Plan Review Notes
Plan Review Notes For Permit 14120500
Permit Number 14120500
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-16 09:23:2212/16/2014
 PROJECT: FARINO RESIDENCE
 PERMIT#: 14120500
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 FBC-WPB AMENDMENTS 107.3.5
 NO ELECTRICAL PLANS, DETAILS OR SPECIFICATIONS
 PROVIDED. PROVIDE THE FOLLOWING FOR MINIMUM PLAN REVIEW
 CRITERIA:
  
 1) PROVIDE DETAILS FOR THE DEMOLITION PLAN TO INDICATE
 THE FOLLOWING:
 A. THE LOCATION OF THE ELECTRICAL SERVICE, ASSOCIATED
 DISCONNECTS AND PANELS.
 B. HOW THE ELECTRICAL DEMOLITION IS PROPOSED TO TAKE
 PLACE. SUCH AS WHAT ELEMENTS ARE EXISTING TO REMAIN AND
 WHAT IS TO BE REMOVED.
 C. FOR THOSE ELECTRICAL ELEMENTS PROPOSED TO BE
 REMOVED, INDICATE THE LOCATION THAT THE CIRCUIT OR
 FEEDER IS PROPOSED TO TERMINATE.
  
 2) PROVIDE DETAILS FOR THE NEW CONSTRUCTION TO INDICATE
 THE FOLLOWING:
 A. A DETAILED ELECTRICAL SERVICE RISER TO INCLUDE A
 GROUNDING ELECTRODE SYSTEM, THE UTILITY METERING
 DEVICE(S) SERVICE DISCONNECT(S), PANEL(S), AND ALL
 CONDUIT AND WIRE SIZES FOR SERVICE ENTRANCE AND
 FEEDERS. NEC 215.5
 B. A COMPLETE DETAILED LOAD CALCULATION. NEC 220
 C. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
 D. PROVIDE A COMPLETE FLOOR PLAN INDICATING ALL OUTLETS
 AND LIGHTING AS REQUIRED BY THE 2008 EDITION OF THE
 NATIONAL ELECTRICAL CODE AND THE 2010 EDITION OF THE
 FBC 107.3.5, NEC 210.52
 E. ALL CIRCUITS NUMBERS IN THE PANEL DIRECTORIES TO BE
 INDICATED ON THE FLLOOR PLAN. FBC-WPB AMENDMENTS
 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  