2015-02-10 14:49:40 | THIS IS A CONCEPTUAL LEVEL REVIEW. TECHNICAL DETAILS OF |
| THE WATER, SEWER, STORMWATER, TRAFFIC CIRCULATION, AND |
| SOLID WASTE COLLECTION ARE BEING REVIEWED AS PART PART |
| OF THE ENGINEERING DEVELOPMENT APPROVAL AND BUILDING |
| PERMIT APPLICATION PROCESSES (E15010026). |
| |
| 1. PLEASE INCLUDE ONE COPY OF THE LANDSCAPE PLAN |
| SHOWING THAT THE CLEAR ZONE AROUND THE FIRE HYDRANTS |
| WILL BE MAINTAINED. A WORKING SPACE OF NOT LESS THAN 36 |
| INCHES IN DIAMETER AND 78 INCHES IN HEIGHT SHALL BE |
| PROVIDED AND MAINTAINED AROUND THE CIRCUMFERENCE OF |
| FREE-STANDING FIRE DEPARTMENT CONNECTIONS. (FBC SECTION |
| 912 AND CWPB CODE 94-302) |
| |
| 2. SUBMIT POTABLE WATER DEMAND, SANITARY PEAK FLOW, AND |
| YARDAGE CALCULATIONS FOR THE POTABLE WATER, SANITARY |
| SEWER, AND SOLID WASTE COLLECTION. |
| |
| 3. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS |
| OF ALL WATER METERS, VALVES, CLEAN-OUTS, DRAINAGE |
| FACILITIES, SANITARY LINES ETC. CONSIDER UTILIZING ROOT |
| BARRIERS WHERE PLANTINGS ARE NEAR UNDERGROUND |
| STORMWATER, SANITARY, OR POTABLE WATER LINES. |
| |
| 4. SUBMIT A FORMAL STRIPING PLAN FOR THE WORK WITHIN |
| THE FLAGLER RIGHT-OF-WAY. (SEE CONDITION 2 OF SITE PLAN |
| APPROVAL LETTER.) PLAN SHALL INCLUDE LAND DIMENSIONS, |
| STRIPING DETAILS, ETC. OVERLAID ON AN AERIAL |
| PHOTOGRAPH. |
| |
| 5. PLEASE REVISE THE SIGNING AND MARKING PLAN TO |
| INCLUDE THE SIGNAGE MENTIONS IN CONDITION 3B OF THE |
| SITE PLAN APPROVAL LETTER. |
| |