2015-01-13 17:28:29BUILDING PLAN REVIEW
 PERMIT: 14120580
 ADD: 901 45TH ST./ QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 13/ 2015
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY FOR THIS LOCATION. THE
 EXISTING STRUCTURE MAY OR MAY NOT BE LOCATED IN A AH
 FLOOD ZONE LOOKING BETWEEN THE FIMA FLOOD MAPS AND THE
 COUNTY GIS, THERE IS SOME DISCREPANCY BETWEEN THE TO,
 THE FEMA FLOOD MAP PANEL 120192- 0015-B DATED 3/01/79
 IS THE CURRENT MAP. THE BASE FLOOD ELEVATION SHOWN ON
 THIS MAP IS 17'-0" NGVD.
  
 PLEASE REVIEW SECTION 1612.4 DESIGN AND CONSTRUCTION
 DOCUMENTS IF THE EXISTING BUILDING IS LOCATED WITHIN
 THE AH FLOOD ZONE. ASCE 24 FOR A STRUTURE CATEGORYII
 DFE + 1FT OR DFE, WHICHEVER IS HIGHER.
  
 IF THE EXISTING BUILDING IS LOCATED IN THE AH FLOOD
 ZONE, THEN SUBSTANIAL IMPROVEMENT ON THE EXISTING
 BUILDING THAT WILL BE ANOTHER FACTOR, SEE W.P.B.
 MUNI-CODE 94-611 DEFINITION FOR SUBSTANIAL IMPROVEMENT.
  
 2) PAGE 44 SHEET S-3.1 THE FOUNDATION NOTE # 1.A
 INDICATES THERE IS A SOILS REPORT TO BE PREPARED BY
 ARDAMAN & ASSOCIATES. NO SOILS REPORT WAS INCLUDED IN
 THIS SUBMITTAL. FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE
 THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE
 SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR
 TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL.
  
 3) PAGE 002 SHEET LIFE SAFETY 1:
 3A) UNDER THE CLASSIFICATION OF WORK THE PLANS INDICATE
 A LEVEL II ALTERATION THE PERMIT APPLICATION SCOPE OF
 WORK UNDER THIS PERMIT LIST THE CONSTRUCTION OF A
 20,000 SQ. FT. ADDITION, THERE APPEARS TO BE A
 DISCREPANCY IN THE SCOPE OF WORK TO TAKE PLACE UNDER
 THIS PERMIT? IS THE EXISTING BUILDING TO HAVE A LEVEL
 II ALTERATION? 107.2.1.3 DISCREPANCY, ADDITIONAL
 INFORMATION REQUIRED. FOR THIS REVIEW WE ARE GOING TO
 REVIEW TO A 20,000 SQ. FT. ADDITION AND A LEVEL II
 ALTERATION TO THE EXISTING STRUCTURE.
  
 3B) OCCUPANT LOADS INTHE GROUP HEADINGS OF A2 & STORAGE
 OCCUPANCIES THE OCCUPANT LOAD WAS ROUNDED DOWN AND NOT
 TO THE NEXT FULL OCCUPANT, OCCUPANT LOADS ARE ALWAYS
 ROUNDED UP, NO PARTS OF OCCUPANT. FBC-B 1004.1. AND SEE
 BOAF INFORMAL INTERPRETATION # 5479. UPDATTE OCCUPANT
 LOADS.
  
 3C) CONSTRUCTION TYPE INDICATES: III-B SPRINKLERED,
 PLEASE SPECIFY COMPLIANCE WITH FBC-B 903.3.1.1 NFPA 13
 OR 903.3.1.2 NFPA 13R.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 5. FIRE SUPPRESSION
 SYSTEMS SHALL INCLUDE: EARLY WARNING SMOKE EVACUATION
 SYSTEMS, SCHEMATIC FIRE SPRINKLERS.
  
