Plan Review Notes For Permit 14120585 |
Permit Number |
14120585 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-18 10:04:57 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE ENGINEERING FOR THIS STRUCTURAL REPAIR TO A | | COMMERCIAL (ASSEMBLY OCCUPANCY) BUILDING, FS 471, FBC | | 1609. ENGINEERING TO INCLUDE WIND DESIGN CRITERIA. | | | | THE PLAN PROVIDED SPECIFIES CONNECTORS WHICH ARE | | EMBEDS, BUT THIS IS AN EXISTING BEAM. WIND DESIGN | | CRITERIA NOT INCLUDED, STUCCO DOES NOT HAVE A BOND | | BREAK, STUCCO THICKNESS NOT SPECIFIED. USE OF A | | CONNECTOR IN A MANNER OTHER THAN TESTED/ENGINEERED IS | | TO BE DESIGNED BY A STRUCTURAL ENGINEER. | | | | 2. THERE IS AN EXPIRED PERMIT FOR THIS LOCATION, | | 07080695, PLEASE RESOLVE. | | | | |
|