2015-02-02 15:32:05PLAN DENIED
 1) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 CLOTH DRYERS
 AND FIRE DAMPERS PER SECTION 304.1 GENERAL 2010 FBC (M)
 2) REFER TO SECTION 501.2 EXHAUST DISCHARGE AND 501.2.1
 LOCATION OF EXHAUST OUTLETS. 2010 FBC (M)
 3) PROVIDE GRILL SIZE ON ALL FRESH AIR GRILLS 107 FBC
 2010
 4) PROVIDE ALL AIR CONDITIONING EQUIPMENT ON THE
 EQUIPMENT
 SCHEDULE IF NEW AND NOT EXISTING.
 5) SHOW LOCATION OF THE CONDENSERS FOR AIR HANDLERS 1
 THROUGH 4
 ON THE PLANS.
  