2014-12-15 09:19:34 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. THE CUMULATIVE LIFETIME IMPROVEMENTS FOR THIS | | STRUCTURE EXCEED 50% OF THE PROPERTY APPRAISER | | VALUATION ($406,802 LIFETIME IMPROVEMENTS, $628,274 | | PAPA VALUATION FOR 2014; 65%). THEREFORE, THIS IS | | CONSIDERED A "SUBSTANTIAL IMPROVEMENT" AND THE PROPERTY | | IS TO BE BROUGHT INTO COMPLIANCE. ALTERNATIVELY, | | APPLICANT MAY SUBMIT A CERTIFIED APPRAISAL. | | | | WPB ADMIN CODE 94-546(B)*), FBC 2010 EXISTING BUILDING | | 601.3. | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | 2. FBC 2010 EXISTING BUILDING 611.8, PROVIDE | | INFORMATION AS TO HOW YOU PROPOSE TO COMPLY WITH THIS | | SECTION (ROOF TO WALL CONNECTORS). | | | | |
|