2015-01-13 17:28:29 | BUILDING PLAN REVIEW |
| PERMIT: 14120580 |
| ADD: 901 45TH ST./ QUANTUM HOUSE |
| CONT: HEDRICK BROTHERS |
| TEL: ( |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JAN. 13/ 2015 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A SURVEY FOR THIS LOCATION. THE |
| EXISTING STRUCTURE MAY OR MAY NOT BE LOCATED IN A AH |
| FLOOD ZONE LOOKING BETWEEN THE FIMA FLOOD MAPS AND THE |
| COUNTY GIS, THERE IS SOME DISCREPANCY BETWEEN THE TO, |
| THE FEMA FLOOD MAP PANEL 120192- 0015-B DATED 3/01/79 |
| IS THE CURRENT MAP. THE BASE FLOOD ELEVATION SHOWN ON |
| THIS MAP IS 17'-0" NGVD. |
| |
| PLEASE REVIEW SECTION 1612.4 DESIGN AND CONSTRUCTION |
| DOCUMENTS IF THE EXISTING BUILDING IS LOCATED WITHIN |
| THE AH FLOOD ZONE. ASCE 24 FOR A STRUTURE CATEGORYII |
| DFE + 1FT OR DFE, WHICHEVER IS HIGHER. |
| |
| IF THE EXISTING BUILDING IS LOCATED IN THE AH FLOOD |
| ZONE, THEN SUBSTANIAL IMPROVEMENT ON THE EXISTING |
| BUILDING THAT WILL BE ANOTHER FACTOR, SEE W.P.B. |
| MUNI-CODE 94-611 DEFINITION FOR SUBSTANIAL IMPROVEMENT. |
| |
| 2) PAGE 44 SHEET S-3.1 THE FOUNDATION NOTE # 1.A |
| INDICATES THERE IS A SOILS REPORT TO BE PREPARED BY |
| ARDAMAN & ASSOCIATES. NO SOILS REPORT WAS INCLUDED IN |
| THIS SUBMITTAL. FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE |
| THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE |
| SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR |
| TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL. |
| |
| 3) PAGE 002 SHEET LIFE SAFETY 1: |
| 3A) UNDER THE CLASSIFICATION OF WORK THE PLANS INDICATE |
| A LEVEL II ALTERATION THE PERMIT APPLICATION SCOPE OF |
| WORK UNDER THIS PERMIT LIST THE CONSTRUCTION OF A |
| 20,000 SQ. FT. ADDITION, THERE APPEARS TO BE A |
| DISCREPANCY IN THE SCOPE OF WORK TO TAKE PLACE UNDER |
| THIS PERMIT? IS THE EXISTING BUILDING TO HAVE A LEVEL |
| II ALTERATION? 107.2.1.3 DISCREPANCY, ADDITIONAL |
| INFORMATION REQUIRED. FOR THIS REVIEW WE ARE GOING TO |
| REVIEW TO A 20,000 SQ. FT. ADDITION AND A LEVEL II |
| ALTERATION TO THE EXISTING STRUCTURE. |
| |
| 3B) OCCUPANT LOADS INTHE GROUP HEADINGS OF A2 & STORAGE |
| OCCUPANCIES THE OCCUPANT LOAD WAS ROUNDED DOWN AND NOT |
| TO THE NEXT FULL OCCUPANT, OCCUPANT LOADS ARE ALWAYS |
| ROUNDED UP, NO PARTS OF OCCUPANT. FBC-B 1004.1. AND SEE |
| BOAF INFORMAL INTERPRETATION # 5479. UPDATTE OCCUPANT |
| LOADS. |
| |
| 3C) CONSTRUCTION TYPE INDICATES: III-B SPRINKLERED, |
| PLEASE SPECIFY COMPLIANCE WITH FBC-B 903.3.1.1 NFPA 13 |
| OR 903.3.1.2 NFPA 13R. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: 5. FIRE SUPPRESSION |
| SYSTEMS SHALL INCLUDE: EARLY WARNING SMOKE EVACUATION |
| SYSTEMS, SCHEMATIC FIRE SPRINKLERS. |
| |
| 4) THIS BUILDING QUALIFIES FOR THE RESIDENT INSPECTOR |
| PROGRAM WITH AN AREA OF 20,000 SQ. FT. 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. |
| THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| SERVICE IN THE FOLLOWING INSTANCES: (5.) FOR BUILDINGS |
| WITH AREA GREATER THAN 20,000 SQUARE FOOT. RESIDENT |
| INSPECTOR FORMS WILL BE E-MAILED OUT TO THE CONTRACTOR |
| CONTACT. |
| |
| SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| |
| NOTE: WHEN THE PERMIT IS ISSUED, AND THE PROJECT DOX |
| LIBRARIAN E-MAILS YOU THAT YOU CAN DOWNLOAD YOUR |
| APPROVED PLANS FOR PRINTING, THE CITY WILL REQUIRE 2 |
| COLOR SETS OF PLANS, ONE FOR THE RESIDENT INSECTOR, THE |
| OTHER FOR THE CITY MEP INSPECTORS. |
| |
| NOTE: EVEN WITH AN ONSITE RESIDNET INSPECTOR, THE |
| CONTRACTOR IS STILL REQUIRED TO CALL IN THE STRUCTURAL |
| INSPECTIONS FOR AUDITING PURPOSES, PLUS NO ACTIVITY |
| WILL EXPIRE THE PERMIT WITH NO ACTIVITY. |
| |
| 5) THE PERMIT APPLICATION INDICATES A TOTAL OF |
| 2,800,000.00 FOR THE TOTAL PROJECT PLEASE BREAK OUT THE |
| VARIOUS PERMIT VALUES FOR ; |
| SIGNAGE, LANDSCAPING, SITE WORK, PAVING, IRRIGATION, |
| FIRE SPRINKLER, FIRE ALARM LOW VOLTAGE, ALL PERMITS |
| THAT WILL NOT BE INCLUDED UNDER THE PRIME PERMIT. |
| THE MEP & ROOFING ARE A NO FEE SUB-PERMIT. THIS WAY WE |
| CAN FIGURE THE ACTUAL PERMIT FEES FOR THE BUILDING |
| PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF |
| PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| 108.3* BUILDING PERMIT VALUATION. |
| |
| 6) PLEASE PROVIDE WHAT THE MEAN ROOF HEIGHT IS FOR THIS |
| PROJECT, NEITHER THE A3.00 SERIES NOR SHEET S-5 PROVIDE |
| WHAT THE MEAN ROOF HEIGHT. SHEET S-5 THE ROOF PRESSURES |
| ARE LOW FOR A 4:12 PITCH ROOF IN A C EXPOSURE. WILL THE |
| ROOF PRESSURES FOR OVER THE CLEAR STORY BE ON A |
| SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN ROOF |
| HEIGHT FOR THE CLEARSSTORY. FBC-B 1609.6.4.4.1/ TABLE |
| 1609.6.2(2) |
| |
| 6A) WILL THE ROOF PRESSURES FOR OVER THE CLEAR STORY BE |
| ON A SEPARATE PRESSURE CHART? AGAIN PROVIDE THE MEAN |
| ROOF HEIGHT FOR THE CLEARSTORY. FBC-B 1609.6.4.4.1/ |
| TABLE 1609.6.2(2) |
| |
| 6B) THE ROOF ZONES 2 & 3 BOTH INDICATE THE SAME |
| PRESSURES AS IF THERE WAS A 3 FOOT PARAPET AROUND THE |
| PERMITER ELIMENATING ROOF ZONE # 3 THE ROOF SCHEMATIC |
| SHOWS A ROOF ZONE 3 AND A CORNER DISTANCE OF 6 FT. |
| FBC-B 1609.6.4.4.1/ TABLE 1609.6.2(2) |
| |
| 6C) THE ROOF OVER HANG ZONES HAVE NOT BEEN SHOWN ON |
| SHEET S-5 EITHER. FBC-B 1609.6.4.4.1/ TABLE |
| 1609.6.2(2). |
| |
| 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| NOTE: IF EITHER THE DESIGNER OF RECORD OR THE |
| CONTRACTOR WOULD PREFER TO SUBMIT THE PRODUCT APPROVALS |
| AFTER THE PERMIT ISSUANCE AS A DEFERRED SUBMITTAL |
| PLEASE IN YOUR RESPONSE LETTER NOTE AS SUCH. 107.3.4.2 |
| DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE |
| DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL |
| THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY |
| THE BUILDING OFFICIAL. |
| |
| 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) PAGE 12 SHEET A1.4 PARTIAL NORTH, DOOR 153, 154 & |
| 159 ARE WITHIN A 1 HOUR FIRE RATED CORRIDOOR TABLE |
| 1018.1/ TABLE 715.4.ALSO SEE PAGE 31 SHEET A6.0 DOOR |
| SCHEDULE NO FIRE RATING. |
| |
| 10) PAGE 08 SHEET A1.0 INDICATE THE 1 HOUR FIRE RATED |
| CORRIDORS IN THE R1 OCCUPANCY, CORRIDORS 308 & 412. |
| THIS PLAN DOES NOT SHOW HOW THE 1 HOUR FIRE RATED |
| CORRIDORS SHALL BE CONTINUOUS TO AN EXIT. SEE FBC-B |
| 1018.6 CORRIDOR CONTINUITY, THE EXCEPTION ALLOWS FOR |
| FOYERS, LOBBIES OR RECEPTION ROOMS TO BE CONSTRUCTED AS |
| CORRIDORS. THE PROBLEM IS IN THE CORIDOR 308 & 412 |
| DUMPING INTO ANOTHER OCCUAPNCY (A2 OR B) THAT DOES NOT |
| REQUIRE A RATED CORRIDOR FOR A SPRINKLERED BUILDING. |
| |
| 11) A SIMILAR SITUATION OCCURS ON THE SOUTH GUEST WING |
| WHERE THE R1 OCCUPANCY RUNS INTO A BUSINESS OCCUPANCY |
| AND INTO THE EXISTING KITCHEN WHICH IS HIGHLIGHTED AS |
| WORK TO BE ACCCOMPLISHED UNDER THIS PERMIT. |
| |
| 12) PLEASE PROVIDE THE DISTANCE FROM THE DINING ROOM |
| 157 WALL TO THE PROPERTY LINE, IT APPEARS TO BE RIGHT |
| AT 20 FT. IF UNDER 20 FT. SEE FBC-B TABLE 705.8 |
| PROVIDE CALCULATIONS FOR ALLOWABLE WALL AREA. |
| UNPROTECTED, SPRINKLRED, 75 %. |
| |
| 13) THE 500 SERIES WALL SECTIONS SHOW THE USE OF |
| ICYNENE SPRAY INSULATION, MINIMUM OF R-19. PLEASE |
| PROVIDE COMPLIANCE WITH 2603.4.1.6 PROTECTION AGAINST |
| IGNITION. THERMAL BARRIER REQUIREMENTS 2603.4. ALSO |
| PROVIDE THE EVALUATION REPORT FOR THIS PRODUCT WITH |
| INSTALATION INSTRUCTIONS, CIRCLE THE SUB-SYSTEM THAT |
| WILL BE USED FOR THIS APPLICATIONAND THE MAXIMUM |
| AMOUNTS THIS INSTALATION CAN BE APPLIED IN THICKNESS. |
| |
| 14) SHEET SP1.0: |
| 14A) THE PORT COCHERE IS A COVERED DROP OFF AREA BUT |
| THE PLANS ALSO SHOW THE LOADING ZONE INFRONT OF THE |
| PORT COCHERE. THE PASSENGER LOADING ZONE NEEDS TO |
| COMPLY WITH BOTH SECTIONS OF THE 2010 FL ACCESS. CODE |
| 503.2 VEHICLE PULL-UP SPACE AND 503.3 AN ACCESS AISLE. |
| THESE ELEMENTS SHOULD BE UNDER THE PORT COCHERE TO MEET |
| EQUIVALENT FACILITATION 103. |
| |
| 14B) THE VERTICAL DISTANCE REQUIRED FOR THE PASSENGER |
| LOADING ZONE IS 114 INCHES MINIMUM 2010 FL ACCESS. CODE |
| 503.5. |
| |
| 14C) WILL THERE BE EITHER A BUS OR VAN SERVICE THAT |
| WILL SHUTTLE FAMILIES FROM QUANTUM HOUSE TO THE MAIN |
| HOSPITAL CAMPUS? 2010 FL ACCESS. CODE |
| 209.2.2 BUS LOADING ZONES. IN BUS LOADING ZONES |
| RESTRICTED TO USE BY DESIGNATED OR SPECIFIED PUBLIC |
| TRANSPORTATION VEHICLES, EACH BUS BAY, BUS STOP, OR |
| OTHER AREA DESIGNATED FOR LIFT OR RAMP DEPLOYMENT SHALL |
| COMPLY WITH 810.2. BUS BOARDING AND ALIGHTING AREAS. |
| |
| 14D) THE SITE PLAN SHOWS (2) AREAS WHERE THE 4'-0" WIDE |
| WALK PATH (THE NORTH & EAST) EXCEED THE 200 FT. WITHOUT |
| A PASSING ZONE, SEE 2010 FL ACCESS. CODE 403.5.3. |
| |
| 14E) FUTURE GAZEBO NOT PART OF THIS PREMIT. |
| |
| 15) THE PORT COCHERE SHOWS INSULATION AT THE ROOF LEVEL |
| BUT NOT UNDER THE CEILING OF THE PORT COCHERE, NOR AT |
| THE BUILDING LINE AS SHOWN AT THE BACK OF THE BUILDING |
| SEE DETAIL3 SHEET A-5.0. NOTE DETAIL 3 SHEET A-5.0 |
| SHOWS THE USE OF ICYNENE SPRAY INSULATION IN THE |
| VERTICAL WALL APPLICATION. PLEASE PROVIDE THE |
| MANUFACTURERS SPECIFICATION FOR THIS PRODUCT AND |
| LIMITATIONS OF USE IN THE VERTICAL PLANE. FBC-B |
| 2603.1.AND SCOPE 2601. THESE PROVISIONS SHALL GOVERN |
| THE MATERIAL, DESIGN AND APPLICATION OF THE FOAM |
| PLASTIC INSULATION. |
| |
| 16A) SHEET A-7.0 LAUNDRY DETAILS DO NOT SHOW ANY |
| VENDING MACHINES FOR SOAP POWDER IF OFFERED THE |
| MACHINES NEED TO BE AT A ELEVATION IN COMPLIANCE WITH |
| REACH RANCGES ACCESS. CODE 308 AND OPERABLE PARTS |
| ACCESS. |
| |
| 16B) THE HEIGHT OF THE WASHER AND DRYER ARE TO MEET THE |
| REQUIREMENTS OF ACCESS. CODE 611.4 AND OPERABLE PARTS, |
| INCLUDING DOORS, LINT SCREENS, AND DETERGENT AND BLEACH |
| COMPARTMENTS SHALL COMPLY WITH 309. |
| |
| 17) SHEET A7.3 FOOD PREPERATION DETAIL # 1 158 SHOWS A |
| 48 INCH ISLAND COUNTER TOP SHOWS A DETAIL 5/A7.2 FOR |
| THE ELEVATION AND HEIGHT OF THIS UNIT. THAT DETAIL IS |
| OF A BATH AT GUEST ROOM. DISCREPANCY IN |
| PLANS.107.2.1.3. |
| |
| 18) SHEET A7.2 PLEASE SHOW COMPLIANCE WITH FL ACCESS. |
| CODE TRANSIENT LODGING GUEST ROOMS: |
| 18A) 806.2.4 TOILET AND BATHING FACILITIES. |
| |
| 18B)806.3 GUEST ROOMS WITH COMMUNICATION FEATURES. |
| |
| 18C) GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION |
| FEATURES SHALL COMPLY WITH 806.3. |
| |
| 18D) 806.3.1 ALARMS. |
| |
| 18E) 806.3.2 NOTIFICATION DEVICES. |
| |
| 18F) 224.2 GUEST ROOMS WITH MOBILITY FEATURES. IN |
| TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH MOBILITY |
| FEATURES COMPLYING WITH 806.2 SHALL BE PROVIDED IN |
| ACCORDANCE WITH TABLE 224.2. |
| |
| 19) SHEET ID-2 AND ID-3 SHOWS THE USE OF CARPET IN THE |
| R-1 UNITS AND CORIDORS OF THE R-1 UNITS. PLEASE PROVIDE |
| COMPLIANCE WITH 2010 FBC-B 804.4.1 MINIMUM CRITICAL |
| REDIANT FLUX. SEE EXCEPTION FOR SPRINKLERED BUILDINGS. |
| |
| 20) PLEASE SHOW COMPLIANCE WITH 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 21) PLEASE SHOW COMPLIANCE WITH 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |