Plan Review Notes For Permit 14120646 |
Permit Number |
14120646 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-24 05:42:11 | 1) GALVANIZED PIPNG IS NOT PERMITTED BELOW GRADE PER | | THE 2010 FL. GAS CODE SECS.403.8, 404.9, 404.9.2. | | 2) ON THE SURVEY, SHOW THE DISTANCE OF THE GENERATOR | | FROM THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH | | NFPA 37 SEC. 4.1.4. | | 3) THE GENERATOR EXHAUST SHALL BE A MIN. 10 FT. FROM | | ANY BUILDING OPENINGS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|