Plan Review Notes
Plan Review Notes For Permit 14120580
Permit Number 14120580
Review Stop B
Sequence Number 2
Notes
Date Text
2015-03-30 16:04:12BUILDING PLAN REVIEW
 PERMIT: 14120580
 ADD: 901 45TH ST./ QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)589-8880
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 30/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST, PLEASE SEE SURVEY NOTE # 5 THIS SURVEY
 WAS PREPARED FOR DELINEATING THE EXISTING IMPROVEMENTS
 IN THE VICINITY OF THE QUANTUM HOUSE, NOT FOR THE
 DELINEATING THE AH FLOOD ZONE FROM THE B FLOOD ZONE.
 PLEASE PROVIDE A SURVEY FOR THIS LOCATION. THE EXISTING
 STRUCTURE MAY OR MAY NOT BE LOCATED IN A AH FLOOD ZONE
 LOOKING BETWEEN THE FIMA FLOOD MAPS AND THE COUNTY GIS,
 THERE IS SOME DISCREPANCY BETWEEN THE FEMA FLOOD MAP
 PANEL 120192- 0015-B DATED 3/01/79 IS THE CURRENT MAP.
 THE BASE FLOOD ELEVATION SHOWN ON THIS MAP IS 17'-0"
 NGVD.
 IF THE EXISTING BUILDING IS LOCATED IN THE AH FLOOD
 ZONE, THEN SUBSTANTIAL IMPROVEMENT ON THE EXISTING
 BUILDING THAT WILL BE ANOTHER FACTOR, SEE W.P.B.
 MUNI-CODE 94-611 DEFINITION FOR SUBSTANTIAL
 IMPROVEMENT.
  
 2) COMPLIED.
 3) PAGE 002 SHEET LIFE SAFETY 1:
 3A) COMPLIED.
  
 3B) COMPLIED. OCCUPANT LOADS ROUNDED UP
 3C) 2ND REQUEST NO PLANS SUBMITTED. CONSTRUCTION TYPE
 INDICATES: III-B SPRINKLERED, PLEASE SPECIFY COMPLIANCE
 WITH FBC-B 903.3.1.1 NFPA 13 OR 903.3.1.2 NFPA 13R.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 5. FIRE SUPPRESSION
 SYSTEMS SHALL INCLUDE: EARLY WARNING SMOKE EVACUATION
 SYSTEMS, SCHEMATIC FIRE SPRINKLERS.
  
 4)2ND REQUEST. THIS BUILDING QUALIFIES FOR THE RESIDENT
 INSPECTOR PROGRAM WITH AN AREA OF 20,000 SQ. FT. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: (5.)
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT. RESIDENT INSPECTOR FORMS WILL BE E-MAILED OUT TO
 THE CONTRACTOR CONTACT.
  
 4A)FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 4C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4D) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) THE PERMIT APPLICATION INDICATES A TOTAL OF
 2,800,000.00 FOR THE TOTAL PROJECT PLEASE BREAK OUT THE
 VARIOUS PERMIT VALUES FOR ;
 SIGNAGE, LANDSCAPING, SITE WORK, PAVING, IRRIGATION,
 FIRE SPRINKLER, FIRE ALARM LOW VOLTAGE, ALL PERMITS
 THAT WILL NOT BE INCLUDED UNDER THE PRIME PERMIT.
 THE MEP & ROOFING ARE A NO FEE SUB-PERMIT. THIS WAY WE
 CAN FIGURE THE ACTUAL PERMIT FEES FOR THE BUILDING
 PERMIT. W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION.
 RESPONSE: NOTED FOR FUTURE REFERENCE:
  
  
 6) SEMI-COMPLIED. PLEASE PROVIDE WHAT THE MEAN ROOF
 HEIGHT IS FOR THIS PROJECT, NEITHER THE A3.00 SERIES
 NOR SHEET S-5 PROVIDE WHAT THE MEAN ROOF HEIGHT. SHEET
 S-5 THE ROOF PRESSURES ARE LOW FOR A 4:12 PITCH ROOF IN
 A C EXPOSURE. WILL THE ROOF PRESSURES FOR OVER THE
 CLEAR STORY BE ON A SEPARATE PRESSURE CHART? AGAIN
 PROVIDE THE MEAN ROOF HEIGHT FOR THE CLEARSTORY. FBC-B
 1609.6.4.4.1/ TABLE 1609.6.2(2)
  
