2015-01-15 03:45:421) THE MODEL NUMBER ON THE MANUFACTURER'S SPEC SHEETS
 FOR THE GENERAC GENERATOR IS NOT LISTED IN THE APPROVED
 GENERAC MODEL LIST ON SHEET 1 OF 3 OF THE AMERICAST
 SLAB DRAWINGS.CLARIFY.
 2) THE MODEL NUMBER OF THE GENERATOR ON THE SUBMITTED
 MANUFACTURER'S SPEC SHEET AND THE AMERICAST SHEET ARE
 ALL DIFFERENT. CLARIFY.( THERE IS A SPEC SHEET WITH THE
 GAS DRAWING AND TWO OTHER SHEETS WITH THE OLANS AND
 NONE OF THE MODEL NUMBERS MATCH THE NUMBERS ON THE
 AMERICAST PLANS.)
 3)TTHERE ARE CALCULATIONS DONE ON SHT, 1 OF THE
 AMERICAST PLANS FOR THE GENERATOR ANCHORING BUT THESE
 CALCULATIONS ARE FOR A KOHLER GENERATOR, NOT A GENERAC.
 CLARIFY.
 4) IDENTIFY ON THE MANUFACTURER'S SPEC SHEETS THE
 CORRECT MODEL OF THE GENERATOR BEING INSTALLED. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 5) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FT.
 FROM THE EXTERIOR WALL PER NFPA 37 SEC.4.1.4. SHOW THE
 DISTANCE FROM THE EXTERIOR WALL ON THE SURVEY.
 6) THE GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FT.
 AWAY FROM ANY BUILDING OPENINGS. SHOW THIS ON THE
 SURVEY. WPB AMEND. TO 2010 FBC SEC.107.2.1.
  