Plan Review Notes
Plan Review Notes For Permit 14120532
Permit Number 14120532
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-02 12:34:581. SHOW LOCATION OF PANELS A & B AND IDENTIFY ON PLANS.
 BRANCH CIRCUITS IN AREA BEING SERVED ORIGINATE IN BOTH
 PANELBOARDS.
 2. N.E.C. 700.12(F) SHOW LOCATION OF ALL EMERGENCY
 LIGHTS NEEDED FOR 1 FT. CANDLE FOR EGRESS.
 3. N.E.C. 210.63. LOCATION OF RECEPTACLE OUTLET WITHIN
 25 FEET OF AIR CONDITIONING EQUIPMENT AND GFCI
 PROTECTED PER N.E.C. 210.8(B).