2015-01-05 17:43:26 | BUILDING PROVISO: | | DOORS 2 & 5 ARE LOCATED IN A FIRE BARRIER WALL | | (OCCUPANCY SEPERATION WALL), | | 2010 FBC-B TABLE 715.4 REQUIRES THESE DOORS TO BE 45 | | MINUTE DOORS NOT A 20 MINUTE DOOR. |
|