Plan Review Notes For Permit 14120732
Permit Number 14120732
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-05 14:20:02****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 PLAN REVIEW HAS BEEN PASSED WITH REDLINES.
  
 THE INSTALLATION SCHEDULE HAS BEEN REVISED AND THE NOA
 HAS BEEN CIRCLED SO THAT CONTRACTOR CAN SEE WHERE THE
 INFORMATION WAS OBTAINED. IF CONTRACTOR DOES NOT AGREE
 WITH THE CHANGES, PLEASE REVISE THE PRODUCT APPROVAL TO
 INDICATE ANCHORING PROPOSED, REVISE THE INSTALLATION
 SCHEDULE, AND PROVIDE EXPLANATION FOR THE FOLLOWING:
  
 PAGE 10, A DETAIL WITH WOOD SUBSTRATE CIRCLED, BUT IT
 APPEARS THAT WOOD IS NOT A SUBSTRATE FOR ANY OPENINGS.
 INSTALLATION SCHEDULE STATED THAT SUBSTRATE IS
 CONCRETE; MOST CBS STRUCTURES HAVE CONCRETE TOP (FORMED
 AND POURED TIE BEAM OR LINTEL) AND BLOCK BOTTOM
 SUBSTRATES.
 OPENINGS 7 & 8, DUE TO THE SIZE IT APPEARS THAT THEY
 ARE SLIDING GLASS DOORS. THE FLOOR PLAN IS NOT CLEAR.
 THESE TWO OPENINGS ARE LIKELY CONCRETE TOP & BOTTOM,
 BUT I WAS UNABLE TO LOCATE MOUNTING CONNECTION TYPE
 "D2" ON THE PRODUCT APPROVAL (SEE PAGES 4 & 5 - A, B, C
 ONLY).
  
  
  
  