2015-04-14 12:31:48 | 1) SHT. A-2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE |
| SIZING FOR THE ROOF GUTTERS.TABLE 1106.6 SIZES THE |
| GUTTERS BASED ON THE HORIZONTALLY PROJECTED ROOF AREA, |
| THE RAINFALL RATE ( 5 INCHES PER HOUR ) AND THE SLOPE |
| OF THE GUTTERS. |
| 2) SHT. A7.1 - DETAIL # 4 0 THE TOILET PAPER DISPENSER |
| SHALL BE LOCATED 7 INCHES TO 9 INCHES IN FRONT OF THE |
| WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. 2010 FAC SEC.604.7. |
| 3) SHT.A7.2 - ELEVATIONS #6 & #7 - SHOW THE DISTANCE OF |
| THE SIDE GRAB BAR FROM THE REAR WALL AND THE REAR GRAB |
| BAR FROM THE SIDE WALL. COMPLY WITH 2010 FAC |
| SECS.604.5.1 & 604.5.2. |
| 4) SHT. A7.2 - DETAIL # 1 - SHOW THE FIXTURE CLEARANCE |
| OF THE WATER CLOSET FROM THE SIDE WALL. COMPLY WITH THE |
| 2010 FAC SEC.604.2. |
| 5) I COULD NOT FIND ANY CALCULATIONS FOR COMBUSTION |
| AIR. THE RESPONSE STATES "SEE KEYNOTE #13 BUT THERE IS |
| NO REFERNCED PAGE FOR THIS KEYNOTE TO BE FOUND. |
| CLARIFY.SUBMIT COMBUSTION AIR CALCULATIONS PER THE FUEL |
| GAS CODE SEC. 304. |
| 6) SHT. P2.1 - THE DISHWASHERS SHALL BE INDIRECTLY |
| WASTED TO THE GREASY WASTE SYSTEM IF THEY ARE |
| COMMERCIAL DISHWASHERS.CLARIFY. |
| 7) SUBMIT SPECIFICATIONS/INSTALLATION DOCUMENTS FOR THE |
| KGAVT0601CVT VENT. THE VENT SHALL BE LISTED, LABELED |
| AND TESTED PER THE 2010 FGC SEC.502.1. I AM NOT |
| FAMILIAR WITH THE CONCENTRIC VENT SYSTEM. SUBMIT |
| ADDITIONAL INFORMATION AS TO HOW THE VENT WILL SUPPLY |
| THE REQUIRED COMBUSTION AIR PER SEC. 304 OF THE FGC. |
| 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED PER |
| THE FGC SEC. 301.3. THE RESPONSE STATES "SEE ATTACHED |
| WATER HEATER SPECS.ALL OTHER GAS APPLIANCES TO BE |
| PROVIDED BY ARCHITECT." NO SPECS HAVE BEEN PROVIDED FOR |
| THE WATER HEATER OR ANY OTHER APPLIANCE. CLARIFY. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |