2014-12-31 14:15:34 | 1) SHT. A2.0 - SUBMIT ROOF DRAINAGE CALCULATIONS. ROOF |
| GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE 2010 |
| FL.PLUMBING CODE. INDICATE THE SLOPE OF THE GUTTERS ON |
| THE PLAN. THE SIZE OF THE VERTICAL CONDUCTORS SHALL |
| COMPLY WITH TABLE 1106.2(1) OR 1106.2(2). |
| 2) SHT.A7.1ELEV.#3 THE BOTTOM OF THE REFLECTING SURFACE |
| OF THE MIRROR SHALL BE A MAX. OF 40 INCHES ABOVE THE |
| FINISH FLOOR PER THE2010 FL. ACCESSIBILITY CODE |
| SEC.603.3. |
| 3) SHT.A7.1 - ELEV.#4 - THE GRAB BARS SHALL BE MEASURED |
| FROM THE FINISH FLOOR TO THE TOP OF THE GRIPPING |
| SURFACE, NOT TO THE CENTERLINE AS SHOWN PER THE FAC |
| SEC.609.4. |
| 4) SHT.A7.1 - ELEV.#4 - THE SEAT HEIGHT SHALL BE 17-19 |
| INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE |
| TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4. |
| 5) SHT.A7.1 - ELEV.# 4 - THE TOILET PAPER DISPENSER |
| SHALL BE LOCATED 7-9 INCHES IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| 6) SHT. A7.2 - DETAIL #1 - THE HEIGHT OF THE ROBE HOOK |
| SHALL COMPLY WITH FAC SEC. 308. THE MAXIMUM HEIGHT |
| SHALL BE 48 INCHES ABOVE THE FINISH FLOOR. |
| 7) SHT. A7.2 - ELEV.#7 - THE SEAT HEIGHT SHALL BE 17-19 |
| INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE |
| TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4. |
| 8) SHT.A7.2 - ELEV.#6 & #7 - SHOW THE DISTANCE OF THE |
| SIDE GRAB BAR FROM THE REAR WALL AND THE REAR GRAB BAR |
| FROM THE SIDE WALL. COMPLY WITH FAC SEC.604.5.1 & |
| 604.5.2. |
| 9) SHT.A7.2 - ELEV.#6 - SHOW THE HEIGHT OF THE LAVATORY |
| ABOVE THE FINISH FLOOR. COMPLY WITH FAC SECS.305 & 606. |
| 10) SHT. A7.2 - ELEV.#1 - SHOW THE FIXTURE CLEARANCE OF |
| THE WATER CLOSET FROM THE SIDE WALL. COMPLY W/ FAC SEC. |
| 604.2. |
| 11) SHT. A7.2 - ELEV.#5 - SHOW THE HEIGHT OF THE SHOWER |
| CONTROLS. COMPLY WITH FAC SEC.608.5.2. |
| 12) SHT.A8.0 - THE THRESHOLD AT THE SHOWER SHALL BE A |
| MAX. OF 1/2/INCH PER THE FAC SEC.608.7. |
| 13) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS |
| APPLIANCES PER THE 2010 FUEL GAS CODE SEC. 304. |
| 14) SUBMIT VENTING DETAILS FOR THE WATER HEATERS. |
| COMPLY WITH FGC SECS.502 & 503. THE PLANS REFER TO THE |
| MECHANICAL DRAWINGS FOR VENTING DETAILS BUT THERE ARE |
| NO DETAILS ON THE MECHANICAL PLANS. |
| 15) SUBMIT MANUFACTURER'S SPECS FOR ALL GAS APPLIANCES. |
| APPLIANCES SHALL BE LISTED AND LABELED PER THE FGC SEC. |
| 301.3. |
| 16) SUBMIT DETAILS FOR THE LINT INTERCEPTORS. COMPLY |
| WITH FL.PLUMBING CODE SEC.1003.6. |
| 17) SHT. P2.1 - THE DISHWASHER AT THE FOOD PREPARATION |
| AREA # 158 SHALL DISCHARGE TO THE GREASY WASTE SYSTEM |
| PER FPC SEC.1003.3.1. |
| 18) SUBMIT A CONDENSATE RISER FOR REVIEW. WPB AMEND. TO |
| 2010 FPC SEC.107.2.1. |
| 19) SUBMIT GREASE TRAP SIZING CALCULATIONS. COMPLY WITH |
| FPC SECS.1003.2, 1003.3.4. |
| 20) SUBMIT DETAILS FOR THE GREASE TRAP. COMPLY WITH FPC |
| SEC.1003.5.2, 1003.5.3. |
| 21) SHT. P2.1 REFERS TO CIVIL DRAWINGS FOR THE |
| CONTINUATION OF THE GREASE AND SANITARY LINES. CIVIL |
| DRAWINGS ARE NOT PART OF THIS SUBMITTAL. CLARIFY. |
| |