Plan Review Notes For Permit 14120850 |
Permit Number |
14120850 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-31 10:31:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | SHEET A1.0 INDICATES DOOR # 5 AS A NON-RATED DOOR | | COMMUNICATING TO A STORAGE AREA. CHANGE DOOR # 5 TO A | | 20 MIN DOOR. |
|