Plan Review Notes
Plan Review Notes For Permit 14120580
Permit Number 14120580
Review Stop P
Sequence Number 1
Notes
Date Text
2014-12-31 14:15:341) SHT. A2.0 - SUBMIT ROOF DRAINAGE CALCULATIONS. ROOF
 GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE 2010
 FL.PLUMBING CODE. INDICATE THE SLOPE OF THE GUTTERS ON
 THE PLAN. THE SIZE OF THE VERTICAL CONDUCTORS SHALL
 COMPLY WITH TABLE 1106.2(1) OR 1106.2(2).
 2) SHT.A7.1ELEV.#3 THE BOTTOM OF THE REFLECTING SURFACE
 OF THE MIRROR SHALL BE A MAX. OF 40 INCHES ABOVE THE
 FINISH FLOOR PER THE2010 FL. ACCESSIBILITY CODE
 SEC.603.3.
 3) SHT.A7.1 - ELEV.#4 - THE GRAB BARS SHALL BE MEASURED
 FROM THE FINISH FLOOR TO THE TOP OF THE GRIPPING
 SURFACE, NOT TO THE CENTERLINE AS SHOWN PER THE FAC
 SEC.609.4.
 4) SHT.A7.1 - ELEV.#4 - THE SEAT HEIGHT SHALL BE 17-19
 INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE
 TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4.
 5) SHT.A7.1 - ELEV.# 4 - THE TOILET PAPER DISPENSER
 SHALL BE LOCATED 7-9 INCHES IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 6) SHT. A7.2 - DETAIL #1 - THE HEIGHT OF THE ROBE HOOK
 SHALL COMPLY WITH FAC SEC. 308. THE MAXIMUM HEIGHT
 SHALL BE 48 INCHES ABOVE THE FINISH FLOOR.
 7) SHT. A7.2 - ELEV.#7 - THE SEAT HEIGHT SHALL BE 17-19
 INCHES MAX. ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE SEAT.THE ELEVATION SHOWS THE MEASUREMENT TO THE
 TOP OF THE WATER CLOSET BOWL.FAC SEC.604.4.
 8) SHT.A7.2 - ELEV.#6 & #7 - SHOW THE DISTANCE OF THE
 SIDE GRAB BAR FROM THE REAR WALL AND THE REAR GRAB BAR
 FROM THE SIDE WALL. COMPLY WITH FAC SEC.604.5.1 &
 604.5.2.
 9) SHT.A7.2 - ELEV.#6 - SHOW THE HEIGHT OF THE LAVATORY
 ABOVE THE FINISH FLOOR. COMPLY WITH FAC SECS.305 & 606.
 10) SHT. A7.2 - ELEV.#1 - SHOW THE FIXTURE CLEARANCE OF
 THE WATER CLOSET FROM THE SIDE WALL. COMPLY W/ FAC SEC.
 604.2.
 11) SHT. A7.2 - ELEV.#5 - SHOW THE HEIGHT OF THE SHOWER
 CONTROLS. COMPLY WITH FAC SEC.608.5.2.
 12) SHT.A8.0 - THE THRESHOLD AT THE SHOWER SHALL BE A
 MAX. OF 1/2/INCH PER THE FAC SEC.608.7.
 13) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES PER THE 2010 FUEL GAS CODE SEC. 304.
 14) SUBMIT VENTING DETAILS FOR THE WATER HEATERS.
 COMPLY WITH FGC SECS.502 & 503. THE PLANS REFER TO THE
 MECHANICAL DRAWINGS FOR VENTING DETAILS BUT THERE ARE
 NO DETAILS ON THE MECHANICAL PLANS.
 15) SUBMIT MANUFACTURER'S SPECS FOR ALL GAS APPLIANCES.
 APPLIANCES SHALL BE LISTED AND LABELED PER THE FGC SEC.
 301.3.
 16) SUBMIT DETAILS FOR THE LINT INTERCEPTORS. COMPLY
 WITH FL.PLUMBING CODE SEC.1003.6.
 17) SHT. P2.1 - THE DISHWASHER AT THE FOOD PREPARATION
 AREA # 158 SHALL DISCHARGE TO THE GREASY WASTE SYSTEM
 PER FPC SEC.1003.3.1.
 18) SUBMIT A CONDENSATE RISER FOR REVIEW. WPB AMEND. TO
 2010 FPC SEC.107.2.1.
 19) SUBMIT GREASE TRAP SIZING CALCULATIONS. COMPLY WITH
 FPC SECS.1003.2, 1003.3.4.
 20) SUBMIT DETAILS FOR THE GREASE TRAP. COMPLY WITH FPC
 SEC.1003.5.2, 1003.5.3.
 21) SHT. P2.1 REFERS TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF THE GREASE AND SANITARY LINES. CIVIL
 DRAWINGS ARE NOT PART OF THIS SUBMITTAL. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  