2014-12-16 10:10:39PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE ROOFING SYSTEM
 SPECIFIED ON PAGE 14 OF NOA NO. 14-0224.03 IS -60 PSF.
 THIS IS NOT ADEQUATE FOR ALL OF THE ROOF AREAS. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED ROOF FASTENING AS REQUIRED BY GENERAL
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA.