2015-03-02 06:47:56BUILDING PLAN REVIEW
 PERMIT: 14120661
 ADD: 2601 OKEECHOBEE BLVD
 CONT: MASON DEVELOPMENT
 TEL: (561)623-8801
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. MAR. 02 /2015
 ACTION: BUILDING PROVISO
  
 1) MISSING WERE THE PRODUCT APPROVALS REQUIRED BY THE:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING,
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NOTE CIRCLE
 SUB-SYSTEMS AND THE ASSOCIATED PRESSURES, SEE DESIGN
 LIMITATIONS.
 NOTE: THIS CAN BE A DEFERRED SUBMITTAL UNDER THE
 ROOFING PERMIT, TO DO THIS THERE WOULD BE A MINIMUM
 PLAN REVIEW CHARGE.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) : DEALS WITH THE LOCATION OF THE BILCO HATCH.
 SEE SHEETS A2.02 AND A3.04. SHEET A2.02 SHOWS BOTH THE
 BILCO HATCH WITHIN 10'-0" OF THE PARAPET. SHEET A2.02
 DOES NOT PROVIDE A CUT SECTION THROUGH THE BUILDING
 PROVIDING THE ROOF ELEVATION AND FINISH PARAPET HEIGHT.
 PLEASE SEE 2010 FBC-B SECTIONS:
 2010 FBC-B 1013.6 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER