Plan Review Notes
Plan Review Notes For Permit 14120580
Permit Number 14120580
Review Stop P
Sequence Number 2
Notes
Date Text
2015-04-14 12:31:481) SHT. A-2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 SIZING FOR THE ROOF GUTTERS.TABLE 1106.6 SIZES THE
 GUTTERS BASED ON THE HORIZONTALLY PROJECTED ROOF AREA,
 THE RAINFALL RATE ( 5 INCHES PER HOUR ) AND THE SLOPE
 OF THE GUTTERS.
 2) SHT. A7.1 - DETAIL # 4 0 THE TOILET PAPER DISPENSER
 SHALL BE LOCATED 7 INCHES TO 9 INCHES IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. 2010 FAC SEC.604.7.
 3) SHT.A7.2 - ELEVATIONS #6 & #7 - SHOW THE DISTANCE OF
 THE SIDE GRAB BAR FROM THE REAR WALL AND THE REAR GRAB
 BAR FROM THE SIDE WALL. COMPLY WITH 2010 FAC
 SECS.604.5.1 & 604.5.2.
 4) SHT. A7.2 - DETAIL # 1 - SHOW THE FIXTURE CLEARANCE
 OF THE WATER CLOSET FROM THE SIDE WALL. COMPLY WITH THE
 2010 FAC SEC.604.2.
 5) I COULD NOT FIND ANY CALCULATIONS FOR COMBUSTION
 AIR. THE RESPONSE STATES "SEE KEYNOTE #13 BUT THERE IS
 NO REFERNCED PAGE FOR THIS KEYNOTE TO BE FOUND.
 CLARIFY.SUBMIT COMBUSTION AIR CALCULATIONS PER THE FUEL
 GAS CODE SEC. 304.
 6) SHT. P2.1 - THE DISHWASHERS SHALL BE INDIRECTLY
 WASTED TO THE GREASY WASTE SYSTEM IF THEY ARE
 COMMERCIAL DISHWASHERS.CLARIFY.
 7) SUBMIT SPECIFICATIONS/INSTALLATION DOCUMENTS FOR THE
 KGAVT0601CVT VENT. THE VENT SHALL BE LISTED, LABELED
 AND TESTED PER THE 2010 FGC SEC.502.1. I AM NOT
 FAMILIAR WITH THE CONCENTRIC VENT SYSTEM. SUBMIT
 ADDITIONAL INFORMATION AS TO HOW THE VENT WILL SUPPLY
 THE REQUIRED COMBUSTION AIR PER SEC. 304 OF THE FGC.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 APPLIANCES.APPLIANCES SHALL BE LISTED AND LABELED PER
 THE FGC SEC. 301.3. THE RESPONSE STATES "SEE ATTACHED
 WATER HEATER SPECS.ALL OTHER GAS APPLIANCES TO BE
 PROVIDED BY ARCHITECT." NO SPECS HAVE BEEN PROVIDED FOR
 THE WATER HEATER OR ANY OTHER APPLIANCE. CLARIFY.
  