 6A)SEMI COMPLIED. THE DESIGNER OF RECORD HAS PROVIDED
 TO CHARTS ONE FOR THE MAIN BUILDING MEAN ROOF HEIGHT,
 THE SECOND FOR THE CLEARSTORY. THE CHARTS FOR THE ROOF
 SHOW A 10 SQ. FT. AREA FOR FASTENING, THIS IS CORRECT,
 BUT NEITHER CHART SHOWS OPENINGS GREATER THAN 10 SQ FT
 FOR WINDOWS AND DOORS. CHARTS SHOULD SHOW PRESSURES,
 POSITIVE & NEGATIVE FOR 10, 20, 50, & 100 SQ. FT. VASD.
 FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2)
  
 6B)2ND REQUEST, THE ROOF ZONES 2 & 3 BOTH INDICATE THE
 SAME PRESSURES AS IF THERE WAS A 3 FOOT PARAPET AROUND
 THE PERIMETER ELIMINATING ROOF ZONE # 3 THE ROOF
 SCHEMATIC SHOWS A ROOF ZONE 3 AND A CORNER DISTANCE OF
 6 FT. FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2). UPDATE
 CHARTS.
  
 6C) COMPLIED
  
 7) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 PRODUCT APPROVALS HAVE NOT IDENTIFIED OPENING SIZES,
 TYPE OF GLAZING, MULLIONS, PRESSURES, FASTENERS, NOR
 PRESSURES, CIRCLE TO IDENTIFY FOR REVIEW.
 NOTE: IF EITHER THE DESIGNER OF RECORD OR THE
 CONTRACTOR WOULD PREFER TO SUBMIT THE PRODUCT APPROVALS
 AFTER THE PERMIT ISSUANCE AS A DEFERRED SUBMITTAL
 PLEASE IN YOUR RESPONSE LETTER NOTE AS SUCH. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 8)2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9) COMPLIED. CHANGED LOCATION OF THE RATED WALLS AND
 DOORS LEADING TO THE RESIDENTIAL CORRIDOR.
 10) 2ND REQUEST. PAGE 08 SHEET A1.0, PAGE 10/A1.2 AND
 PAGE 12/ A1.4. IN SPEAKING WITH THE DESIGNER OF RECORD,
 THE 2ND MEANS OF EGRESS FROM THE R1 OCCUPANCIES WAS
 GOING TO BE THROUGH THE DINING ROOM 157. THERE WAS TO
 BE NO KITCHEN IN THIS AREA AND THE EXIT DOOR WAS TO BE
 THE DOOR FROM THE DINING ROOM THAT LEADS TO THE
 EXTERIOR. THE DESIGNER OF RECORD WAS CONSIDERING THIS
 AREA TO BE CONSIDERED A HORIZONTAL EXIT (FBC-B 1025.2)
 WITH A 2 HOUR FIRE BARRIER REQUIRING THE DOUBLE DOORS
 AT EACH END THAT LEADS INTO THE R2 OCCUPANCY TO HAVE 1
 ? HOUR OPENING PROTECTIVE, FBC-B TABLE 715.4.
 11) 2ND REQUEST. RESPONSE INDICATES THEY ARE DOING
 NOTHING WITH THIS SECTION. THIS IS THE PORTION OF THE
 PROJECT WHICH IS A LEVEL II ALTERATION SHOWING WORK IN
 THE EXISTING KITCHEN EXISTING HALL, LAUNDRY AND HOUSE
 KEEPING/ STORAGE. PAGE 11/ A1.3 PARTIAL FLOOR PLANS
 SHOW THE LEVEL II AREA OF ALTERATION. THE 2010 FBC-B
 705.2 EXCEPTION # 2 STATES MEANS OF EGRESS CONFORMING
 TO THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING AND THE FLORIDA FIRE PREVENTION CODE UNDER
 WHICH THE BUILDING WAS CONSTRUCTED SHALL BE CONSIDERED
 COMPLIANT MEANS OF EGRESS IF, IN THE OPINION OF THE
 CODE OFFICIAL, THEY DO NOT CONSTITUTE A DISTINCT HAZARD
 TO LIFE.
 THERE IS NO FIRE BARRIERS BETWEEN THE R1 OCCUPANCY AND
 THE KITCHEN AS WELL AS THE REMAINDER OF THE ORIGINAL
 BUILDING. THE 2010 FBC-B TABLE 1018.1 REQUIRES FIRE
 RATED CORRIDORS AND (2) MEANS OF EGRESS TABLE 1015.1.
 12) COMPLIED. OPENINGS % OF OPENINGS FROM PROPERTY LINE
 13) 2ND REQUEST. THE 500 SERIES WALL SECTIONS SHOW THE
 USE OF ICYNENE SPRAY INSULATION, MINIMUM OF R-19.
 PLEASE PROVIDE COMPLIANCE WITH 2603.4.1.6 PROTECTION
 AGAINST IGNATION. PROVIDE THE MANUFACTURERS TEST REPORT
 AND CIRCLE THE SUB-SYSTEM THE DESIGNER OF RECORD WISHES
 TO USE.
 THERMAL BARRIER REQUIREMENTS 2603.4. ALSO PROVIDE THE
 EVALUATION REPORT FOR THIS PRODUCT WITH INSTALATION
 INSTRUCTIONS, CIRCLE THE SUB-SYSTEM THAT WILL BE USED
 FOR THIS APPLICATION AND THE MAXIMUM AMOUNTS THIS
 INSTALLATION CAN BE APPLIED IN THICKNESS.
  
 14) SHEET SP1.0:
 14A) 2ND REQUEST. THE RESPONSE INDICATES THAT THE PORT
 COCHERE IS FOR DELIVERIES . BY THE DEFINITION OF PORT
 COCHERE . A ROOFED STRUCTURE COVERING A DRIVEWAY AT THE
 ENTRANCE OF A BUILDING TO PROVIDE SHELTER WHILE
 ENTERING OR LEAVING A VEHICLE. A PASSAGEWAY THROUGH A
 BUILDING OR SCREEN WALL DESIGNED TO LET VEHICLES PASS
 FROM THE STREET TO AN INTERIOR COURTYARD.
 THE PORT COCHERE IS A COVERED DROP OFF AREA , IT WILL
 NEED TO MEET THE EQUIVALENT FACILITATION 2010 FBC-B
 EQUIVALENT OR GREATER ACCESSIBILITY AND USABILITY. THE
 LOADING ZONE MUST BE UNDER THE PORTCOCHERE OR SHOW
 EQUIVALENCY. THE PLANS WILL ALSO NEED TO SHOW THE
 LOADING ZONE IN FRONT OF THE PORT COCHERE. THE
 PASSENGER LOADING ZONE NEEDS TO COMPLY WITH BOTH
 SECTIONS OF THE 2010 FL ACCESS. CODE 503.2 VEHICLE
 PULL-UP SPACE AND 503.3 AN ACCESS AISLE.
 14B) 2ND REQUEST. THE VERTICAL DISTANCE REQUIRED FOR
 THE PASSENGER LOADING ZONE IS 114 INCHES MINIMUM 2010
 FL ACCESS. CODE 503.5.
  
 14C)2ND REQUEST. THE RESPONSE STATED THERE WOULD BE NO
 PUBLIC T BUS SERVICE, THAT IS NOT WHAT WAS REQUESTED.
 WILL THERE BE EITHER A BUS OR VAN SERVICE THAT WILL
 SHUTTLE FAMILIES FROM QUANTUM HOUSE TO THE MAIN
 HOSPITAL CAMPUS? 2010 FL ACCESS. CODE 209.2.2 BUS
 LOADING ZONES. IN BUS LOADING ZONES RESTRICTED TO USE
 BY DESIGNATED OR SPECIFIED PUBLIC TRANSPORTATION
 VEHICLES, EACH BUS BAY, BUS STOP, OR OTHER AREA
 DESIGNATED FOR LIFT OR RAMP DEPLOYMENT SHALL COMPLY
 WITH 810.2. BUS BOARDING AND ALIGHTING AREAS.
  
 14D-E)COMPLIED.
 15) COMPLIED
 16A) PROVISO: SHEET A-7.0 LAUNDRY DETAILS DO NOT SHOW
 ANY VENDING MACHINES FOR SOAP POWDER IF OFFERED THE
 MACHINES NEED TO BE AT A ELEVATION IN COMPLIANCE WITH
 REACH RANCGES ACCESS. CODE 308 AND OPERABLE PARTS
 ACCESS.
  
 16B) PROVISO: THE HEIGHT OF THE WASHER AND DRYER ARE TO
 MEET THE REQUIREMENTS OF ACCESS. CODE 611.4 AND
 OPERABLE PARTS, INCLUDING DOORS, LINT SCREENS, AND
 DETERGENT AND BLEACH COMPARTMENTS SHALL COMPLY WITH
 309.
  
 17) COMPLIED
 18) SHEET A7.2 PLEASE SHOW COMPLIANCE WITH FL ACCESS.
 CODE TRANSIENT LODGING GUEST ROOMS:
 18A) 806.2.4 TOILET AND BATHING FACILITIES.
  
 18B)806.3 GUEST ROOMS WITH COMMUNICATION FEATURES.
  
 18C) 2ND REQUEST. GUEST ROOMS REQUIRED TO PROVIDE
 COMMUNICATION FEATURES SHALL COMPLY WITH 806.3.
 IN GUEST ROOMS REQUIRED TO HAVE ACCESSIBLE
 COMMUNICATION FEATURES, CONSIDER ENSURING COMPATIBILITY
 WITH ADAPTIVE EQUIPMENT USED BY PEOPLE WITH HEARING
 IMPAIRMENTS. TO ENSURE COMMUNICATION WITHIN THE
 FACILITY, AS WELL AS ON COMMERCIAL LINES, PROVIDE
 TELEPHONE INTERFACE JACKS THAT ARE COMPATIBLE WITH BOTH
 DIGITAL AND ANALOG SIGNAL USE. IF AN AUDIO HEADPHONE
 JACK IS PROVIDED ON A SPEAKER PHONE, A CUTOFF SWITCH
 CAN BE INCLUDED IN THE JACK SO THAT INSERTION OF THE
 JACK CUTS OFF THE SPEAKER. IF A TELEPHONE-LIKE HANDSET
 IS USED, THE EXTERNAL SPEAKERS CAN BE TURNED OFF WHEN
 THE HANDSET IS REMOVED FROM THE CRADLE. FOR HEADSET OR
 EXTERNAL AMPLIFICATION SYSTEM COMPATIBILITY, A STANDARD
 SUBMINIATURE JACK INSTALLED IN THE TELEPHONE WILL
 PROVIDE THE MOST FLEXIBILITY.
  
 18D-E) COMPLIED
  
 18F)(A) 2ND REQUEST. FL ACC CODE 224.2 GUEST ROOMS WITH
 MOBILITY FEATURES. IN TRANSIENT LODGING FACILITIES,
 GUEST ROOMS WITH MOBILITY FEATURES COMPLYING WITH 806.2
 SHALL BE PROVIDED IN ACCORDANCE WITH TABLE 224.2.
 MINIMUM NUMBER OF REQUIRED ROOMS WITHOUT ROLL-IN
 SHOWERS.
  
 18F)(B) 18F)(A) 2ND REQUEST. FL ACC CODE 224. GUEST
 ROOMS WITH COMMUNICATION FEATURES. IN TRANSIENT LODGING
 FACILITIES, GUEST ROOMS WITH COMMUNICATION FEATURES
 COMPLYING WITH 806.3 SHALL BE PROVIDED IN ACCORDANCE
 WITH TABLE 224.4.
 19) COMPLIED.
 20) PLEASE SHOW COMPLIANCE WITH 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 21) 2ND REQUEST. UL U-419 DOES NOT PROVIDE A STC
 RATING. PLEASE SHOW COMPLIANCE WITH 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 22) COMPLIED. IMPACT FEES.
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved