Plan Review Notes For Permit 14120646 |
Permit Number |
14120646 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-15 03:45:42 | 1) THE MODEL NUMBER ON THE MANUFACTURER'S SPEC SHEETS | | FOR THE GENERAC GENERATOR IS NOT LISTED IN THE APPROVED | | GENERAC MODEL LIST ON SHEET 1 OF 3 OF THE AMERICAST | | SLAB DRAWINGS.CLARIFY. | | 2) THE MODEL NUMBER OF THE GENERATOR ON THE SUBMITTED | | MANUFACTURER'S SPEC SHEET AND THE AMERICAST SHEET ARE | | ALL DIFFERENT. CLARIFY.( THERE IS A SPEC SHEET WITH THE | | GAS DRAWING AND TWO OTHER SHEETS WITH THE OLANS AND | | NONE OF THE MODEL NUMBERS MATCH THE NUMBERS ON THE | | AMERICAST PLANS.) | | 3)TTHERE ARE CALCULATIONS DONE ON SHT, 1 OF THE | | AMERICAST PLANS FOR THE GENERATOR ANCHORING BUT THESE | | CALCULATIONS ARE FOR A KOHLER GENERATOR, NOT A GENERAC. | | CLARIFY. | | 4) IDENTIFY ON THE MANUFACTURER'S SPEC SHEETS THE | | CORRECT MODEL OF THE GENERATOR BEING INSTALLED. WPB | | AMEND. TO 2010 FBC SEC. 107.2.1. | | 5) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FT. | | FROM THE EXTERIOR WALL PER NFPA 37 SEC.4.1.4. SHOW THE | | DISTANCE FROM THE EXTERIOR WALL ON THE SURVEY. | | 6) THE GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FT. | | AWAY FROM ANY BUILDING OPENINGS. SHOW THIS ON THE | | SURVEY. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|