2015-01-22 10:26:4114120580
 901 45TH ST.
 ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE SPECIFICATIONS FOR THE LIGHTING POLES AND
 FIXTURES. PROVIDE SIGNED AND SEALED WIND LOADING
 CERTIFICATION FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES
 AND FOUNDATION FROM THE ENGINEER OF RECORD. NEC 110.2,
 FBC 1609.1, ASCE 7-10 ( NOTE: THIS MAY ALSO BE
 ACCOMPLISHED AS PART OF THE SITE LIGHTING PERMIT)
  
 INDICATE THE SIZE OF BRANCH CIRCUITS AND CONDUIT FOR
 THE SITE LIGHTING. NEC 210.3 ( NOTE: THIS MAY ALSO BE
 ACCOMPLISHED AS PART OF THE SITE LIGHTING PERMIT)
  
 PROVIDE A DETAIL OR DESCRIPTION FOR THE RELOCATION AND
 MODIFICATION REQUIRED OF THE EXISTING MDP TO RELOCATE
 THE MAIN BONDING JUMPER TO THE NEW SERVICE DISCONNECT.
 NEC 250.28
  
 PROVIDE A SIGN AT THE NEW MDP INDICATING LOCATION OF
 THE MAIN DISCONNECT. NEC 230.2(E)
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS ON THE ELECTRICAL PLAN. NEC 110.22
  
 PANEL EM OVERCURRENT DEVICE EXCEEDS RATING OF THE
 FEEDER. NEC T 320.16
  
 TWO ADDITIONAL RECEPTACLES THAT ARE READILY ACCESSIBLE
 ARE REQUIRED IN THE TYPICAL UNIT. NEC 210.60(B)
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY, SITE LIGHTING AND DATA SYSTEMS.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  