2015-02-03 11:56:52 | BUILDING PLAN REVIEW |
| PERMIT: 14120661 |
| ADD: 2601 OKEECHOBEE BLVD |
| CONT: MASON DEVELOPMENT |
| TEL: (561)623-8801 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. FEB. 03 /2015 |
| ACTION: DENIED |
| |
| 1) COMPLIED. SHEET A0.01 CODE SUMMARY: |
| |
| |
| 2) COMPLIED. ENERGY FORMS. |
| |
| 3) SEMI-COMPLIED/ PROVISO. 2010 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 1803.6 REPORTING. WHERE GEOTECHNICAL INVESTIGATIONS ARE |
| REQUIRED, A WRITTEN REPORT OF THE INVESTIGATIONS SHALL |
| BE SUBMITTED TO THE BUILDING OFFICIAL BY THE OWNER OR |
| AUTHORIZED AGENT AT THE TIME OF PERMIT APPLICATION. |
| THIS GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE |
| LIMITED TO, THE FOLLOWING INFORMATION: |
| 3.1. A PLOT SHOWING THE LOCATION OF THE SOIL |
| INVESTIGATIONS. |
| 3.2. A COMPLETE RECORD OF THE SOIL BORING AND |
| PENETRATION TEST LOGS AND SOIL SAMPLES. |
| 3.3. A RECORD OF THE SOIL PROFILE. |
| 3.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. |
| 3.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| CAPACITY OF NATURAL OR COMPACTED SOIL; |
| PROVISIONS TO MITIGATE THE EFFECTS OF EXPANSIVE SOILS; |
| MITIGATION OF THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL |
| SETTLEMENT AND VARYING SOIL |
| STRENGTH; AND THE EFFECTS OF ADJACENT LOADS. |
| 3.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. |
| |
| NOTE: THE NEW SHEET S-2 THE NEW SOILS NOTES IT APPEARS |
| THE ENGINEEER OF RECORD IS GOING TO BE THE SOILS |
| ENGINEER AS WELL. IT APPEARS THE ENGINEER IS ASKING |
| THIS CODE REQUIREMENT TO BE A DEFERRED SUBMITTAL, THE |
| ABOVE REPORTING REQUIREMENTS WILL NEED TO BE INCLUDED |
| IN THE SIGNED & SEALED DOCUMENTATION. |
| |
| 4) THIS BUILDING IS INDICATED AS HAVING 55,000 SQ. FT |
| OF COMMERCIAL SPACE TO BE REMODELED, A LEVEL III |
| ALTERATION. THIS BUILDING WILL QUALIFY FOR A ONSITE |
| RESIDENT INSPECTOR. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.3.9 OTHER |
| INSPECTIONS SERVICES. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| INCH |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| |
| NOTE; RESIDNET INSPECTOR PACKAGE AND FORMS WERE SENT |
| TO, E-MAIL : [email protected] 12/20/2014 |
| |
| 4A) COMPLIED. SUCH INSPECTORS SHALL BE ADEQUATELY |
| PRESENT AT TIMES WORK IS UNDERWAY ON THE STRUCTURAL |
| ELEMENTS OF THE BUILDING. SUCH INSPECTORS SHALL BE A |
| REGISTERED ARCHITECT, OR ENGINEER, OR A PERSON LICENSED |
| UNDER CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| |
| 4B) NOTE ONLY NO ACTION REQUIRED. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 110.4 INSPECTION AGENCIES. THE BUILDING |
| OFFICIAL IS AUTHORIZED TO ACCEPT REPORTS OF APPROVED |
| INSPECTION AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE |
| REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY. THE |
| RESIDENT INSPECTOR AND ALL INTERESTED PARTIESSHALL FILE |
| OUT AND BE NOTIRIZED, THE RESIDENT INSPECTOR FORMS AND |
| RETURN TO THE CITY BEFORE PERMIT ISSUANCE, |
| |
| 4C)NOTE ONLY NO ACTION REQUIRED. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 110.5 INSPECTION REQUESTS. IT SHALL BE |
| THE DUTY OF THE HOLDER OF THE BUILDING PERMIT OR THEIR |
| DULY AUTHORIZED AGENT TO NOTIFY THE BUILDING OFFICIAL |
| WHEN WORK IS READY FOR INSPECTION. IT SHALL BE THE DUTY |
| OF THE PERMIT HOLDER TO PROVIDE ACCESS TO AND MEANS FOR |
| INSPECTIONS OF SUCH WORK THAT ARE REQUIRED BY THIS |
| CODE. |
| |
| 4D) 2ND REQUEST. PLEASE NOTE (3) SETS OF PLANS AND |
| PRODUCT APPROVALS WILL BE REQUIRED, A 3RD SET FOR THE |
| RESIDENT INSPECTOR. |
| |
| 4E) NEW NOTE: THE RESIDENT INSPECTOR FORMS SUBMITTED |
| WERE FILLED OUT BY THE ENGINEER/ SPECIAL INSPECTOR, BUT |
| THE PORTION TO BE FILLED OUT BY THE CONTRACTOR IS BLANK |
| AND NOT NOTIRIZED. |
| |
| 5) MISSING WERE THE PRODUCT APPROVALS REQUIRED BY THE: |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING, |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NOTE CIRCLE |
| SUB-SYSTEMS AND THE ASSOCIATED PRESSURES, SEE DESIGN |
| LIMITATIONS. |
| NOTE: THIS CAN BE A DEFERRED SUBMITTAL UNDER THE |
| ROOFING PERMIT, TO DO THIS THERE WOULD BE A MINIMUM |
| PLAN REVIEW CHARGE. |
| |
| 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7-8) COMPLIED. |
| |
| 9A) COMPLIED.PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| 1509.6 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| ELEVATED STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. |
| |
| 9B) NEW COMMENT: DEALS WITH THE LOCATION OF THE BILCO |
| HATCH AND ROOF TOP A/C UNIT #1. SEE SHEETS A2.02 AND |
| A3.04. SHEET A2.02 SHOWS BOTH THE BILCO HATCH AND RTU # |
| 1 WITHIN 10'-0" OF THE PARAPET. SHEET A2.02 DOES NOT |
| PROVIDE A CUT SECTION THROUGH THE BUILDING PROVIDING |
| THE ROOF ELEVATION AND FINISH PARAPET HEIGHT. PLEASE |
| SEE 2010 FBC-B SECTIONS: |
| |
| 1013.5 MECHANICAL EQUIPMENT. |
| GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| |
| 1013.6 ROOF ACCESS. |
| GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| INCHES (533 MM) IN DIAMETER. |
| |
| |
| 10-13) COMPLIED. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |