2014-12-23 15:35:41 | 600 OKEECHOBEE BOULEVARD |
| PERMIT #14120664 |
| MASTER #14050111 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: PLANS INDICATE UNDERGROUND FIRE PROTECTION |
| PIPING TO BE INSTALLED BY OTHERS. IS THIS TO BE DONE |
| UNDER A SEPARATE PERMIT AND CONTRACTOR OR IS THIS PART |
| OF SUMMER'S PERMIT AND SUMMERS IS HIRING A |
| SUBCONTRACTOR? |
| |
| GENERAL: ELIMINATE THE 1-1/2" REDUCER FROM THE 2-1/2" |
| HOSE VALVES. |
| |
| GENERAL: SUBMIT PRODUCT DATA FOR FIRE/JOCKEY PUMP, |
| CONTROLLERS, TRANSFER SWITCH, PRESSURE REGULATING |
| VALVES, BACKFLOW PREVENTERS, JOINT RESTRAINT |
| ASSEMBLIES, PIPE, FITTINGS, HANGERS, ETC. |
| |
| GENERAL: NORTH ARROWS (ALL SHEETS) APPEAR TO BE |
| POINTING IN THE WEST DIRECTION. |
| |
| SHEET FP-1: CANNOT LOCATE A SECONDARY FIRE DEPARTMENT |
| CONNECTION REQUIRED FOR HIG-RISE BUILDINGS. |
| |
| SHEET FP-1: SPRINKLER NOTE #5 DOES NOT INDICATE WHICH |
| ROOMS OR AREAS ARE DESIGNED AS LIGHT OR ORDINARY |
| HAZARD. SHEET FP-2 EVEN INDICATES A STORAGE ROOM |
| DESIGNATED AS ORDINARY HAZARD GROUP II WITH A DESIGN |
| DENSITY OF 0.20 GPM/SF. |
| |
| SHEET FP-2: CONFIRM FIRE PUMP ROOM IS LARGE ENOUGH FOR |
| PROPER INSTALLATION, CONTROLLER CLEARANCES AND WORKING |
| SPACE. PROVIDE PLAN VIEW DIMENSIONING EQUIPMENT TO BE |
| PROVIDED IN THIS ROOM. |
| |
| SHEET FP-2: COULD NOT LOCATE SPRINKLERS IN THE BASEMENT |
| POOL EQUIPMENT ROOM #B020. |
| |
| SHEET FP-3: SPRINKLER COVERAGES IN SERVICE CORRIDOR |
| APPEAR TO BE FOR LIGHT HAZARD. ORDINARY HAZARD MAY BE |
| MORE APPROPRIATE FOR THE EQUIPMENT AND STORAGE |
| TYPICALLY GATHERED IN THESE SPACES. |
| |
| SHEET FP-4: COULD NOT LOCATE SPRINKLER PROTECTION FOR |
| HYDRAULIC SERVICE ELEVATOR ADJACENT TO STAIR #4. |
| |
| SHEET FP-6: VERIFY (WITH LOAD CALCULATIONS) BAR TERRACE |
| CANOPY STRUCTURE CAN SUPPORT 5X THE WEIGHT OF |
| WATER-FILLED SPRINKLER PIPE. |
| |
| SHEET FP-8: PUMP ROOM #253 IS LOCATED ON THE SECOND |
| FLOOR. THESE SPRINKLERS WILL NEED TO BE SUPPLIED FROM |
| THE SECOND FLOOR SYSTEM/FLOW SWITCH TO AVOID CONFUSION |
| THINKING THERE IS A FIRE ON THE FIRST FLOOR WHEN IT IS |
| ACTUALLY ON THE SECOND. |
| |
| SHEET FP-9: COULD NOT LOCATE A FIRE DEPARTMENT HOSE |
| VALVE IN STAIR #3. |
| |
| SHEET FP-14: PLANS IN THE CENTRAL ELEVATOR LOBBY |
| INDICATE AN 1-1/2" LINE GOING UP TO THE ROOF; HOWEVER, |
| THE LINE SIZE INDICATES 1-INCH. |
| |
| SHEET FP-14: PLANS INDICATE RESIDENTIAL TYPE SPRINKLERS |
| TO BE USED IN THE PRES SUITE #1238; HOWEVER, THE |
| SCHEDULE INDICATES A QR TYPE SPRINKLER WITH A K-FACTOR |
| OF 5.6. |
| |
| SHEET FP-16: THE FIRE PUMP ROOM SECTION VIEW SHOWS THE |
| FIRE PUMP BEING FED FROM BELOW IN LIEU OF OVERHEAD. |
| PROVIDE ACCURATE DETAIL ENSURING LAMINAR/NON-TURBULENT |
