Plan Review Notes For Permit 14120516 |
Permit Number |
14120516 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-27 12:17:04 | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | FIXED WINDOWS FL15349.15 ARE FOR A TRIPLE FIXED GLASS | | WINDOW WITH DESIGN PRESSURES OF +55 / -55 PSF. THE | | FIXED GLASS WINDOWS ON THE PLANS ARE SMALL SINGLE FIXED | | GLASS WINDOWS IN THE BATHROOMS ( SAFETY GLAZING | | REQUIRED ). THE WINDOW SCHEDULE ON SHEET A3.0 HAS THIS | | PRODUCT APPROVAL LISTED WITH A PRESSURE OF +50 / -50 | | PSF. WINDOW 11F IS LISTED IN THE SCHEDULE ON A3.0 AND | | ON A1.3 WITH A REQUIRED PRESSURE OF +41.2 / -54.8 PSF | | WHICH EXCEEDS THE PRODUCT PRESSURES LISTED IN THE | | SCHEDULE. |
|