Plan Review Notes For Permit 14120559
Permit Number 14120559
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-12-17 16:50:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTAL DID NOT INLUDED ELECTRICAL POWER WIRES
 AND OR BACK-UP POWER.
  
 THESUBMITTAL INDICATES THAT THE INSTALATION WIL BE
 ABOVE THE CEILING TILE. THE SPEC SHEETS INDICATES THAT
 IT SHALL BE INSTALLED IN THE SAME ROOM WITHIN 20FT OF
 THE PANEL. THE EILING IS ASEPARATEPACE OR ROOM AND AN
 INTALLATION IN THIS SPACE IS REJECTE. PLEASE MOVE THE
 INSTALLATION INTO THESAME ROOM OR PROVIDE JUSTIFICATION
 THAT THE SPACE ABOVE THE CEILING QUALIFIES AS THE SAME
 ROOM.