2015-03-07 13:14:51 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| |
| 1. OK |
| |
| 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND |
| OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE |
| CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. |
| |
| TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION |
| NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN |
| HEIGHT: |
| |
| STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS |
| - AWNING, CASEMENT, SINGLE HUNG? |
| |
| STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. |
| CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE |
| WINDOW IS FULLY OPEN. |
| |
| 3. NEW COMMENT - IT IS NOT POSSIBLE TO DETERMINE |
| CORRELATE THE PRODUCT APPROVALS WITH THE OPENINGS. FOR |
| INSTANCE: |
| |
| PRODUCT APPROVAL 14610.5 VINYL HORIZONTAL ROLLER NON |
| IMPACT HAS "WINDOW #3" WRITTEN ON IT, BUT OPENING #3 |
| DOES NOT HAVE SHUTTERS PROPOSED. |
| |
| 14610.6 AND 17472.2 ARE IMPACT PRODUCTS, "W-3" WRITTEN |
| ON BOTH. |
| |
| REVISE THE FLOOR PLAN TO INDICATE TYPE OF WINDOW |
| PROPOSED (CORRELATE WITH THE PRODUCT APPROVAL), |
| INDICATE LOCATION OF THE IMPACT WINDOWS. PROVIDE THE |
| SIZES OF ALL OPENIINGS AND THE ADDITIONAL INFORMATION |
| REQUIRED FOR BEDROOM WINDOWS AS INDICATED IN ITEM #2. |
| |
| THE PAGE PROVIDED PREVIOUSLY NO LONGER CORRELATES WITH |
| THE NEW FLOOR PLAN AND PRODUCT APPROVALS PROVIDED. FOR |
| INSTANCE, OPENING #3 ON THE CHART PROVIDED IN FIRST |
| SUBMITTAL STATES THAT FL1850 R9 IS PROPOSED, NOT |
| CONSISTENT WITH THE NEW INFORMATION. |
| |
| |
| |