2014-12-18 08:18:26 | 12/18/2014 |
| PROJECT: WOMELSDORFF |
| PERMIT#: 14120591 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| LEVEL 2 ALTERATION |
| ACTION: DENIED |
| |
| 1) LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. REVISE |
| PLAN TO INCLUDE ALL GFI OUTLETS AS REQUIRED IN THE |
| 210.52(C)(1) WALL COUNTERTOP SPACES. |
| |
| 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| 668.001-668.006 |
| FBC, WPB AMENDMENTS 107.2.1 |
| |
| 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH |
| SMOKE ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| REVISE PLANS TO ILLUSTRATE COMPLIANCE WITH THE FBC-R |
| 314 AND 315. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |