2015-01-08 16:39:55 | 705 NORTH OLIVE AVENUE |
| PERMIT #14120670 |
| MASTER #14030096 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE PERMIT APPLICATION FOR THE SPRINKLER WORK NEEDS TO |
| INCLUDE A JOB VALUE (LABOR AND MATERIALS). KAST |
| CONSTRUCTION'S MASTER PERMIT VALUE SHOULD NOT INCLUDE |
| SUB-PERMIT VALUES SUCH AS FIRE SPRINKLER, FIRE ALARM, |
| ETC. |
| |
| THE MASTER BUILDING PERMIT PLANS ALREADY ESTABLISH THE |
| FIRE PROTECTION ENGINEER OF RECORD; THEREFORE, THE |
| SPRINKLER SHOP DRAWINGS SHOULD NOT BE SIGNED AND SEALED |
| BY BRIAN MESKOL P.E. UNLESS HE HAS BEEN ASSIGNED TO BE |
| A DELEGATED ENGINEER BY THE ENGINEER OF RECORD. |
| |
| THE 1/16-INCH SCALED DRAWINGS ARE TOO DIFFICULT READ |
| AND SCALE. |
| |
| PROVIDE CEILING/SOFFIT ELEVATIONS ON PLANS SO |
| COMPLIANCE WITH OBSTRUCTION RULES CAN BE VERIFIED. |
| |
| INDICATE THE HANGER TYPE OR METHOD TO BE USED FOR |
| RESTRAINING UPWARD MOVEMENT. |
| |
| FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) |
| INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR |
| UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM |
| SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF |
| DECK (IF OBSTRUCTED CONSTRUCTION). |
| |
| SHEET 1 OF 8: THE 6-INCH STANDPIPE FEED MAIN APPEARS TO |
| BE ROUTED OUTSIDE OF THE BUILDING ADJACENT TO STAIR #5. |
| INDICATE HOW THIS PIPING BE SUPPORTED AND PROTECTED |
| FROM MECHANICAL DAMAGE. |
| |
| SHEET 1 OF 8: CONFIRM CORROSION RESISTANT PIPING AND |
| FITTINGS ARE NOT APPROPRIATE FOR THE TRASH ROOMS AND |
| PARKING STRUCTURE AREAS. |
| |
| SHEET 3 OF 8: CONFIRM THE PARKING GARAGE |
| CEILING/STRUCTURE DOES NOT EXCEED A SLOPE OF 2 IN 12 |
| REQUIRING THE HYDRAULIC AREA TO BE INCREASED BY 30%. |
| |
| SHEET 6 OF 8: CONFIRM THE SPRAY FROM 4 CONTIGUOUS |
| SPRINKLERS ON THE SAME 3/4-INCH CPVC BRANCH LINE IN |
| UNIT B2 IS NOT MORE HYDRAULICALLY DEMANDING. |
| |
| SHEET 6 OF 8: PLANS INDICATE A SCALE OF 3/16"=1'-0"; |
| HOWEVER, THERE ARE NO PLAN DIMENSIONS OR SCALE BAR TO |
| ENSURE THE SCALE IS ACCURATE ON THIS PAPER SIZE. |
| |
| NOTE: METRO SPRINKLER HAS INDICATED THAT THE |
| UNDERGROUND FIRE LINE IS NOT IN THEIR SCOPE WORK. A |
| SEPARATE PLAN, PERMIT AND CONTRACTOR IS NEEDED. |
| |