Plan Review Notes
Plan Review Notes For Permit 14120580
Permit Number 14120580
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2015-04-02 11:48:48901 45TH STREET
 PERMIT #14120580
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS) CHAPTER 28 - NEW
 HOTELS & DORMITORIES. FOR NON-SEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING.
  
 SHEET C2: PLAN INDICATES THE DEMOLITION OF THE EXISTING
 FIRE HYDRANT AND FIRE LINE SUPPLYING THE EXISTING
 BUILDING. IS THE EXISTING BUILDING TO BE UNOCCUPIED
 DURING CONSTRUCTION?
  
 SHEET C6: THE NEW FIRE HYDRANT ON THE WEST SIDE OF THE
 PROPERTY NEEDS TO BE RELOCATED TO EAST (APPROX 100
 FEET) AS THIS PAVED DRIVE IS NOT DESIGNED AS A FIRE
 LANE.
  
 SHEET C6: SUPPLYING TWO FIRE HYDRANTS WITH A DEAD-END
 FIRE MAIN IS NOT SUPPORTED.
  
  
  
  
 SHEET LS1.0: EXIT ACCESS CORRIDORS IN THE DORM AREA
 LEAD DIRECTLY TO ONLY 1 EXIT. PER 7.5.1.1.1 FIRE RATED
 EXIT ACCESS CORRIDORS SHALL PROVIDE ACCESS TO TWO EXITS
 BY SEPARATE WAYS OF TRAVEL.
  
  
  
  
 SHEET A1.0: EXISTING KITCHEN #111 IS OPEN TO EXISTING
 FIRE RATED EXIT ACCESS CORRIDOR #200 AND NEW CORRIDOR
 #129.
  
 SHEET A1.3: PATIO AREAS DO NOT APPEAR TO BE EQUIPPED
 WITH EXIT SIGNS, EMERGENCY LIGHTS. PATIO DOORS DO NOT
 APPEAR TO BE ON DOOR SCHEDULE AND MAY REQUIRE PANIC
 HARDWARE FOR EXITING.
  
 SHEET A-6.0: FOR NEW AND EXISTING ASSEMBLY OCCUPANCIES
 WITH AN OCCUPANT LOAD OF 100 OR MORE PERSONS (50
 PERSONS PER THE FLORIDA BUILDING CODE), PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
 PROVIDE A DOOR SCHEDULE FOR THE EXISTING BUILDING AS
 THESE DOORS MAY REQUIRE PANIC/FIRE EXIT HARDWARE DUE TO
 THE INCREASED BUILDING OCCUPANCY.
  
 SHEET E2.1: NO EXIT SIGN ABOVE EXIT DOOR IN DINING
 #157.
  
 SHEET E2.1: DID NOT LOCATE EMERGENCY LIGHTING FOR PATIO
 #139 AND COVERED ENTRY #136.
  
 SHEET FA1.1: NO CARBON MONOXIDE DETECTORS PROVIDED;
 HOWEVER, PLUMBING SHEET P1.1 INDICATES THE USE OF GAS
 FIRED APPLIANCES.
  
 SHEET FA1.1: INDICTE THE LOCATION OF THE EXISTING FACP.
 THIS BUILDING MAY CREATE A NON-CONFORMITY WHEREBY
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 300 PERSONS REQUIRE A VOICE EVACUATION FIRE ALARM
 SYSTEM THROUGHOUT THE BUILDING.
  
 SHEET FA1.1: NO NOTIFICATION APPLIANCE LOCATED IN
 LAUNDRY #159, DINING #122 AND PASSAGE #121. POSSIBLE
 INSUFFICIENT COVERAGE IN DINING #157 AND IN CORRIDORS
 #412 AND #306 BY UTILIZING A WALL MOUNTED APPLIANCE
 WITH THE STROBES LOCATED PERPENDICULAR TO EACHOTHER.
  
 GENERAL: NO CIVIL PLANS (PAVING, WATER, DRAINAGE)
 SUBMITTED. NEW AND EXISTING DEAD-END FIRE DEPARTMENT
 ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL BE
 PROVIDED WITH APPROVED PROVISIONS FOR THE FIRE
 APPARATUS TO TURN AROUND. PER SECTION 18.2.3.4.1.1
 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A
 SURFACE DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING
 AT LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
  
 FIRE PROTECTION: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 GENERAL: IS THE EXISTING FACILITY TO REMAIN OPERATIONAL
 DURING CONSTRUCTION OF THE ADDITION? IF YES, INDICATE
 THE 1-HOUR FIRE BARRIER TO BE INSTALLED TO SEPARATE THE
 CONSTRUCTION FROM THE OCCUPIED BUILDING. PROVIDE
 DRAWING NOTE INDICATING ALL CONSTRUCTION AND DEMOLITION
 WORK SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241.
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN
 DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR
 CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS
 POSTED. WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES
 FOR SMOKING MATERIALS SHALL BE PROVIDED. PROVIDE
 DRAWING NOTE INDICATING, "FIRE PROTECTION SYSTEMS SHALL
 REMAIN ACTIVE DURING DEMOLITION AND RENOVATION
 ACTIVITIES. IN THE EVENT A FIRE PROTECTION SYSTEM IS
 OUT OF SERVICE FOR MORE THAN 4-HOURS IN A 24-HOUR
 PERIOD, THE BUILDING SHALL BE PLACED UNDER A FIRE
 WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED BY
 EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED WHEN
 PLANS ARE RESUBMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730