Plan Review Notes
Plan Review Notes For Permit 14120646
Permit Number 14120646
Review Stop G
Sequence Number 1
Notes
Date Text
2014-12-24 05:42:111) GALVANIZED PIPNG IS NOT PERMITTED BELOW GRADE PER
 THE 2010 FL. GAS CODE SECS.403.8, 404.9, 404.9.2.
 2) ON THE SURVEY, SHOW THE DISTANCE OF THE GENERATOR
 FROM THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH
 NFPA 37 SEC. 4.1.4.
 3) THE GENERATOR EXHAUST SHALL BE A MIN. 10 FT. FROM
 ANY BUILDING OPENINGS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  