| FLOW INTO THE FIRE PUMP SUCTION FLANGE. PER NFPA 20 |
| (2007 EDITION) SECTION 5.14.6.3.2, THE DISTANCE OF THE |
| FIRE PUMP SUCTION FLANGE AND ANY ADJACENT SUCTION PIPE |
| ELBOW/TEE FLANGE SHALL BE SEPARATED BY AT LEAST 10 PIPE |
| DIAMETERS WHEN THE ELBOW/TEE HAS A CENTERLINE PLANE |
| PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE: |
| THE CODE REQUIREMENTS HAVE NOT CHANGED IN THE LATEST |
| EDITION OF THE STANDARD; HOWEVER, DIAGRAMS OF |
| CORRECT/INCORRECT SUCTION PIPE INSTALLATIONS HAVE BEEN |
| UPDATED IN FIGURE A4.14.6 OF NFPA 20 - 2013 EDITION. |
| |
| GENERAL: FOR SYSTEM PRESSURES EXCEEDING 100 PSI, |
| ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS |
| SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL |
| BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE |
| THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING |
| UPWARD MOVEMENT. |
| |
| GENERAL: FOR THE AREAS EXPOSED TO STRUCTURE (NO |
| CEILING) INDICATE IF THE SPACE IS OBSTRUCTED |
| CONSTRUCTION OR UNOBSTRUCTED CONSTRUCTION AND INDICATE |
| THE SPRINKLER DISTANCE BELOW THE STRUCTURE OR ROOF DECK |
| (IF OBSTRUCTED CONSTRUCTION). |
| |
| GENERAL: PER NFPA 13 (2007 EDITION) SECTION 24.2.1.2, |
| PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO SYSTEM |
| WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE TESTED |
| AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING PRESSURE |
| AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR |
| 2-HOURS. |
| |
| GENERAL: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES |
| FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| POSITION. |
| |
| GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| GENERAL: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING |
| THE FIRE DEPARTMENT CONNECTION. |
| |
| GENERAL: INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE |
| ON EACH FLOOR. SPECIFY THE FLOORS THAT WILL HAVE |
| PRESSURE REGULATING VAVLES AND THEIR DESIGN SETTINGS. |
| RECOMMEND FIELD ADJUSTABLE TYPE VALVES. |
| |
| PRESSURE REGULATING VALVES: PER NFPA 14 SECTION 7.2.2 |
| WHEN SYSTEM PRESSURE-REGULATING DEVICES ARE USED IN |
| LIEU OF PROVIDING SEPARATE PUMPS, MULTIPLE ZONES SHALL |
| BE PERMITTED TO BE SUPPLIED BY A SINGLE PUMP AND |
| PRESSURE-REGULATING DEVICE(S) UNDER THE FOLLOWING |
| CONDITIONS: |
| (1) PRESSURE-REGULATING DEVICE(S) SHALL BE PERMITTED TO |
| CONTROL PRESSURE IN THE LOWER ZONE(S). |
| (2) A METHOD TO ISOLATE THE PRESSURE-REGULATING |
| DEVICE(S) SHALL BE PROVIDED FOR MAINTENANCE AND REPAIR. |
| (3) REGULATING DEVICES SHALL BE ARRANGED SO THAT THE |
| FAILURE OF ANY SINGLE DEVICE DOES NOT ALLOW PRESSURE IN |
| EXCESS OF 175 PSI (12.1 BAR) TO MORE THAN TWO HOSE |
| CONNECTIONS. |
| (4) AN EQUALLY SIZED BYPASS AROUND THE |
