2015-01-05 17:43:26BUILDING PROVISO:
 DOORS 2 & 5 ARE LOCATED IN A FIRE BARRIER WALL
 (OCCUPANCY SEPERATION WALL),
 2010 FBC-B TABLE 715.4 REQUIRES THESE DOORS TO BE 45
 MINUTE DOORS NOT A 20 MINUTE DOOR.