |
| |
| SINCE THE HEIGHT OF THE BUILDING THE DINING ROOM |
| ADDITION IS PART OF THE THRESHOLD BUILDING REQUIREMENTS |
| WILL STAY PART OF THIS REVIEW. IN REVIEWING THE P. B.C. |
| PROPERTY APPRAISERS OFFICE LIST A STRUCTURE AT 4920 |
| LORING DR, IS THIS AND ADDITION TO THAT STRUCTURE. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| NOTE :THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE |
| 1/10/2015 01:05 PM. |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2A) SHEET S-8.10THRESHOLD INSPECTION NOTES NOT INCLUDED |
| IN THIS SUBMITTAL. 109.3.6.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| (WRITTEN/ TYPED) STRUCTURAL INSPECTION PLAN PREPARED BY |
| THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE INSPECTION COMPANY & |
| THRESHOLD INSPECTOR WILL NEED TO FILL OUT THE SPECIAL |
| INSPECTOR AGREEMENT FORMS AND RESUBMIT TO THE CITY FOR |
| REVIEW. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 2F) NOTE THIS IS A DIGITAL PLAN, AFTER PERMIT ISSUANCE, |
| THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLLOR, (1) |
| FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| 2G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL |
| COMPLY WITH : |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF |
| CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS |
| OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE |
| CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, |
| DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW |
| CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL |
| HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 5) THE (4) FOUNDATION SHEETS SUBMIITED DOES NOT HAVE |
| ENOUGH INFORMATION ON THESE SHEETS WITH DIMENSIONS, NOR |
| STEEL LAYOUT FOR THE VERTICAL COLUMNS, NOR COLUMN |
| SIZES. THE DETAIL SHEETS AND SECTIONS FOR ELEVATOR PITS |
| ARE ALSO MISSING FROM THIS SUBMITTAL, THE MINIMUM |
| BEARING VALUE NOT PROVIDED, MINIMUM CONCRETE DESIN MIX, |
| THERE IS NOT ENOUGH INFORMATION PROVIDED TO DO A |
| THROGOUGH REVIEW. |
| |
| 6) 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE |
| PROTECTION SHALL BE PROVIDED BY REGISTERED |
| TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES, |
| BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR |
| OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE |
| TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| AND CONSUMER SERVICES." |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |