2014-12-16 09:23:22 | 12/16/2014 |
| PROJECT: FARINO RESIDENCE |
| PERMIT#: 14120500 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED. |
| |
| FBC-WPB AMENDMENTS 107.3.5 |
| NO ELECTRICAL PLANS, DETAILS OR SPECIFICATIONS |
| PROVIDED. PROVIDE THE FOLLOWING FOR MINIMUM PLAN REVIEW |
| CRITERIA: |
| |
| 1) PROVIDE DETAILS FOR THE DEMOLITION PLAN TO INDICATE |
| THE FOLLOWING: |
| A. THE LOCATION OF THE ELECTRICAL SERVICE, ASSOCIATED |
| DISCONNECTS AND PANELS. |
| B. HOW THE ELECTRICAL DEMOLITION IS PROPOSED TO TAKE |
| PLACE. SUCH AS WHAT ELEMENTS ARE EXISTING TO REMAIN AND |
| WHAT IS TO BE REMOVED. |
| C. FOR THOSE ELECTRICAL ELEMENTS PROPOSED TO BE |
| REMOVED, INDICATE THE LOCATION THAT THE CIRCUIT OR |
| FEEDER IS PROPOSED TO TERMINATE. |
| |
| 2) PROVIDE DETAILS FOR THE NEW CONSTRUCTION TO INDICATE |
| THE FOLLOWING: |
| A. A DETAILED ELECTRICAL SERVICE RISER TO INCLUDE A |
| GROUNDING ELECTRODE SYSTEM, THE UTILITY METERING |
| DEVICE(S) SERVICE DISCONNECT(S), PANEL(S), AND ALL |
| CONDUIT AND WIRE SIZES FOR SERVICE ENTRANCE AND |
| FEEDERS. NEC 215.5 |
| B. A COMPLETE DETAILED LOAD CALCULATION. NEC 220 |
| C. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| SPECIFIC PURPOSE OR USE. NEC 408.4 |
| D. PROVIDE A COMPLETE FLOOR PLAN INDICATING ALL OUTLETS |
| AND LIGHTING AS REQUIRED BY THE 2008 EDITION OF THE |
| NATIONAL ELECTRICAL CODE AND THE 2010 EDITION OF THE |
| FBC 107.3.5, NEC 210.52 |
| E. ALL CIRCUITS NUMBERS IN THE PANEL DIRECTORIES TO BE |
| INDICATED ON THE FLLOOR PLAN. FBC-WPB AMENDMENTS |
| 107.3.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |