Plan Review Notes For Permit 14120559 |
Permit Number |
14120559 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-17 16:50:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE SUBMITTAL DID NOT INLUDED ELECTRICAL POWER WIRES | | AND OR BACK-UP POWER. | | | | THESUBMITTAL INDICATES THAT THE INSTALATION WIL BE | | ABOVE THE CEILING TILE. THE SPEC SHEETS INDICATES THAT | | IT SHALL BE INSTALLED IN THE SAME ROOM WITHIN 20FT OF | | THE PANEL. THE EILING IS ASEPARATEPACE OR ROOM AND AN | | INTALLATION IN THIS SPACE IS REJECTE. PLEASE MOVE THE | | INSTALLATION INTO THESAME ROOM OR PROVIDE JUSTIFICATION | | THAT THE SPACE ABOVE THE CEILING QUALIFIES AS THE SAME | | ROOM. |
|