 4) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR
 PROGRAM WITH AN AREA OF 20,000 SQ. FT. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES.
 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY
 OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE
 MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES: (5.) FOR BUILDINGS
 WITH AREA GREATER THAN 20,000 SQUARE FOOT. RESIDENT
 INSPECTOR FORMS WILL BE E-MAILED OUT TO THE CONTRACTOR
 CONTACT.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 NOTE: WHEN THE PERMIT IS ISSUED, AND THE PROJECT DOX
 LIBRARIAN E-MAILS YOU THAT YOU CAN DOWNLOAD YOUR
 APPROVED PLANS FOR PRINTING, THE CITY WILL REQUIRE 2
 COLOR SETS OF PLANS, ONE FOR THE RESIDENT INSECTOR, THE
 OTHER FOR THE CITY MEP INSPECTORS.
  
 NOTE: EVEN WITH AN ONSITE RESIDNET INSPECTOR, THE
 CONTRACTOR IS STILL REQUIRED TO CALL IN THE STRUCTURAL
 INSPECTIONS FOR AUDITING PURPOSES, PLUS NO ACTIVITY
 WILL EXPIRE THE PERMIT WITH NO ACTIVITY.
  
 5) THE PERMIT APPLICATION INDICATES A TOTAL OF
 2,800,000.00 FOR THE TOTAL PROJECT PLEASE BREAK OUT THE
 VARIOUS PERMIT VALUES FOR ;
 SIGNAGE, LANDSCAPING, SITE WORK, PAVING, IRRIGATION,
 FIRE SPRINKLER, FIRE ALARM LOW VOLTAGE, ALL PERMITS
 THAT WILL NOT BE INCLUDED UNDER THE PRIME PERMIT.
 THE MEP & ROOFING ARE A NO FEE SUB-PERMIT. THIS WAY WE
 CAN FIGURE THE ACTUAL PERMIT FEES FOR THE BUILDING
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION.
  
 6) PLEASE PROVIDE WHAT THE MEAN ROOF HEIGHT IS FOR THIS
 PROJECT, NEITHER THE A3.00 SERIES NOR SHEET S-5 PROVIDE
 WHAT THE MEAN ROOF HEIGHT. SHEET S-5 THE ROOF PRESSURES
 ARE LOW FOR A 4:12 PITCH ROOF IN A C EXPOSURE. WILL THE
 ROOF PRESSURES FOR OVER THE CLEAR STORY BE ON A
 SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN ROOF
 HEIGHT FOR THE CLEARSSTORY. FBC-B 1609.6.4.4.1/ TABLE
 1609.6.2(2)
  
 6A) WILL THE ROOF PRESSURES FOR OVER THE CLEAR STORY BE
 ON A SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN
 ROOF HEIGHT FOR THE CLEARSTORY. FBC-B 1609.6.4.4.1/
 TABLE 1609.6.2(2)
  
 6B) THE ROOF ZONES 2 & 3 BOTH INDICATE THE SAME
 PRESSURES AS IF THERE WAS A 3 FOOT PARAPET AROUND THE
 PERMITER ELIMENATING ROOF ZONE # 3 THE ROOF SCHEMATIC
 SHOWS A ROOF ZONE 3 AND A CORNER DISTANCE OF 6 FT.
 FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2)
  
 6C) THE ROOF OVER HANG ZONES HAVE NOT BEEN SHOWN ON
 SHEET S-5 EITHER. FBC-B 1609.6.4.4.1/ TABLE
 1609.6.2(2).
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 NOTE: IF EITHER THE DESIGNER OF RECORD OR THE
 CONTRACTOR WOULD PREFER TO SUBMIT THE PRODUCT APPROVALS
 AFTER THE PERMIT ISSUANCE AS A DEFERRED SUBMITTAL
 PLEASE IN YOUR RESPONSE LETTER NOTE AS SUCH. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE
 DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL
 THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY
 THE BUILDING OFFICIAL.
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) PAGE 12 SHEET A1.4 PARTIAL NORTH, DOOR 153, 154 &
 159 ARE WITHIN A 1 HOUR FIRE RATED CORRIDOOR TABLE
 1018.1/ TABLE 715.4.ALSO SEE PAGE 31 SHEET A6.0 DOOR
 SCHEDULE NO FIRE RATING.
  
 10) PAGE 08 SHEET A1.0 INDICATE THE 1 HOUR FIRE RATED
 CORRIDORS IN THE R1 OCCUPANCY, CORRIDORS 308 & 412.
 THIS PLAN DOES NOT SHOW HOW THE 1 HOUR FIRE RATED
 CORRIDORS SHALL BE CONTINUOUS TO AN EXIT. SEE FBC-B
 1018.6 CORRIDOR CONTINUITY, THE EXCEPTION ALLOWS FOR
 FOYERS, LOBBIES OR RECEPTION ROOMS TO BE CONSTRUCTED AS
 CORRIDORS. THE PROBLEM IS IN THE CORIDOR 308 & 412
 DUMPING INTO ANOTHER OCCUAPNCY (A2 OR B) THAT DOES NOT
 REQUIRE A RATED CORRIDOR FOR A SPRINKLERED BUILDING.
  
 11) A SIMILAR SITUATION OCCURS ON THE SOUTH GUEST WING
 WHERE THE R1 OCCUPANCY RUNS INTO A BUSINESS OCCUPANCY
 AND INTO THE EXISTING KITCHEN WHICH IS HIGHLIGHTED AS
 WORK TO BE ACCCOMPLISHED UNDER THIS PERMIT.
  
 12) PLEASE PROVIDE THE DISTANCE FROM THE DINING ROOM
 157 WALL TO THE PROPERTY LINE, IT APPEARS TO BE RIGHT
 AT 20 FT. IF UNDER 20 FT. SEE FBC-B TABLE 705.8
 PROVIDE CALCULATIONS FOR ALLOWABLE WALL AREA.
 UNPROTECTED, SPRINKLRED, 75 %.
  
 13) THE 500 SERIES WALL SECTIONS SHOW THE USE OF
 ICYNENE SPRAY INSULATION, MINIMUM OF R-19. PLEASE
 PROVIDE COMPLIANCE WITH 2603.4.1.6 PROTECTION AGAINST
 IGNITION. THERMAL BARRIER REQUIREMENTS 2603.4. ALSO
 PROVIDE THE EVALUATION REPORT FOR THIS PRODUCT WITH
 INSTALATION INSTRUCTIONS, CIRCLE THE SUB-SYSTEM THAT
 WILL BE USED FOR THIS APPLICATIONAND THE MAXIMUM
 AMOUNTS THIS INSTALATION CAN BE APPLIED IN THICKNESS.
  
 14) SHEET SP1.0:
 14A) THE PORT COCHERE IS A COVERED DROP OFF AREA BUT
 THE PLANS ALSO SHOW THE LOADING ZONE INFRONT OF THE
 PORT COCHERE. THE PASSENGER LOADING ZONE NEEDS TO
 COMPLY WITH BOTH SECTIONS OF THE 2010 FL ACCESS. CODE
 503.2 VEHICLE PULL-UP SPACE AND 503.3 AN ACCESS AISLE.
 THESE ELEMENTS SHOULD BE UNDER THE PORT COCHERE TO MEET
 EQUIVALENT FACILITATION 103.
  
 14B) THE VERTICAL DISTANCE REQUIRED FOR THE PASSENGER
 LOADING ZONE IS 114 INCHES MINIMUM 2010 FL ACCESS. CODE
 503.5.
  
 14C) WILL THERE BE EITHER A BUS OR VAN SERVICE THAT
 WILL SHUTTLE FAMILIES FROM QUANTUM HOUSE TO THE MAIN
 HOSPITAL CAMPUS? 2010 FL ACCESS. CODE
 209.2.2 BUS LOADING ZONES. IN BUS LOADING ZONES
 RESTRICTED TO USE BY DESIGNATED OR SPECIFIED PUBLIC
 TRANSPORTATION VEHICLES, EACH BUS BAY, BUS STOP, OR
 OTHER AREA DESIGNATED FOR LIFT OR RAMP DEPLOYMENT SHALL
 COMPLY WITH 810.2. BUS BOARDING AND ALIGHTING AREAS.
  
 14D) THE SITE PLAN SHOWS (2) AREAS WHERE THE 4'-0" WIDE
 WALK PATH (THE NORTH & EAST) EXCEED THE 200 FT. WITHOUT
 A PASSING ZONE, SEE 2010 FL ACCESS. CODE 403.5.3.
  
 14E) FUTURE GAZEBO NOT PART OF THIS PREMIT.
  
 15) THE PORT COCHERE SHOWS INSULATION AT THE ROOF LEVEL
 BUT NOT UNDER THE CEILING OF THE PORT COCHERE, NOR AT
 THE BUILDING LINE AS SHOWN AT THE BACK OF THE BUILDING
 SEE DETAIL3 SHEET A-5.0. NOTE DETAIL 3 SHEET A-5.0
 SHOWS THE USE OF ICYNENE SPRAY INSULATION IN THE
 VERTICAL WALL APPLICATION. PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATION FOR THIS PRODUCT AND
 LIMITATIONS OF USE IN THE VERTICAL PLANE. FBC-B
 2603.1.AND SCOPE 2601. THESE PROVISIONS SHALL GOVERN
 THE MATERIAL, DESIGN AND APPLICATION OF THE FOAM
 PLASTIC INSULATION.
  
 16A) SHEET A-7.0 LAUNDRY DETAILS DO NOT SHOW ANY
 VENDING MACHINES FOR SOAP POWDER IF OFFERED THE
 MACHINES NEED TO BE AT A ELEVATION IN COMPLIANCE WITH
 REACH RANCGES ACCESS. CODE 308 AND OPERABLE PARTS
 ACCESS.
  
 16B) THE HEIGHT OF THE WASHER AND DRYER ARE TO MEET THE
 REQUIREMENTS OF ACCESS. CODE 611.4 AND OPERABLE PARTS,
 INCLUDING DOORS, LINT SCREENS, AND DETERGENT AND BLEACH
 COMPARTMENTS SHALL COMPLY WITH 309.
  
 17) SHEET A7.3 FOOD PREPERATION DETAIL # 1 158 SHOWS A
 48 INCH ISLAND COUNTER TOP SHOWS A DETAIL 5/A7.2 FOR
 THE ELEVATION AND HEIGHT OF THIS UNIT. THAT DETAIL IS
 OF A BATH AT GUEST ROOM. DISCREPANCY IN
 PLANS.107.2.1.3.
  
 18) SHEET A7.2 PLEASE SHOW COMPLIANCE WITH FL ACCESS.
 CODE TRANSIENT LODGING GUEST ROOMS:
 18A) 806.2.4 TOILET AND BATHING FACILITIES.
  
 18B)806.3 GUEST ROOMS WITH COMMUNICATION FEATURES.
  
 18C) GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION
 FEATURES SHALL COMPLY WITH 806.3.
  
 18D) 806.3.1 ALARMS.
  
 18E) 806.3.2 NOTIFICATION DEVICES.
  
 18F) 224.2 GUEST ROOMS WITH MOBILITY FEATURES. IN
 TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2 SHALL BE PROVIDED IN
 ACCORDANCE WITH TABLE 224.2.
  
 19) SHEET ID-2 AND ID-3 SHOWS THE USE OF CARPET IN THE
 R-1 UNITS AND CORIDORS OF THE R-1 UNITS. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 804.4.1 MINIMUM CRITICAL
 REDIANT FLUX. SEE EXCEPTION FOR SPRINKLERED BUILDINGS.
  
 20) PLEASE SHOW COMPLIANCE WITH 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 21) PLEASE SHOW COMPLIANCE WITH 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  