| PRESSURE-REGULATING DEVICE(S), WITH A NORMALLY CLOSED |
| CONTROL VALVE, SHALL BE INSTALLED. |
| (5) PRESSURE-REGULATING DEVICE(S) SHALL BE INSTALLED |
| NOT MORE THAN 7 FT 6 IN. (2.31 M) ABOVE THE FLOOR. |
| (6) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED |
| WITH INLET AND OUTLET PRESSURE GAUGES. |
| (7) THE FIRE DEPARTMENT CONNECTION(S) SHALL BE |
| CONNECTED TO THE SYSTEM SIDE OF THE OUTLET ISOLATION |
| VALVE. |
| (8) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED |
| WITH A PRESSURE RELIEF VALVE IN ACCORDANCE WITH THE |
| MANUFACTURERS RECOMMENDATIONS. |
| (9) REMOTE MONITORING AND SUPERVISION FOR DETECTING |
| HIGH PRESSURE FAILURE OF THE PRESSURE-REGULATING DEVICE |
| SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72, NATIONAL |
| FIRE ALARM CODE. |
| |
| DRAIN: PER NFPA 14 SECTION 7.11.1 A PERMANENTLY |
| INSTALLED 3 INCH DRAIN RISER WITH 2-1/2 INCH TEE (ON AT |
| LEAST EVERY OTHER FLOOR) SHALL BE PROVIDED ADJACENT TO |
| EACH STANDPIPE EQUIPPED WITH PRESSURE-REGULATING |
| DEVICES TO FACILITATE TESTING OF EACH DEVICE. |
| |
| JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1, |
| ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND |
| HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT |
| BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS. |
| |
| CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION |
| 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS, |
| WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE |
| CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR |
| OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL. |
| |
| HYDRAULIC CALCULATIONS: |
| BASEMENT CALCULATION INDICATES A OH GROUP 1; HOWEVER, |
| DRAWINGS AND CALCULATION INDICATE A DESIGN DENSITY OF |
| 0.20 GPM/SF. |
| |
| CALCULATIONS INDICATE PRESSURES AVAILABLE AS HIGH AS |
| 213 PSI? WHERE ARE THE 165 PSI PRVS IN THESE |
| CALCULATIONS? |
| |
| NO CALCULATIONS PERFORMED OR SUBMITTED FOR ROOF LEVEL |
| SPRINKLERS. |
| |
| CALCULATIONS DO NOT NECESSARILY SUPPORT THE MOST |
| HYDRAULICALLY DEMANDING PORTION OF THE SYSTEMS |
| CALCULATED. FOR EXAMPLE, THE 12TH FLOOR CALCULATION |
| SUPPORTS THE USE OF TWO RESIDENTIAL STYLE SPRINKLERS ON |
| A 1-INCH PIPE; HOWEVER, PRES SUITE #1238 SHOWS 3 |
| SPRINKLERS SUPPLIED FROM AN 1-1/4" PIPE WHICH IS NOT |
| SUPPORTED BY THE CALCULATIONS. THE BASEMENT LEVEL |
| RESTROOM (MENS' B009) IS CERTAINLY LOCATED MORE REMOTE |
| AND SUPPLIES 8 SPRINKLERS FROM 2-INCH PIPING WHICH IS |
| NOT SUPPORTED BY CALCULATIONS. |
| |
| PLAN REVIEW HAS BEEN DISCONTINUED AT THIS TIME DUE TO |
| TOO MANY COMMENTS. ADDITIONAL PLAN REVIEW COMMENTS MAY |
| BE GENERATED WHEN PLANS ARE RESUBMITTED. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |